Aeotec Inline Smart Energy Dimmer AEOEZW099 Manual

June 8, 2024
Aeotec

Table of Contents

Aeotec

Inline Smart Energy Dimmer

SKU: AEOEZW099

Quickstart

This is a
secure
Dimmer
for
Europe
.

To run this device please connect it to your mains power supply.

Inclusion and exclusion are started by pressing the action button once. The LED will flash continuously if the device is not part of a network yet. The Smart Dimmer” 6 supports normal and secure communication.

Important safety information

Please read this manual carefully. Failure to follow the recommendations in this manual may be dangerous or may violate the law.
The manufacturer, importer, distributor and seller shall not be liable for any loss or damage resulting from failure to comply with the instructions in this manual or any other material.
Use this equipment only for its intended purpose. Follow the disposal instructions.

Do not dispose of electronic equipment or batteries in a fire or near open heat sources.

What is Z-Wave?

Z-Wave is the international wireless protocol for communication in the Smart Home. This
device is suited for use in the region mentioned in the Quickstart section.

Z-Wave ensures a reliable communication by reconfirming every message ( two- way
communication
) and every mains powered node can act as a repeater for other nodes
( meshed network ) in case the receiver is not in direct wireless range of the
transmitter.

This device and every other certified Z-Wave device can be used together with any other
certified Z-Wave device regardless of brand and origin
as long as both are suited for the
same frequency range.

If a device supports secure communication it will communicate with other devices
secure as long as this device provides the same or a higher level of security.
Otherwise it will automatically turn into a lower level of security to maintain
backward compatibility.

For more information about Z-Wave technology, devices, white papers etc. please refer
to www.z-wave.info.

Product Description

The Smart Dimmer” 6 is an intelligent socket, which you can switch by remote, wall switch, smartphone or automation. Thanks to Z-Wave the Smart Dimmer 6 offers you much more than a conventional socket. The Smart Dimmer 6 is equipped with a premium energy monitoring, that provides the Z-Wave controller with real-time consumption data of the associated device. All data can be stored and redisplayed afterwards as progression charts. In addition, the coloured LED ring of the Smart Dimmer 6 displays the power requirements of the device in a visual way. The LED ring can be configured as follows:

  • Deactivated: The LED ring is permanently disabled
  • 2-coloured: Blue, if the monitored device is on; White if it”s switched off.
  • 16 Million Colours: The colours vary from blue to yellow, green and red (where blue is the lowest and red the highest energy consumption of the monitored device).

The Smart Dimmer” 6 is only 60 x 60 mm in size and 43% smaller than his predecessor – while being smarter and better. In the age of tablets, smartphones and many other devices that are charged via USB it is only obvious to equip the Smart Dimmer 6 with an USB port at the side. The Smart Switch 6 uses the latest Z-Wave 500 chip generation.

Prepare for Installation / Reset

Please read the user manual before installing the product.

In order to include (add) a Z-Wave device to a network it must be in factory default
state.
Please make sure to reset the device into factory default. You can do this by
performing an Exclusion operation as described below in the manual. Every Z-Wave
controller is able to perform this operation however it is recommended to use the primary
controller of the previous network to make sure the very device is excluded properly
from this network.

Reset to factory default

This device also allows to be reset without any involvement of a Z-Wave controller. This
procedure should only be used when the primary controller is inoperable.

1. Make sure the Smart Dimmer has been connected to the power supply.
2. Press and hold the Z-wave button for 20 seconds.
3. If holding time more than one second, the LED will blink faster and faster. If holding time more than 20seconds, the green LED will be on for 2 seconds and then remain colorful gradient status, it indicates reset success, otherwise please repeat step 2.

Safety Warning for Mains Powered Devices

ATTENTION: only authorized technicians under consideration of the country- specific
installation guidelines/norms may do works with mains power. Prior to the assembly of
the product, the voltage network has to be switched off and ensured against re-switching.

Installation

The Smart Dimmer” 6 can be placed between every normal wall socket and any electrical device with a load up to 3500W. To switch the connected device it is enough to press the action button or you can use your Z-Wave controller to send commands to your Smart Dimmer. The current status is indicated by the LED.

Inclusion/Exclusion

On factory default the device does not belong to any Z-Wave network. The device needs
to be added to an existing wireless network to communicate with the devices of this network.
This process is called Inclusion.

Devices can also be removed from a network. This process is called Exclusion.
Both processes are initiated by the primary controller of the Z-Wave network. This
controller is turned into exclusion respective inclusion mode. Inclusion and Exclusion is
then performed doing a special manual action right on the device.

Inclusion

Put the primary controller into inclusion mode. (For more information please read the controller”s manual.) Press the action button once. The LED will stay solid if the inclusion was successful.

Exclusion

Put the primary controller into inclusion mode. (For more information please read the controller”s manual.) Press the action button once. The LED will stay solid if the inclusion was successful.

Auto-Inclusion

Beside the standard inclusion this devices supports the so called auto inclusion.
Right after powering up the device remains in inclusion state and can be included by
(any) gateway without further actions on the device itself. The auto inclusion mode will
time out after some time.

Product Usage

The device can be can be controlled either by pressing the action button or sending commands from the Z-Wave Controller. A single press on the button switches between active and inactive.

The Smart Energy Switch monitors the current power and energy consumption in kWh and can send this information to your Z-Wave Controller. How or if the data is displayed depends on your Z-Wave Controller. For more information please look up the Controller”s manual.

Node Information Frame

The Node Information Frame (NIF) is the business card of a Z-Wave device. It contains
information about the device type and the technical capabilities. The inclusion and
exclusion of the device is confirmed by sending out a Node Information Frame.
Beside this it may be needed for certain network operations to send out a Node
Information Frame. To issue a NIF execute the following action:

Pressing the action button once sends a NIF (Node Information Frame).

Quick trouble shooting

Here are a few hints for network installation if things dont work as expected.

  1. Make sure a device is in factory reset state before including. In doubt exclude before include.
  2. If inclusion still fails, check if both devices use the same frequency.
  3. Remove all dead devices from associations. Otherwise you will see severe delays.
  4. Never use sleeping battery devices without a central controller.
  5. Dont poll FLIRS devices.
  6. Make sure to have enough mains powered device to benefit from the meshing

Association – one device controls an other device

Z-Wave devices control other Z-Wave devices. The relationship between one device
controlling another device is called association. In order to control a different
device, the controlling device needs to maintain a list of devices that will receive
controlling commands. These lists are called association groups and they are always
related to certain events (e.g. button pressed, sensor triggers, …). In case
the event happens all devices stored in the respective association group will
receive the same wireless command wireless command, typically a ‘Basic Set’ Command.

Association Groups:

Group NumberMaximum NodesDescription

1| 5| Group 1 is assigned to the Lifeline association group and every device has 5 nodes to associate.When the Dimmer is turned on or off using the action button, the Dimmer will send a basic report of its status to the nodes in association group 1. To change what kind of signal is sent to the nodes in group 1, please see the detailed description of configuration parameter 80.
---|---|---
2| 5| When the product receives a controlling Basic Set CC/Switch Multilevel Start Level Change/ Switch Multilevel Stop Level Change/ Switch Multilevel Set command, which if cause the products load state to be changed, which will lead to send the Basic Set CC//Switch Multilevel Start Level Change/ Switch Multilevel Stop Level Change/ Switch Multilevel Set command to nodes in group 2.

Configuration Parameters

Z-Wave products are supposed to work out of the box after inclusion, however
certain configuration can adapt the function better to user needs or unlock further
enhanced features.

IMPORTANT: Controllers may only allow configuring
signed values. In order to set values in the range 128 … 255 the value sent in
the application shall be the desired value minus 256. For example: To set a
parameter to 200 it may be needed to set a value of 200 minus 256 = minus 56.
In case of a two byte value the same logic applies: Values greater than 32768 may
needed to be given as negative values too.

Parameter 3: Current Overload Protection

This parameter is used for the overload protection, which means the load will be disconnected after 2 minutes when the current more than 14A.
Size: 1 Byte, Default Value: 0

SettingDescription

0 Overload Protection Disabled
1 Overload Protection is Enabled

Parameter 20: Configure the output load status after re-power on

Configure the output load status after re-power on the Smart Switch.
Size: 1 Byte, Default Value: 0

SettingDescription

0| The output load status will be the same as the previous state before a power outage.
---|---
1| The output load status will be ON state after re-power on.
2| The output load status will be OFF state after re-power on.

Parameter 33: Change the color value of RGB LED for testing

This parameter is only used for customer checking/testing the products RGB color via changing the RGB values.
Size: 4 Byte, Default Value: 0

SettingDescription

0 – 255 Reserved
255 – 65535 Range of red color value.
65536 – 16777215 Range of green color value.
16777215 – 2147483647 Range of blue color value.

Parameter 80: Enable/Disable to send notifications to associated devices

to associated devices.

This parameter is used to Enable/Disable to send notifications to associated devices (in Group 1) when the state of Smart Switch Gen5 load is changed.”
Size: 1 Byte, Default Value: 0

SettingDescription

0 Send Nothing (Disabled)
1 Send HAIL Command
2 Send BASIC Report Command

Parameter 81: Configure the state of LED

This parameter is used to configure the LED state when the Smart Switch is in Energy mode/Momentary indicate mode/Night light mode.
Size: 1 Byte, Default Value: 0

SettingDescription

0 The state of LED will follow with the output load state(Energy mode)
1 The state of LED will follow with the output load state, but will turn off

after 5 seconds if there is no any switch action.(Momentary indicate mode)
2| The state of LED will the same with Night light mode state configured by parameter 83.

Parameter 83: Configure the LED indication status when it is in Night

light mode

This parameter is used to configure the LED indication status when the current mode is Night light mode.
Size: 4 Byte, Default Value: 14524637

SettingDescription

0 – 255 Set the indication value of red Led.
256 – 65535 Set the indication value of green Led.
65536 – 16777215 Set the indication value of blue Led.

Parameter 84: Configure the brightness level for the LED indication

This parameter is used to configure the brightness level for the LED indication.Brightness level range is 0 to 100%.
Size: 1 Byte, Default Value: 50

SettingDescription

0 – 100 Brightness level range is 0 to 100%.

Parameter 90: Enable/Disable the function of parameter 91 and 92.

This parameter is used to Enable/Disable the function of parameter 91 and 92.
Size: 1 Byte, Default Value: 1

SettingDescription

0 Configuration Parameters 91 and 92 are Disabled
1 Configuration Parameters 91 and 92 are Enabled

Parameter 91: Induce an automatic report

This parameter is used to induce an automatic report when the change of the current power is more/less than the threshold in wattage.
Size: 2 Byte, Default Value: 25

SettingDescription

0 – 32767 The threshold can be set from 0 to 32767 watt.

Parameter 92: Induce an automatic report

This parameter is used to induce an automatic report when the change of the current power is more/less than the threshold in percentage.
Size: 1 Byte, Default Value: 5

SettingDescription

0 – 100 The threshold can be set from 0 to 100 percent.

Parameter 100: Reset Parameter 101 – 103

__
Size: 1 Byte, Default Value: 0

SettingDescription

1 Reset Parameter 101-103

Parameter 101: To set which report need to be sent.

This parameter is used to configure which reports need to be sent in Report Group 1.The values corresponding to the first four bits of the parameter value may be combined to create different combinations of reports that you wish to have sent. For example, instantaneous Current is the value 2 and instantaneous Watts is the value 4, so setting parameter 101 to a value of 6 will result in both instantaneous Current and instantaneous Watts to be reported. See the full description of the parameter values for other possible settings.
Size: 4 Byte, Default Value: 4

SettingDescription

1 Report Instantaneous Voltage
2 Report Instantaneous Current (Amperes)
4 Report Instantaneous Watts
8 Report Accumulated kWh

Parameter 102: To set which report need to be sent.

This parameter is used to configure which reports need to be sent in Report Group 2.The values corresponding to the first four bits of the parameter value may be combined to create different combinations of reports that you wish to have sent. For example, instantaneous Current is the value 2 and instantaneous Watts is the value 4, so setting parameter 102 to a value of 6 will result in both instantaneous Current and instantaneous Watts to be reported. See the full description of the parameter values for other possible settings.
Size: 4 Byte, Default Value: 8

SettingDescription

1 Report Instantaneous Voltage
2 Report Instantaneous Current (Amperes)
4 Report Instantaneous Watts
8 Report Accumulated kWh

Parameter 103: To set which report need to be sent.

This parameter is used to configure which reports need to be sent in Report Group 3.The values corresponding to the first four bits of the parameter value may be combined to create different combinations of reports that you wish to have sent. For example, instantaneous Current is the value 2 and instantaneous Watts is the value 4, so setting parameter 103 to a value of 6 will result in both instantaneous Current and instantaneous Watts to be reported. See the full description of the parameter values for other possible settings.
Size: 4 Byte, Default Value: 0

SettingDescription

1 Report Instantaneous Voltage
2 Report Instantaneous Current (Amperes)
4 Report Instantaneous Watts
8 Report Accumulated kWh

Parameter 110: Reset Parameter 111-113

__
Size: 1 Byte, Default Value: 0

SettingDescription

1 Reset Parameter 111-113

Parameter 111: Set the interval time of sending report.

This parameter is used to set the interval time of sending report in Report Group 1.”
Size: 4 Byte, Default Value: 600

SettingDescription

0 – 268435456 Interval Seconds

Parameter 112: Set the interval time of sending report.

This parameter is used to set the interval time of sending report in Report Group 2.”
Size: 4 Byte, Default Value: 600

SettingDescription

0 – 268435456 Interval Seconds

Parameter 113: Set the interval time of sending report.

This parameter is used to set the interval time of sending report in Report Group 3.
Size: 4 Byte, Default Value: 600

SettingDescription

0 – 268435456 Interval Seconds

Parameter 200: Partner ID

This parameter is used to configure the partner ID.”
Size: 1 Byte, Default Value: 0

SettingDescription

0 Aeon Labs Standard Product
1 – 255 Partner ID of Partner Product

Parameter 252: Enable/Disable Lock Configuration

This parameter is used to enable/disable Lock all configuration parameters.
Size: 1 Byte, Default Value: 0

SettingDescription

0 All configuration parameters are configurable.
1 All configuration parameters are not configurable (Locked).

Parameter 254: Device Tag

This parameter is used to save the device tag, which will be written/ assigned in factory/ manufacturer.
Size: 2 Byte, Default Value: 0

SettingDescription

0 – 32767 Device Tag

Parameter 255: Reset to default factory setting

This parameter is used to reset product to default factory setting. (There are just 2 values can be used).
Size: 4 Byte, Default Value: 0

SettingDescription

1 Resets all configuration parameters to default setting.
1431655765 Reset the product to default factory setting and be excluded from

the Z-wave network.

Technical Data

Hardware Platform ZM5101
IP Class IP 20
Voltage 230 V
Load 2,5 A
Device Type Dimmer
Generic Device Class Multilevel Switch
Specific Device Class Routing Multilevel Switch
Firmware Version 01.02
Z-Wave Version 04.05
Z-Wave Product Id 0x0086.0x0003.0x0063
Frequency Europe – 868,4 Mhz
Maximum transmission power 5 mW

Supported Command Classes

  • Basic
  • Switch Multilevel
  • Switch All
  • Meter
  • Switch Color
  • Association Grp Info
  • Multi Channel
  • Configuration
  • Powerlevel
  • Firmware Update Md
  • Clock
  • Association
  • Version
  • Multi Channel Association
  • Security
  • Zwaveplus Info
  • Manufacturer Specific
  • Device Reset Locally
  • Hail

Controlled Command Classes

  • Device Reset Locally
  • Hail

Explanation of Z-Wave specific terms

  • Controller — is a Z-Wave device with capabilities to manage the network.
    Controllers are typically Gateways,Remote Controls or battery operated wall controllers.

  • Slave — is a Z-Wave device without capabilities to manage the network.
    Slaves can be sensors, actuators and even remote controls.

  • Primary Controller — is the central organizer of the network. It must be
    a controller. There can be only one primary controller in a Z-Wave network.

  • Inclusion — is the process of adding new Z-Wave devices into a network.

  • Exclusion — is the process of removing Z-Wave devices from the network.

  • Association — is a control relationship between a controlling device and
    a controlled device.

  • Wakeup Notification — is a special wireless message issued by a Z-Wave
    device to announces that is able to communicate.

  • Node Information Frame — is a special wireless message issued by a
    Z-Wave device to announce its capabilities and functions.

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals