Knightsbridge T8000MHF Series Emergency Batten Instruction Manual

June 8, 2024
Knightsbridge

INSTALLATION & MAINTENANCE MANUAL
T8136EMHF / T8158EMHF
T8170EMHF / T8236EMHF
T8258EMHF / T8270EMHF

GENERAL INSTRUCTIONS

These instructions should be read carefully and retained after installation by the end user for future reference and maintenance. These instructions should be used to aid installation of the following products: T8136EMHF / T8158EMHF / T8170EMHF / T8236EMHF / T8258EMHF / T8270EMHF

SAFETY

  • This product must be installed in accordance with the latest edition of the IEE Wiring Regulations (BS7671) and current Building Regulations. If in any doubt, consult a qualified electrician
  • Please isolate mains prior to installation or maintenance
  • Check the total load on the circuit (including when this luminaire is fitted) does not exceed the rating of the circuit cable, fuse or circuit breaker
  • Please note the IP (Ingress Protection) rating of this product when deciding the location for installation
  • This product is for indoor use only
  • This product is Class I and must be earthed
  • This product is IP20 rated

INSTALLATION

  • Provide power to the required point of installation

  • Unfasten the two screws (see Fig. 1) and remove the cover plate

  • Mark the location of the fixing holes and drill the holes ensuring not to infringe with any gas/water pipes or electric·al cables

  • Feed the mains cable into the luminaire, either through the rear, or by drilling the end cap and using a 20mm compre·ssion gland (not included)

  • Secure the luminaire to the surface

  • Ensuring correct polarity is observed, carefully wire as shown in Fig. 2

  • Connect the battery to the inverter via the plug and socket connector

  • Fit the lamp holders into place at either end of the fitting and refasten the cover plate

  • Fit a suitable T8 fluorescent lamp

  • Switch on and check for correct operation ensuring the green indicator LED is illuminated

  • We recommend, on commissioning the installation, a minimum charge period of 24 hours before carrying out an emergency duration test

  • If the batteries have been left in a discharged state for an extended period, we recommend that one or more charge and discharge cycles are completed which should help to restore the battery capacity

WARNING

This product must be disconnected from the circuit if subjected to any high voltage or insulation resistance testing. Irreparable damage will occur if this instruction is not followed.

GENERAL

This product contains a control gear which can be replaced by a professional.

Clean with a soft dry cloth only, do not use aggressive cleaning products or solvents which may damage the product.
This product is non-dimmable.
This product should be dismantled for disposal when it reaches the end of its life. Please see website for dismantling instructions. This product should be recycled in the correct manner when it reaches the end of its life. Check local authorities for where facilities exist.
The batteries in this luminaire are Nickel Cadmium and must be disposed of correctly. Please contact the local authorities for the disposal of this toxic waste.

WARRANTY

This product has a warranty of 1 year (excluding battery) from date of purchase. Failure to install this product in accordance with the current edition of the IEE Wiring Regulations, improper use, or removal of the batch codes will invalidate the warranty. If this product should fail within its warranty period, it should be returned to the place of purchase for a free of charge replacement. ML Accessories does not accept responsibility for any installation costs associated with the replacement product. Your statutory rights are not affected. ML Accessories reserve the right to alter product specification without prior notice.

TESTING FOR EMERGENCY LUMINAIRES

Recommended routine test procedure in accordance with BS5266

  • Daily check ­ check LED charge indicator is illuminated
  • Monthly functional test – simulate a mains supply failure for approx. 30 seconds by operation of key switch or switching off circuit breaker. Ensure normal supply is restored after test and ensure charge indicator is illuminated
  • Annual 3-hour duration test – simulate a mains supply failure for 3-hour continuous test by operation of key switch or switching off circuit breaker. Ensure normal supply is restored after test and ensure charge indicator is illuminated
  • If the luminaire fails any of the above tests, please contact a qualified electrician. See below for test record sheet

TEST RECORD SHEET

INITIAL COMMISSIONING
3 HOUR TEST| SIGNED| DATE
---|---|---
|
MONTH| TEST| FIRST YEAR| SECOND YEAR| THIRD YEAR| FOURTH YEAR| FIFTH YEAR
SIGNED| DATE| SIGNED| DATE| SIGNED| DATE| SIGNED| DATE| SIGNED| DATE
1| FUNCTIONAL| | | | | | | | | |
2| FUNCTIONAL| | | | | | | | | |
3| FUNCTIONAL| | | | | | | | | |
4| FUNCTIONAL| | | | | | | | | |
5| FUNCTIONAL| | | | | | | | | |
6| FUNCTIONAL| | | | | | | | | |
7| FUNCTIONAL| | | | | | | | | |
8| FUNCTIONAL| | | | | | | | | |
9| FUNCTIONAL| | | | | | | | | |
10| FUNCTIONAL| | | | | | | | | |
11| FUNCTIONAL| | | | | | | | | |
12| 3 HOUR| | | | | | | | | |

Installed by: ___ Installation date: __ Contact number: __

INTERNATIONAL
CONTACT DETAILS

https://www.mlaccessories.co.uk/contact-us

ML Accessories Limited LU5 4LT
www.mlaccessories.co.uk
DCOCT21_V2

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Knightsbridge User Manuals

Related Manuals