HELTUN Fan Coil Thermostat HE-FT01 Manual
- June 8, 2024
- HELTUN
Table of Contents
- HELTUN
- Fan Coil Thermostat
- SKU: HE-FT01
- Quickstart
- Important safety information
- What is Z-Wave?
- Product Description
- Prepare for Installation / Reset
- Inclusion/Exclusion
- Quick trouble shooting
- Association – one device controls an other device
- Configuration Parameters
- Parameter 1: TIME CORRECTION
- Parameter 10: MANUAL BRIGHTNESS
- Parameter 11: TOUCH THRESHOLD
- Parameter 12: RESERVED
- Parameter 13: RESERVED
- Parameter 14: BASIC SET MODE
- Parameter 15: RESERVED
- Parameter 16: RESERVED
- Parameter 17: RESERVED
- Parameter 18: RESERVED
- Parameter 19: RESERVED
- Parameter 2: TIME FORMAT
- Parameter 20: RESERVED
- Parameter 21: RESERVED
- Parameter 22: RESERVED
- Parameter 23: RESERVED
- Parameter 24: RESERVED
- Parameter 25: RESERVED
- Parameter 26: RESERVED
- Parameter 27: RESERVED
- Parameter 28: RESERVED
- Parameter 29: RESERVED
- Parameter 3: WEEKDAY
- Parameter 30: RESERVED
- Parameter 31: SENSORS REPORT TIME
- Parameter 32: CONSUMPTION REPORT TIME
- Parameter 33: TEMPERATURE THRESHOLD
- Parameter 34: HUMIDITY THRESHOLD
- Parameter 35: LIGHT THRESHOLD
- Parameter 36: OUT1 LOAD
- Parameter 37: OUT-2 LOAD
- Parameter 38: OUT3 LOAD
- Parameter 39: OUT4 LOAD
- Parameter 4: HOUR
- Parameter 40: OUT5 LOAD
- Parameter 41: TIME MODE OPERATION
- Parameter 42: MORNING START TIME
- Parameter 43: DAY START TIME
- Parameter 44: EVENING START TIME
- Parameter 45: NIGHT START TIME
- Parameter 46: MONDAY MORNING TEMP
- Parameter 47: MONDAY DAYTIME TEMP
- Parameter 48: MONDAY EVENING TEMP
- Parameter 49: MONDAY NIGHT TEMP
- Parameter 5: MINUTE
- Parameter 50: TUESDAY MORNING TEMP
- Parameter 51: TUESDAY DAYTIME TEMP
- Parameter 52: TUESDAY EVENING TEMP
- Parameter 53: TUESDAY NIGHT TEMP
- Parameter 54: WEDNESDAY MORNING TEMP
- Parameter 55: WEDNESDAY DAYTIME TEMP
- Parameter 56: WEDNESDAY EVENING TEMP
- Parameter 57: WEDNESDAY NIGHT TEMP
- Parameter 58: THURSDAY MORNING TEMP
- Parameter 59: THURSDAY DAYTIME TEMP
- Parameter 6: DEGREE MODE
- Parameter 60: THURSDAY EVENING TEMP
- Parameter 61: THURSDAY NIGHT TEMP
- Parameter 62: FRIDAY MORNING TEMP
- Parameter 63: FRIDAY DAYTIME TEMP
- Parameter 64: FRIDAY EVENING TEMP
- Parameter 65: FRIDAY NIGHT TEMP
- Parameter 66: SATURDAY MORNING TEMP
- Parameter 67: SATURDAY DAYTIME TEMP
- Parameter 68: SATURDAY EVENING TEMP
- Parameter 69: SATURDAY NIGHT TEMP
- Parameter 7: AIR TEMP CORRECTION
- Parameter 70: SUNDAY MORNING TEMP
- Parameter 71: SUNDAY DAYTIME TEMP
- Parameter 72: SUNDAY EVENING TEMP
- Parameter 73: SUNDAY NIGHT TEMP
- Parameter 8: TEMP HYSTERESYS
- Parameter 9: AUTO BRIGHTNESS
- Technical Data
- Supported Command Classes
- Explanation of Z-Wave specific terms
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
HELTUN
Fan Coil Thermostat
SKU: HE-FT01
Quickstart
This is a
secure
HVAC-Thermostat
for
.
To run this device please connect it to your mains power supply.
Important safety information
Please read this manual carefully. Failure to follow the recommendations in
this manual may be dangerous or may violate the law.
The manufacturer, importer, distributor and seller shall not be liable for any
loss or damage resulting from failure to comply with the instructions in this
manual or any other material.
Use this equipment only for its intended purpose. Follow the disposal
instructions.
Do not dispose of electronic equipment or batteries in a fire or near open heat sources.
What is Z-Wave?
Z-Wave is the international wireless protocol for communication in the Smart
Home. This
device is suited for use in the region mentioned in the Quickstart section.
Z-Wave ensures a reliable communication by reconfirming every message ( two-
way
communication) and every mains powered node can act as a repeater for other
nodes
( meshed network ) in case the receiver is not in direct wireless range of
the
transmitter.
This device and every other certified Z-Wave device can be used together
with any other
certified Z-Wave device regardless of brand and origin as long as both are
suited for the
same frequency range.
If a device supports secure communication it will communicate with other
devices
secure as long as this device provides the same or a higher level of security.
Otherwise it will automatically turn into a lower level of security to
maintain
backward compatibility.
For more information about Z-Wave technology, devices, white papers etc.
please refer
to www.z-wave.info.
Product Description
The HE-FT01 is HELTUNs advanced programmable Z-Wave thermostat for heating/cooling systems such as fan coil units, floor convectors, and wall, window, or ceiling mounted air conditioning units. The HE-FT01 thermostat is impossibly thin on the wall while still being packed full of features, delivering highly accurate comfort control through proprietary technology and four built-in sensors. You can monitor and control the HE-FT01 from anywhere in the world using a Z-Wave hub and your smartphone. And because it uses Z-Wave Plus version 2, Smart Start, S2 Security and 700 platform technologies, the HE-FT01 can be placed up to 100 meters away from the hub and is a snap to install. Best of all, the built-in Power Consumption System precisely monitors how much energy you used during any particular day, week or month, helping you save money on energy costs while staying comfortable all year long.The HELTUN HE-FT01 is part of an entire line of smart, connected products designed to provide the best technology has to offer without compromising stylish living. (hub and smartphone not included)
Prepare for Installation / Reset
Please read the user manual before installing the product.
In order to include (add) a Z-Wave device to a network it must be in factory
default
state. Please make sure to reset the device into factory default. You can do
this by
performing an Exclusion operation as described below in the manual. Every
Z-Wave
controller is able to perform this operation however it is recommended to use
the primary
controller of the previous network to make sure the very device is excluded
properly
from this network.
Safety Warning for Mains Powered Devices
ATTENTION: only authorized technicians under consideration of the country-
specific
installation guidelines/norms may do works with mains power. Prior to the
assembly of
the product, the voltage network has to be switched off and ensured against
re-switching.
Inclusion/Exclusion
On factory default the device does not belong to any Z-Wave network. The
device needs
to be added to an existing wireless network to communicate with the
devices of this network.
This process is called Inclusion.
Devices can also be removed from a network. This process is called
Exclusion.
Both processes are initiated by the primary controller of the Z-Wave network.
This
controller is turned into exclusion respective inclusion mode. Inclusion and
Exclusion is
then performed doing a special manual action right on the device.
Quick trouble shooting
Here are a few hints for network installation if things dont work as expected.
- Make sure a device is in factory reset state before including. In doubt exclude before include.
- If inclusion still fails, check if both devices use the same frequency.
- Remove all dead devices from associations. Otherwise you will see severe delays.
- Never use sleeping battery devices without a central controller.
- Dont poll FLIRS devices.
- Make sure to have enough mains powered device to benefit from the meshing
Association – one device controls an other device
Z-Wave devices control other Z-Wave devices. The relationship between one
device
controlling another device is called association. In order to control a
different
device, the controlling device needs to maintain a list of devices that will
receive
controlling commands. These lists are called association groups and they are
always
related to certain events (e.g. button pressed, sensor triggers, …). In case
the event happens all devices stored in the respective association group will
receive the same wireless command wireless command, typically a ‘Basic Set’
Command.
Association Groups:
Group NumberMaximum NodesDescription
1| 1| This is the Lifeline Group 1 which sends status (lifeline) reports to
the primary controller.
---|---|---
2| 1| Fan Low Speed (OUT-1) is used to turn the associated devices on/off
reflecting OUT-1 operation.
3| 1| Fan Medium Speed (OUT-2) is used to turn the associated devices on/off
reflecting OUT-2 operation.
4| 1| Fan High Speed (OUT-3) is used to turn the associated devices on/off
reflecting OUT-3 operation.
5| 1| Heater (OUT-4) is used to turn the associated devices on/off reflecting
OUT-4 operation.
6| 1| Cooler (OUT-5) is used to turn the associated devices on/off reflecting
OUT-5 operation.
Configuration Parameters
Z-Wave products are supposed to work out of the box after inclusion, however
certain configuration can adapt the function better to user needs or unlock
further
enhanced features.
IMPORTANT: Controllers may only allow configuring
signed values. In order to set values in the range 128 … 255 the value sent in
the application shall be the desired value minus 256. For example: To set a
parameter to 200 it may be needed to set a value of 200 minus 256 = minus
56.
In case of a two byte value the same logic applies: Values greater than 32768
may
needed to be given as negative values too.
Parameter 1: TIME CORRECTION
Time correction by controller
Size: 1 Byte, Default Value: 1
SettingDescription
0 | Switch off auto-correction |
---|---|
1 – 0 | If thermostat is connected to a Z-Wave gateway, the time and day will |
be periodically polled and corrected from the gateway
Parameter 10: MANUAL BRIGHTNESS
Display manual brightness level.The Display Brightness Level Parameter will
take effect when Parameter 22 is set to Manual Control (value = 0). Note: The
environment illumination is displayed in the TIME position and also can be
checked at any time via a Z-Wave gateway.
Size: 1 Byte, Default Value: 10
SettingDescription
1 – 15| The LCD brightness may be adjusted from 1 (lowest brightness) to 15
(highest brightest).
---|---
Parameter 11: TOUCH THRESHOLD
Touch buttons sensitivity. 5 = Highly sensitive. 50 = Lowest sensitivity.
Note: Setting the sensitivity too high can lead to false touch detection. We
recommend not changing this Parameter unless there is a need to do so.
Size: 1 Byte, Default Value: 15
SettingDescription
5 – 50| Threshold to be adjusted from level 5 (very sensitive) to 50 (minimal
sensitivity).
---|---
Parameter 12: RESERVED
Parameter reserved by the manufacturer. Setting this parameter will have no
impact on DUT functionality.
Size: 1 Byte, Default Value: 0
SettingDescription
0 – 1| Parameter reserved by the manufacturer. Setting this parameter will
have no impact on DUT functionality.
---|---
Parameter 13: RESERVED
Parameter reserved by the manufacturer. Setting this parameter will have no
impact on DUT functionality.
Size: 1 Byte, Default Value: 0
SettingDescription
0 – 1| Parameter reserved by the manufacturer. Setting this parameter will
have no impact on DUT functionality.
---|---
Parameter 14: BASIC SET MODE
Mode to switch to on Basic Set Action command This Parameter defines which
Operating Mode the HE-FT01 reverts to if the Basic Set command is received. If
the Basic Set command value is 0 (OFF state) the HE-FT01 will go to OFF mode
and switch the operating state to IDLE. If the Basic Set command value is 0xFF
(ON state) the HE-FT01 will change the Mode to the corresponding Parameter
value.
Size: 1 Byte, Default Value: 2
SettingDescription
0 | No action |
---|---|
1 – 0 | COM with Heating & Cooling Climate Mode |
2 – 0 | COM with Heating Climate Mode |
3 – 0 | COM with Cooling Climate Mode |
4 – 0 | TIME with Heating & Cooling Climate Mode |
5 – 0 | TIME with Heating Climate Mode |
6 – 0 | TIME with Cooling Climate Mode |
7 – 0 | ECO with Heating Climate Mode |
8 – 0 | ECO with Cooling Climate Mode |
9 – 0 | Ventilation Climate Mode |
Parameter 15: RESERVED
Parameter reserved by the manufacturer. Setting this parameter will have no
impact on DUT functionality.
Size: 1 Byte, Default Value: 0
SettingDescription
0 – 1| Parameter reserved by the manufacturer. Setting this parameter will
have no impact on DUT functionality.
---|---
Parameter 16: RESERVED
Parameter reserved by the manufacturer. Setting this parameter will have no
impact on DUT functionality.
Size: 1 Byte, Default Value: 0
SettingDescription
0 – 1| Parameter reserved by the manufacturer. Setting this parameter will
have no impact on DUT functionality.
---|---
Parameter 17: RESERVED
Parameter reserved by the manufacturer. Setting this parameter will have no
impact on DUT functionality.
Size: 1 Byte, Default Value: 0
SettingDescription
0 – 1| Parameter reserved by the manufacturer. Setting this parameter will
have no impact on DUT functionality.
---|---
Parameter 18: RESERVED
Parameter reserved by the manufacturer. Setting this parameter will have no
impact on DUT functionality.
Size: 1 Byte, Default Value: 0
SettingDescription
0 – 1| Parameter reserved by the manufacturer. Setting this parameter will
have no impact on DUT functionality.
---|---
Parameter 19: RESERVED
Parameter reserved by the manufacturer. Setting this parameter will have no
impact on DUT functionality.
Size: 1 Byte, Default Value: 0
SettingDescription
0 – 1| Parameter reserved by the manufacturer. Setting this parameter will
have no impact on DUT functionality.
---|---
Parameter 2: TIME FORMAT
Time format
Size: 1 Byte, Default Value: 1
SettingDescription
0 | 24 hour format |
---|---|
1 – 0 | 12 hour (AM/PM) format |
Parameter 20: RESERVED
Parameter reserved by the manufacturer. Setting this parameter will have no
impact on DUT functionality.
Size: 1 Byte, Default Value: 0
SettingDescription
0 – 1| Parameter reserved by the manufacturer. Setting this parameter will
have no impact on DUT functionality.
---|---
Parameter 21: RESERVED
Parameter reserved by the manufacturer. Setting this parameter will have no
impact on DUT functionality.
Size: 1 Byte, Default Value: 0
SettingDescription
0 – 1| Parameter reserved by the manufacturer. Setting this parameter will
have no impact on DUT functionality.
---|---
Parameter 22: RESERVED
Parameter reserved by the manufacturer. Setting this parameter will have no
impact on DUT functionality.
Size: 1 Byte, Default Value: 0
SettingDescription
0 – 1| Parameter reserved by the manufacturer. Setting this parameter will
have no impact on DUT functionality.
---|---
Parameter 23: RESERVED
Parameter reserved by the manufacturer. Setting this parameter will have no
impact on DUT functionality.
Size: 1 Byte, Default Value: 0
SettingDescription
0 – 1| Parameter reserved by the manufacturer. Setting this parameter will
have no impact on DUT functionality.
---|---
Parameter 24: RESERVED
Parameter reserved by the manufacturer. Setting this parameter will have no
impact on DUT functionality.
Size: 1 Byte, Default Value: 0
SettingDescription
0 – 1| Parameter reserved by the manufacturer. Setting this parameter will
have no impact on DUT functionality.
---|---
Parameter 25: RESERVED
Parameter reserved by the manufacturer. Setting this parameter will have no
impact on DUT functionality.
Size: 1 Byte, Default Value: 0
SettingDescription
0 – 1| Parameter reserved by the manufacturer. Setting this parameter will
have no impact on DUT functionality.
---|---
Parameter 26: RESERVED
Parameter reserved by the manufacturer. Setting this parameter will have no
impact on DUT functionality.
Size: 1 Byte, Default Value: 0
SettingDescription
0 – 1| Parameter reserved by the manufacturer. Setting this parameter will
have no impact on DUT functionality.
---|---
Parameter 27: RESERVED
Parameter reserved by the manufacturer. Setting this parameter will have no
impact on DUT functionality.
Size: 1 Byte, Default Value: 0
SettingDescription
0 – 1| Parameter reserved by the manufacturer. Setting this parameter will
have no impact on DUT functionality.
---|---
Parameter 28: RESERVED
Parameter reserved by the manufacturer. Setting this parameter will have no
impact on DUT functionality.
Size: 1 Byte, Default Value: 0
SettingDescription
0 – 1| Parameter reserved by the manufacturer. Setting this parameter will
have no impact on DUT functionality.
---|---
Parameter 29: RESERVED
Parameter reserved by the manufacturer. Setting this parameter will have no
impact on DUT functionality.
Size: 1 Byte, Default Value: 0
SettingDescription
0 – 1| Parameter reserved by the manufacturer. Setting this parameter will
have no impact on DUT functionality.
---|---
Parameter 3: WEEKDAY
Week day. This parameter allows manually adjustment of the day of the week
in case if the thermostat is not connected to any Z-Wave gateway or Parameter
09 (auto-correction) is selected as 0.
Size: 1 Byte, Default Value: 1
SettingDescription
1 – 0 | Monday |
---|---|
2 – 0 | Tuesday |
3 – 0 | Wednesday |
4 – 0 | Thursday |
5 – 0 | Friday |
6 – 0 | Saturday |
7 – 0 | Sunday |
Parameter 30: RESERVED
Parameter reserved by the manufacturer. Setting this parameter will have no
impact on DUT functionality.
Size: 1 Byte, Default Value: 0
SettingDescription
0 – 1| Parameter reserved by the manufacturer. Setting this parameter will
have no impact on DUT functionality.
---|---
Parameter 31: SENSORS REPORT TIME
Sensors consecutive reporting interval, minutes.When the device is connected
to the Z-Wave gateway (controller), it periodically sends to the gateway
reports from its room & floor temperature, humidity and light sensors even if
there are not changes in the values. This Parameter defines the interval
between consecutive reports. The value can be adjusted from 1 min to 120
min.Note: If the sensor readings change, the device will send the report to
the gateway regardless of this parameter value. In order not to increase
traffic on your network, it is not recommended to reduce the value of this
parameter. We recommend to reduce the value of this parameter only in case of
poor connection, when reports from the device does not always reach the
gateway.
Size: 1 Byte, Default Value: 10
SettingDescription
1 – 120 | The value can be adjusted from 1 to 120 minutes |
---|
Parameter 32: CONSUMPTION REPORT TIME
This Parameter defines the interval (in minutes) between consecutive reports
of real time and cumulative energy consumption data to the gateway. The value
can be adjusted from 1 min to 120 min. The factory default value is 10 min.
Note: If the sensor readings change, the device will send the report to the
gateway regardless of this parameter value. In order to not increase traffic
on your network, we recommend not reducing this value.
Size: 1 Byte, Default Value: 10
SettingDescription
1 – 120 | Consumption meter consecutive reporting interval in minutes. |
---|
Parameter 33: TEMPERATURE THRESHOLD
Temperature difference to send to controller, value x10. This parameter
determines the change in temperature level (in C) resulting in temperature
sensors report being sent to the gateway. The value of this parameter should
be x10, e.g. for 0.4C use value 40. From 0.5C to 10C can be selected. The
factory default value is 0.5C (5).
Size: 1 Byte, Default Value: 5
SettingDescription
0 | Stop sending the reports |
---|---|
5 – 100 | Temperature level difference (in C), value x10. |
Parameter 34: HUMIDITY THRESHOLD
This parameter determines the percentage change in relative humidity level
which will trigger a report being sent to the gateway. From 2% to 25% can be
selected.
Size: 1 Byte, Default Value: 2
SettingDescription
0 | Stop sending the reports |
---|---|
2 – 25 | Humidity level difference in % |
Parameter 35: LIGHT THRESHOLD
This parameter determines the change in the ambient illumination level that
will trigger a report being sent to the gateway.
Size: 1 Byte, Default Value: 50
SettingDescription
0 | Stop sending the reports |
---|---|
10 – 99 | Light sensor values difference |
Parameter 36: OUT1 LOAD
Power of the Relay 1 load in W. It is possible to specify the consumption of
the loads in watts for each relays channel. The device will calculate total
consumption relative to the time, during which the output of the relays is in
the ON state.
Size: 2 Byte, Default Value: 0
SettingDescription
0 – 5000 | Power of the Relay 1 load in W |
---|
Parameter 37: OUT-2 LOAD
Power of the Relay 2 load in W. It is possible to specify the consumption of
the loads in watts for each relays channel. The device will calculate total
consumption relative to the time, during which the output of the relays is in
the ON state.
Size: 2 Byte, Default Value: 0
SettingDescription
0 – 5000 | Power of the Relay 2 load in W |
---|
Parameter 38: OUT3 LOAD
Power of the Relay 3 load in W.It is possible to specify the consumption of
the loads in watts for each relays channel. The device will calculate total
consumption relative to the time, during which the output of the relays is in
the ON state.
Size: 2 Byte, Default Value: 0
SettingDescription
0 – 5000 | Power of the Relay 3 load in W |
---|
Parameter 39: OUT4 LOAD
Power of the Relay 4 load in W.It is possible to specify the consumption of
the loads in watts for each relays channel. The device will calculate total
consumption relative to the time, during which the output of the relays is in
the ON state.
Size: 2 Byte, Default Value: 0
SettingDescription
0 – 5000 | Power of the Relay 4 load in W |
---|
Parameter 4: HOUR
This Parameter allows manual adjustment of Time in hours (24 hours).
Size: 1 Byte, Default Value: 0
SettingDescription
0 – 23 | Manual adjustment of time hours (24 hours). |
---|
Parameter 40: OUT5 LOAD
Power of the Relay 5 load in W.It is possible to specify the consumption of
the loads in watts for each relays channel. The device will calculate total
consumption relative to the time, during which the output of the relays is in
the ON state.
Size: 2 Byte, Default Value: 0
SettingDescription
0 – 5000 | Power of the Relay 5 load in W |
---|
Parameter 41: TIME MODE OPERATION
This parameter determines the Climate Mode (Heating or Cooling) to which HE-
FT01 will switch when the TIME operating mode is selected.
Size: 1 Byte, Default Value: 1
SettingDescription
1 – 0 | The thermostat will go to Heating & Cooling mode |
---|---|
2 – 0 | The thermostat goes to Heating mode |
3 – 0 | The thermostat goes to Cooling Mode |
Parameter 42: MORNING START TIME
Morning start time for the Temperature Schedules. Format: HHMM. e.g.08:00
should be sent as 0800.
Size: 2 Byte, Default Value: 600
SettingDescription
0 – 2359 | Morning start time. Format: HHMM (from 00:00 to 23:59) |
---|
Parameter 43: DAY START TIME
Day start time for the Temperature Schedules. Format: HHMM. e.g.08:00 should
be sent as 0800.
Size: 2 Byte, Default Value: 900
SettingDescription
0 – 2359 | Day start time. Format: HHMM (from 00:00 to 23:59) |
---|
Parameter 44: EVENING START TIME
Evening start time for the Temperature Schedules. Format: HHMM. e.g.08:00
should be sent as 0800.
Size: 2 Byte, Default Value: 1800
SettingDescription
0 – 2359 | Evening start time. Format: HHMM (from 00:00 to 23:59) |
---|
Parameter 45: NIGHT START TIME
Night start time for the Temperature Schedules. Format: HHMM. e.g.08:00
should be sent as 0800.
Size: 2 Byte, Default Value: 2300
SettingDescription
0 – 2359 | Night start time. Format: HHMM (from 00:00 to 23:59) |
---|
Parameter 46: MONDAY MORNING TEMP
Monday Morning temperature, valueX10
Size: 2 Byte, Default Value: 240
SettingDescription
40 – 370 | Monday Morning temperature value |
---|
Parameter 47: MONDAY DAYTIME TEMP
Monday Day temperature, valueX10
Size: 2 Byte, Default Value: 200
SettingDescription
40 – 370 | Monday Day temperature value |
---|
Parameter 48: MONDAY EVENING TEMP
Monday Evening temperature, valueX10
Size: 2 Byte, Default Value: 230
SettingDescription
40 – 370 | Monday Evening temperature value |
---|
Parameter 49: MONDAY NIGHT TEMP
Monday Night temperature, valueX10
Size: 2 Byte, Default Value: 180
SettingDescription
40 – 370 | Monday Night temperature value |
---|
Parameter 5: MINUTE
This Parameter allows manual adjustment of the Time in minutes (60
minutes))
Size: 1 Byte, Default Value: 0
SettingDescription
0 – 59 | Manual adjustment of time minutes (60 minutes) |
---|
Parameter 50: TUESDAY MORNING TEMP
Tuesday Morning temperature, valueX10
Size: 2 Byte, Default Value: 240
SettingDescription
40 – 370 | Tuesday Morning temperature value |
---|
Parameter 51: TUESDAY DAYTIME TEMP
Tuesday Day temperature, valueX10
Size: 2 Byte, Default Value: 200
SettingDescription
40 – 370 | Tuesday Day temperature value |
---|
Parameter 52: TUESDAY EVENING TEMP
Tuesday Evening temperature, valueX10
Size: 2 Byte, Default Value: 230
SettingDescription
40 – 370 | Tuesday Evening temperature value |
---|
Parameter 53: TUESDAY NIGHT TEMP
Tuesday Night temperature, valueX10
Size: 2 Byte, Default Value: 180
SettingDescription
40 – 370 | Tuesday Night temperature value |
---|
Parameter 54: WEDNESDAY MORNING TEMP
Wednesday Morning temperature, valueX10
Size: 2 Byte, Default Value: 240
SettingDescription
40 – 370 | Wednesday Morning temperature value |
---|
Parameter 55: WEDNESDAY DAYTIME TEMP
Wednesday Day temperature, valueX10
Size: 2 Byte, Default Value: 200
SettingDescription
40 – 370 | Wednesday Day temperature value |
---|
Parameter 56: WEDNESDAY EVENING TEMP
Wednesday Evening temperature, valueX10
Size: 2 Byte, Default Value: 230
SettingDescription
40 – 370 | Wednesday Evening temperature value |
---|
Parameter 57: WEDNESDAY NIGHT TEMP
Wednesday Night temperature, valueX10
Size: 2 Byte, Default Value: 180
SettingDescription
40 – 370 | Wednesday Night temperature value |
---|
Parameter 58: THURSDAY MORNING TEMP
Thursday Morning temperature, valueX10
Size: 2 Byte, Default Value: 240
SettingDescription
40 – 370 | Thursday Morning temperature value |
---|
Parameter 59: THURSDAY DAYTIME TEMP
Thursday Day temperature, valueX10
Size: 2 Byte, Default Value: 200
SettingDescription
40 – 370 | Thursday Day temperature value |
---|
Parameter 6: DEGREE MODE
Degree mode (C/F)Floor and air temperature, as well as Set Point and all
Parameters will be indicated in the chosen mode. Factory default value is
degrees Celsius (0).
Size: 1 Byte, Default Value: 0
SettingDescription
0 | Celsius |
---|---|
1 – 0 | Fahrenheit |
Parameter 60: THURSDAY EVENING TEMP
Thursday Evening temperature, valueX10
Size: 2 Byte, Default Value: 230
SettingDescription
40 – 370 | Thursday Evening temperature value |
---|
Parameter 61: THURSDAY NIGHT TEMP
Thursday Night temperature, valueX10
Size: 2 Byte, Default Value: 180
SettingDescription
40 – 370 | Thursday Night temperature value |
---|
Parameter 62: FRIDAY MORNING TEMP
Friday Morning temperature, valueX10
Size: 2 Byte, Default Value: 240
SettingDescription
40 – 370 | Friday Morning temperature value |
---|
Parameter 63: FRIDAY DAYTIME TEMP
Friday Day temperature, valueX10
Size: 2 Byte, Default Value: 200
SettingDescription
40 – 370 | Friday Day temperature value |
---|
Parameter 64: FRIDAY EVENING TEMP
Friday Evening temperature, valueX10
Size: 2 Byte, Default Value: 230
SettingDescription
40 – 370 | Friday Evening temperature value |
---|
Parameter 65: FRIDAY NIGHT TEMP
Friday Night temperature, valueX10
Size: 2 Byte, Default Value: 180
SettingDescription
40 – 370 | Friday Night temperature value |
---|
Parameter 66: SATURDAY MORNING TEMP
Saturday Morning temperature, valueX10
Size: 2 Byte, Default Value: 240
SettingDescription
40 – 370 | Saturday Morning temperature value |
---|
Parameter 67: SATURDAY DAYTIME TEMP
Saturday Day temperature, valueX10
Size: 2 Byte, Default Value: 200
SettingDescription
40 – 370 | Saturday Day temperature value |
---|
Parameter 68: SATURDAY EVENING TEMP
Saturday Evening temperature, valueX10
Size: 2 Byte, Default Value: 230
SettingDescription
40 – 370 | Saturday Evening temperature value |
---|
Parameter 69: SATURDAY NIGHT TEMP
Saturday Night temperature, valueX10
Size: 2 Byte, Default Value: 180
SettingDescription
40 – 370 | Saturday Night temperature value |
---|
Parameter 7: AIR TEMP CORRECTION
This Parameter defines the offset value for room air temperature. If the
internal air temperature sensor is not correctly calibrated, then manual
calibration can be accomplished by adjusting the values up to 9.5C (17F). This
value will be added or subtracted from the internal air temperature sensor
reading.
Size: 1 Byte, Default Value: 0
SettingDescription
-95 – 95 | Air temperature offset value (C x 10) |
---|
Parameter 70: SUNDAY MORNING TEMP
Sunday Morning temperature, valueX10
Size: 2 Byte, Default Value: 240
SettingDescription
40 – 370 | Sunday Morning temperature value |
---|
Parameter 71: SUNDAY DAYTIME TEMP
Sunday Day temperature, valueX10
Size: 2 Byte, Default Value: 200
SettingDescription
40 – 370 | Sunday Day temperature value |
---|
Parameter 72: SUNDAY EVENING TEMP
Sunday Evening temperature, valueX10
Size: 2 Byte, Default Value: 230
SettingDescription
40 – 370 | Sunday Evening temperature value |
---|
Parameter 73: SUNDAY NIGHT TEMP
Sunday Night temperature, valueX10
Size: 2 Byte, Default Value: 180
SettingDescription
40 – 370 | Sunday Night temperature value |
---|
Parameter 8: TEMP HYSTERESYS
This Parameter defines the hysteresis value for temperature control. The HE-
FT01 will stabilize the temperature with the selected hysteresis. For example,
if the SET POINT is set for 25C and HYSTERESIS is set for 0.5C, the HE-FT01
will change the state to IDLE if the temperature reaches 25.0C. It will change
the state to HEATING if the temperature becomes lower than 24.5C, and will
change the state to COOLING if the temperature rises beyond 25.5C. The
hysteresis value can be changed from 0.2C to 10.0C range in Celsius mode, and
0.3F to 18.0F in Fahrenheit. The factory-default value is 0.5C (0.9F).
Size: 1 Byte, Default Value: 5
SettingDescription
2 – 100 | Temperature hysteresis value (C x 10) |
---|
Parameter 9: AUTO BRIGHTNESS
Display auto-brightness controlThe HE-FT01 can adjust its display brightness
automatically depending on the ambient room brightness.
Size: 1 Byte, Default Value: 1
SettingDescription
0| Manual Control: Inactive Level brightness will be set to the level defined
by Parameter 10.
---|---
1 – 0| Automatic Brightness Control.
Technical Data
Hardware Platform | ZGM130 |
---|---|
Device Type | Thermostat – HVAC |
Network Operation | Always On Slave |
Firmware Version | HW: 20 FW: 2.01 |
Z-Wave Version | 7.11.1 |
Certification ID | ZC12-20010025 |
Z-Wave Product Id | 0x0344.0x0004.0x0002 |
Neutral Wire Required | ok |
Firmware Updatable | Updatable by Consumer by RF |
Thermostat HVAC Systems Supported | Cool OnlyHeat OnlyMulti StageVentilation |
Control
Thermostat Modes| AutoAuto ChangeoverCoolEnergy Save CoolEnergy Save HeatFan
OnlyHeat
Thermostat Power Source| Mains powered (120V/240V)Power Stealing (hard-wired
24V)
Switch Type| Dry Contact
Security V2| S2_UNAUTHENTICATED ,S2_AUTHENTICATED
Frequency| XXfrequency
Maximum transmission power| XXantenna
Supported Command Classes
- Application Status
- Association Grp Info V3
- Association V2
- Basic V2
- Clock
- Configuration V4
- Device Reset Locally
- Firmware Update Md V5
- Indicator V3
- Manufacturer Specific V2
- Meter V4
- Multi Channel Association V3
- Powerlevel
- Security
- Security 2
- Sensor Multilevel V11
- Supervision
- Thermostat Fan Mode V4
- Thermostat Fan State V2
- Thermostat Mode V3
- Thermostat Operating State
- Thermostat Setpoint V3
- Transport Service V2
- Version V3
- Zwaveplus Info V2
Explanation of Z-Wave specific terms
-
Controller — is a Z-Wave device with capabilities to manage the network.
Controllers are typically Gateways,Remote Controls or battery operated wall controllers. -
Slave — is a Z-Wave device without capabilities to manage the network.
Slaves can be sensors, actuators and even remote controls. -
Primary Controller — is the central organizer of the network. It must be
a controller. There can be only one primary controller in a Z-Wave network. -
Inclusion — is the process of adding new Z-Wave devices into a network.
-
Exclusion — is the process of removing Z-Wave devices from the network.
-
Association — is a control relationship between a controlling device and
a controlled device. -
Wakeup Notification — is a special wireless message issued by a Z-Wave
device to announces that is able to communicate. -
Node Information Frame — is a special wireless message issued by a
Z-Wave device to announce its capabilities and functions.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>