HELTUN High Load Switch User Manual
- June 7, 2024
- HELTUN
Table of Contents
- Overview
- Technical Specifications
- Functions & Features
- Installation
- Disassembly
- Factory Reset (RES)
- Common Configurations
- Time Configuration
- Sensors Configuration
- Protections and Notifications
- Device type “Binary Switch”
- Protections and Notifications
- Auto On/Off function
- External Input Configuration
- Scenarios
- Device type “Thermostat”
- Parameters
- External Input Configuration
- Power and Energy Consumption
- Z-Wave Network
- Associations
- Z-Wave Plus V2 Specifications
- Supported Command Classes
- LIMITED WARRANTY
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
HELTUN High Load Switch
Overview
The HELTUN HE-HLS01 High Load Switch with Thermostat Functions brings incredible capabilities to any connected device: saving energy, wireless control of connected devices, and absolute comfort and convenience for your home. It fits easily behind outlets or switches in standard electrical junction boxes—or in a circuit breaker panel connected to entire banks of lights or outlets—making them ‘Impossibly Smart’ with over the-Internet monitoring, control, and advanced programmability.
Full thermostat functions
The High Load Switch provides Internet-connected thermostat functions where a
local display and controls are not
needed such as roof or driveway de-icing systems. An included NTC temperature
sensor can be installed on the wall,
under floorboards, on the roof, or under decking allowing accurate monitoring
of ambient or radiant floor/roof system
temperatures.
Inputs & outputs
It can also be connecting to external switches or systems—such as a light
switch or alarm system, etc.— through a
pilot wire to allow direct or pre-programmed control of connected devices
using eight different modes.
Know how much energy you use
Determine how much energy is used by major appliances, entertainment systems,
computers, small appliances, or
entire lighting systems by monitoring how much energy has passed through the
HE-HLS01 during any particular day, week, or month.
Makes circuit breakers ‘Impossibly Smart’
Since the High Load Switch can handle up to 16 Amp loads, it is a perfect
addition to your circuit breaker panel for monitoring and controlling groups
of devices from the Internet through a Z-Wave™ gateway.
Safety
The High Load Switch adds safety to your home by protecting against overloads,
overheat, sparks conditions, and it can even be configured to turn off an
outlet if a family member leaves a high load device turned on for a long
period of time, possibly preventing a fire.
Enables scenarios triggered by time
The High Load Switch has an onboard Real Time Clock (RTC) that enables
scenarios where connected devices can be triggered on a schedule.
Based on the latest Z-Wave platform
The HE-HLS01 integrates a Z-Wave Plus™ v2 700 platform module allowing it to
be used with Z-Wave home automation systems. The HE-HLS01 supports Z-Wave ‘S0’
and ‘S2’ security protocols, SmartStart technology, and can be connected
(associated) to other Z-Wave devices, such as relays, motor controllers,
dimmers, etc.
Technical Specifications
- Dimensions: 50mm (H) х 50mm (W) х 26mm (D)
- Materials: Flame retardant plastic
- LED indicator for device status
- Operating temperature: 0°C (32°F) to +50°C (122°F)
- Power supply: 85-265VAC 50Hz/60Hz, 24-48VDC
- Power consumption: 1W
- Active elements: Electromagnetic Relay Switch
- Maximum resistive load: 16А, 4000W @ 250VAC
- Relay switching with HELTUN Advanced Zero-Cross Technology
- Relay life time: 000 switches
- External floor temperature sensor
- NTC 10kΩ
- Measurement range: -30°C (-22°F) to +120°C (248°F)
- Accuracy: ±0.5°C(±1°F)
- Device control
- Through Z-Wave network
- Directly with pilot wire
- Real-time energy consumption meter
- IP class: IP21
- Z-Wave Plus V2 SDK: 11
- Z-Wave module: ZGM130S
- Requires mounting to flush electrical junction box: round, square or rectangular type – depth 40mm
Functions & Features
The functions and features of HE-HLS01 could be different depending on how the
device is included in ZWave network. Depending on the number of button presses
(two or four) during the inclusion process HEHLS01 could function as either
“Binary Switch“ or “Thermostat“.
In case if the device is already included in Z-Wave network and there is a
need to change the device type, it should be removed from network and re-
included with the corresponding type.
Common for “Binary Switch“ and “Thermostat“ device types
- Options for Inclusion/Exclusion to/from Z-Wave network
- Non-Secure
- S0 Secure
- S2 Unauthorized, S2 Authorized with Key
- Association control of devices in z-wave network
- 8 safety functions:
- Overheat protection & notification
- Temperature Rise protection & notification
- Over-current protection & notification
- Over-load protection & notification
- Over-voltage protection & notification
- Voltage drop protection & notification
- Spark & Surge protection & notification
- Device Failure notification
- External control input
- Periodic measurements from:
- External temperature sensor
- Energy consumption meter
- Can be used with different NTC-sensors (range: 1kΩ to 100kΩ)
- Calibration of External NTC Temperature Sensor
- Zero-cross relay switching
- NO/NC relay mode
- LED indicator blinking function (for easy identification among other Z-Wave devices)
- Real-time and cumulative energy usage to 1kW accuracy
- Factory reset function
- SmartStart technology for quick addition to Z-Wave networks
- Encrypted OTA (Over The Air) firmware update feature
- Z-Wave Frequency change
“Binary Switch“ device type
-
Auto On/Off function
- Switch output Off if there is no consumption
- Switch output On when the load is reconnected
-
Time limit for high load
-
Timer mode for relay control
-
10 scenarios for relay control
-
operational modes with individual temperature set points:
- Heat – Most comfort mode
- Auto – Time schedule mode
- Dry – Fast floor drying mode
- Energy Saving – Power efficient mode
- Away – Vacation mode
- Off – Thermostat Off (IDLE) mode
-
4 time schedules for 7 days of the week:
- Morning
- Day
- Evening
- Night
-
Additional safety function:
- Load Failure notification
-
Can be used with different NTC-sensors (range: 1kΩ to 100kΩ)
-
Temperature set intervals: 0°C (34°F) to 110.0°C (230°F)
-
Temperature scale selection (Celsius or Fahrenheit)
-
Temperature hysteresis selection range: 2°C (1°F) to 10.0°C (18°F)
Installation
The HELTUN HE-HLS01 High Load Switch must be be installed by a licensed
electrician in a manner that conforms to local regulations and building codes.
Provide these instructions to the licensed electrician who is installing the
HEHLS01.
WARNING: Electrical power must be switched off during installation.
-
FIRST ENSURE THE POWER IS OFF at the main circuit breaker, and then test the wires with a probe or multimeter to verify.
-
Insert the power and load wires to the correct HE-HLS01 terminals by inserting a small Phillipshead screwdriver in the slot beneath each terminal and unscrew to open.
Follow connection diagrams (Figure 2, 3, 4, 5) and the instructions below:
• Power wires: for AC power (85-265VAC) connect Line & Neutral lead wires to L & N terminals labeled “IN”. For DC power (24-48VDC) connect “+” wire to terminal N and “–” wire to terminal L.
• Load wires: connect Line & Neutral wires to L & N terminals labeled with “heating element” graphic
Note: it is possible to connect Neutral wire from load directly to your neutral line ( Figure 3 or 5 ).
Note: HELTUN recommends installing cord terminals (electric wire ferrules) on the ends of wires before connecting them to the HE-HLS01 outputs (various colors terminals are included).
Note: Zero-Cross technology is unavailable if the device is DC (24-48VDC) powered. Tighten wires using Phillips screwdriver in slot beneath each wire. -
If using the HE-HLS01 for radiant floor heating, connect the NTC temperature sensor wire to the terminals labeled “NTC.” A 10 kΩ NTC sensor is included inside the HE-HLS01 packaging, but any NTC sensor can be used.
Note: If an NTC sensor other than 10 kΩ is used, you must change the sensor resistance value in Parameter 8. -
If you will be using an external device to select modes for the HE-HLS01 (such as a security system or wall switch),
connect wires from the external device’s dry contacts to the two HE-HLS01 terminals labeled “S1” & “Sx”.
Two different connection methods for external control are possible:
• Connect S1 to Sx through dry contact switch (as in Figures 2 & 3)
• Connect S1 to electric network Line through dry contact switch (as in Figures 4 & 5)
Note: In case of connecting S1 to electric network Line, it is MANDATORY to connect S1 terminal to the same wire connected to terminal L on the device (labeled as “IN”).
-
Switch On the main power at the circuit breaker. The HE-HLS01 will start up with the original default factory settings and the LED indicator will blink red slowly meaning the device is excluded from a Z-Wave network.
Disassembly
- ENSURE POWER IS SWITCHED OFF at the main circuit breaker AND THE LED INDICATOR IS OFF.
- Disconnect the wires by inserting a small Phillips-head screwdriver into the slot beneath each wire and unscrewing to release.
Factory Reset (RES)
To reset the HE-HLS01 to factory defaults, press and hold the service button
for six seconds. If successful, the LED indicator will blink white for two
seconds then the device will reboot.
The factory reset will change all the Parameters to their original factory
default values and will also Exclude the device from any Z-Wave network.
Note: Please use this procedure only when the network primary controller
is missing or otherwise inoperable.
Common Configurations
1-30 configuration parameters are common for both “Binary Switch” and
“Thermostat” device types.
All configuration parameters are accessed through COMMAND_CLASS_CONFIGURATION
Parameter Number
|
Parameter Size
|
Parameter Name
| Default Value|
Available Values
---|---|---|---|---
1
|
1 byte
| DEVICE TYPE|
0
|
0, 1
2
|
1 byte
| FREQUENCY REGION|
0
|
0 … 9
3
|
1 byte
| OUTPUT MODE|
0
|
0, 1
4
|
1 byte
| TIME CORRECTION|
1
|
0, 1
5
|
1 byte
| WEEKDAY|
1
|
1, 2, 3, 4, 5, 6, 7
6
|
1 byte
| HOUR|
0
|
0 … 23
7
|
1 byte
| MINUTE|
0
|
0 … 59
8
|
1 byte
| NTC RESISTANCE|
10
|
1 … 100
9
|
1 byte
| TEMPERATURE SENSOR OFFSET|
0
|
(-100) … 100 for °C,
(-17) … 17 for °F
10
|
1 byte
| TEMPERATURE SCALE MODE|
0
|
0, 1
11
|
1 byte
| TEMPERATURE REPORT INTERVAL|
10
|
1 … 120
12
|
1 byte
| TEMPERATURE REPORT THRESHOLD|
5
|
0, 1 … 100 for °C,
0, 1 … 18 for °F
13
|
1 byte
| METER REPORT INTERVAL|
10
|
1 … 120
14
|
1 byte
| METER REPORT THRESHOLD|
25
|
0, 1 … 90
15
|
1 byte
| SYSTEM ERROR NOTIFICATION|
1
|
0, 1
16
|
2 bytes
| TEMPERATURE RISE NOTIFICATION|
50 for °C,
122 for °F
|
0 … 120 for °C,
32 … 248 for °F
17
|
2 bytes
| OVERHEAT PROTECTION LEVEL|
60 for °C,
140 for °F
|
0 … 120 for °C,
32 … 248 for °F
18
|
1 byte
| OVERCURRENT NOTIFICATION|
1
|
0, 1
19
|
2 bytes
| OVERLOAD PROTECTION LEVEL|
3500
|
0, 100 …. 4000
20
|
2 bytes
| OVERVOLTAGE PROTECTION LEVEL|
240
|
0, 120 … 280
21
|
2 bytes
| VOLTAGE DROP PROTECTION LEVEL|
200
|
0, 80 … 240
22
|
1 byte
| SPARK PROTECTION|
1
|
0, 1
23-30
|
4 bytes
|
RESERVED BY MANUFACTURER
Parameter 01 – Device Type
This parameter is read only and indicates in which mode the device is
included. The device can be included either in the Binary Switch mode or in
the Thermostat mode. Use inclusion in Binary Switch mode if there is a need to
control on/off device and use inclusion in Thermostat mode if there is a need
to control heating system. For the appropriate inclusion process see the
section Z-Wave Network of this manual.
Parameter 02 – Frequency Region
The HLS01 has Z-Wave 700 platform chip inside which allows to use the device
in different Z-Wave frequencies. If there is a need to use the device in the
frequency different from the factory default change the value of this
parameter according to the list below.
Note: The factory default frequency differs depending on which region the
device was intended for sale in. Check the factory default frequency on the
device plate or on the packaging.
Note: Don’t change this parameter value if there is no a special need.
Note: The frequency change will be applied only after removing from
Z-Wave network and automatic reboot of the device․
Note: The change of this parameter will result in inability to control
the device, if the device was included to the controller/gateway which
supports only one frequency,
Note: Resetting the device to factory default settings will revert back
the frequency to the factory default value.
Note: In most of countries it is not allowed to use the frequency
different from the frequency intended for that country.
Frequency list for different regions:
0: EU (868.4 MHz, 869.85 MHz)
1: US (908.4 MHz, 916.0 MHz)
2: ANZ (919.8 MHz, 921.4 MHz)
3: HK (919.8 MHz)
4: IN (865.2 MHz)| 5: IL (916.0 MHz)
6: RU (869.0 MHz)
7: CH (868.4 MHz)
8: JP (922.5 MHz, 923.9 MHz, 926.3 MHz)
9: KR (920.9 MHz, 921.7 MHz, 923.1 MHz)
---|---
The full list of Z-Wave global regions where Z-Wave works is available at Z Wave Global Regions SiLabs page.
Parameter 03 – Output NO/NC Mode
The device can operate in Normal Open (NO) mode and in Normal Close (NC) mode.
If the Parameter value = 0, the device switch operates in NO mode and there is
no voltage on output when the device is in OFF state. The output will be
powered when device goes to ON state. If the Parameter value = 1, the output
will be powered in OFF state and will be no voltage on output when the device
is in ON state.
The factory default value is 0.
Time Configuration
Parameter 04 – Time Correction by Gateway
If this Parameter value = 1 and the HE-HLS01 is connected to a Z-Wave gateway,
the HE-HLS01 time and day will be periodically polled and corrected from the
gateway. To switch off auto correction set the Parameter value to 0. The
factory default value is 1.
Parameter 05 – Day of the Week
Allows manually adjustment of the day of the week in case the HE-HLS01 is not
connected to any Z-Wave gateway or the Parameter 04 (auto-correction) is set
to 0. The value of this parameter can be set from 1 to 7: 1 = Monday, 2 =
Tuesday, 3 = Wednesday, 4 = Thursday, 5 = Friday, 6 = Saturday, 7 = Sunday.
The factory default value is 1.
Parameter 06 – Clock Hours
Allows manually adjustment of hours for internal clock in case the HE-HLS01 is
not connected to any Z-Wave gateway or the Parameter 04 (auto-correction) is
set to 0. The value of this parameter can be set from 0 to 23.
The factory default value is 0.
Parameter 07 – Clock Minutes
Allows manually adjustment of minutes for internal clock in case the HE HLS01
is not connected to any Z-Wave gateway or the Parameter 04 (auto-correction)
is set to 0. The value of this parameter can be set from 0 to 59. The factory
default value is 0.
Sensors Configuration
Parameter 08 – External NTC Temperature Sensor Resistance
If the external NTC temperature sensor is used it is necessary to select the
correct resistance value in Ohms (Ω) of the sensor. The selection range is 1
to 100 kiloOhms (kΩ). One 10kΩ NTC temperature sensor is included in the HE-
HLS01 package with a 3-meter connection wire.
The factory default value is 10.
Parameter 09 – Temperature Sensor Calibration
This Parameter defines the offset value for external NTC temperature sensor.
If the temperature sensor is not calibrated properly, manual calibration can
be made by adjusting the values up to ±10.0°C or ±18°F. This value will be
added or subtracted from the temperature sensor reading.
The factory default value is 0.
Parameter 10 – Temperature Scale Mode
This parameter determines in which unit of measurement (degrees Celsius or
Fahrenheit) the device will report the temperature, and also determines the
scale that will be interpreted by the configuration parameters. Set the value
0 for Celsius and the value 1 for Fahrenheit.
Factory default value is 0 (degrees Celsius).
Note: This configuration parameter has impact on configuration parameters
9,12,16,17 and 32, 42-69 in thermostat mode. If scale is set to degrees
Fahrenheit, configuration values at mentioned parameters will be automatically
converted from Celsius to Fahrenheit and any change in the values will be
interpreted as Fahrenheits.
Parameter 11 – Temperature Sensor Consecutive Report Interval
This Parameter defines the interval between consecutive reports of temperature
sensor reading to the gateway. The
value can be adjusted from 1 min to 120 min.
The factory default value is 10 min.
Note: If the sensor readings change, the device will send the report to
the gateway regardless of this parameter value.
In order not to increase traffic on your network, it is not recommended to
reduce the value of this parameter. We recommend reducing the value of this
parameter only in case of poor connection, when reports from the device does
not always reach the gateway.
Parameter 12 – Temperature Sensor Report Threshold
This parameter determines the change in temperature level resulting in
temperature sensors report being sent to the gateway. In Celsius scale mode
the value of this parameter should be x10, e.g. for 0.4°C use value 4. From 1
(0.1°C) to 100 (10°C) can be selected in Celsius scale mode and from 1 to 18
can be selected in Fahrenheit scale mode. Use the value 0 if there is a need
to stop sending the reports.
The factory default value is 5 (0.5°) in °C scale and 1 in °F scale.
Parameter 13 – Energy Consumption Meter Consecutive Report Interval
When the device is connected to the Z-Wave gateway (controller), it
periodically sends to the gateway reports from its external temperature sensor
and energy consumption meter even if there are not changes in the values. This
Parameter defines the interval between consecutive reports of real time and
cumulative energy consumption data to the gateway. The value can be adjusted
from 1 min to 120 min.
The factory default value is 10 min.
Note: If the sensor readings change, the device will send the report to
the gateway regardless of this parameter value.
In order not to increase traffic on your network, it is not recommended to
reduce the value of this parameter. We recommend reducing the value of this
parameter only in case of poor connection, when reports from the device does
not always reach the gateway.
Note: Energy consumption meter function is available only if the device
is AC powered.
Parameter 14 – Energy Consumption Meter Report Threshold
This parameter determines how much the cumulative or real time energy
consumption data need to increase/reduce to be reported to the gateway. The
value of this parameter is in % and from 1 to 90 can be selected. Use the
value 0 if there is a need to stop sending the reports.
The factory default value is 25.
Note: Energy consumption meter function is available only if the device
is AC powered.
Protections and Notifications
Parameter 15 – Device Failure Notifications
If the HLS01 does not work properly it sends “System Failure” notification to
the gateway with the error code. Set the value 1 to enable “System Failure”
notification or the value 0 to disable.
The factory default value is 1 (the notification is enabled).
Errors code list (sent with the notification):
0 – No Error (no issue is detected)
1 – Relay Off Error (when unable to switch Off the relay output).
2 – Relay On Error (when unable to switch On the relay output).
3 – Relay On & Off Error (when unable to switch On and Off the relay output).
4 – NTC Error (when no NTC sensor is detected or when it is damaged).
5 – NTC and Relay Off Error (when no NTC sensor is detected or when it is
damaged and unable to switch Off the relay output).
6 – NTC and Relay On Error (when no NTC sensor is detected or when it is
damaged and unable to switch On the relay output).
7 – NTC and Relay On & Off Error (when no NTC sensor is detected or when it is
damaged and unable to switch On and Off the relay output).
Parameter 16 – Temperature Rise Notification
Use this parameter if you want to know about temperature rise before it
reaches the critical value, defined in the “Overheat Protection” parameter.
The device will send “Rapid Temperature Rise” notification to the gateway if
the temperature sensor reading reaches the value defined in this parameter.
The value can be set from 1 to 120 in °C scale mode or from 32 to 248 in °F
scale mode. To disable the notification, set the value of this parameter to 0.
The factory default value is 50 in °C scale and 122 in °F scale.
Note: We recommend setting the value of this Parameter lower than value
of Parameter 17 (Overheat Protection).
Parameter 17 – Overheat Protection & Notification
You can define the maximum limit of temperature, reaching which the device
will automatically switch Off the load and send “Overheat Detected”
notification to the gateway. The value of this parameter can be set from 1 to
120 in °C scale mode or from 32 to 248 in °F scale mode. Use the value 0 if
there is a need to disable this function.
The factory default value is 60 in °C scale and 140 in °F scale.
Parameter 18 – Over-Current Protection & Notification
The maximum load for the device is 16A. If the connected load current exceeds
16A the device will automatically switch Off the output and send the “Over-
Current Detected” notification to the gateway. To disable sending the
notification, set the value of this Parameter to 0.
The factory default value is 1 (the notification is enabled).
Note: Even if you turn off the notification, the device will switch Off
the load when the current reaches 16A.
Note: The protection works only if the device is AC powered.
Parameter 19 – Over-Load Protection & Notification
You can define the maximum power in Watt for connected load. The device will
automatically switch off the output and send “Over-Load Detected” notification
to the gateway if power consumed by the connected load exceeds this limit. The
value of this parameter can be set from 100 to 4000 in watts. Use the value 0
if there is a need to disable this function.
The factory default value is 3500W.
Note: The protection works only if the device is AC powered.
Parameter 20 – Over-Voltage Protection & Notification
The device constantly monitors the voltage of your electricity network. You
can define the maximum voltage of network exceeding which the device will
automatically switch off the output and send “Over-Voltage Detected”
notification to the gateway. The value of this parameter can be set from 120
to 280 in volts. Use the value 0 if there is a need to disable this function.
The factory default value is 240V.
Note: The protection works only if the device is AC powered.
Parameter 21 – Voltage Drop Protection & Notification
You can define the minimum voltage of your electricity network. If the voltage
of the network drops determined level the device will automatically switch off
the output and send “Voltage Drop Detected” notification to the gateway. The
value of this parameter can be set from 80 to 240 in volts. Use the value 0 if
there is a need to disable this function.
The factory default value is 200V.
Note: The protection works only if the device is AC powered.
Parameter 22 – Sparks Protection & Notification
If connected load fails it can create sparks that may cause a fire. The device
constantly monitors the power consumption of connected load and can detect
even a small surge in consumption and automatically switch off the output and
send “Surge Detected” notification to the gateway. Set the value 1 to enable
this function or the value 0 to disable.
The factory default value is 1 (the protection is enabled).
Note: The protection works only if the device is AC powered.
Parameters 23 – 30 – Reserved by Manufacturer
We reserved these parameters for future updates and new functionality.
Changing of these parameters will not have any effect to the device logic.
Device type “Binary Switch”
These parameters will take affect only in case if the device is included in the Binary Switch mode. For more information about the different inclusion modes see the section Z-Wave Network.
Number
|
Size
| Name| Default Value|
Available Values
---|---|---|---|---
31
|
1 byte
| LOAD ON NOTIFICATION|
0
|
0, 1
32
|
1 byte
| LOAD OFF NOTIFICATION|
0
|
0, 1
33
|
2 byte
| TIME LIMITITED LOAD|
0
|
0, 100 … 3500
34
|
2 byte
| HIGH LOAD ON TIME LIMIT|
0
|
0 …. 1440
35
|
1 byte
| LOAD AUTO ON/OFF|
0
|
0, 1
36
|
1 byte
| AUTO OFF TIMEOUT|
5
|
0 … 120
37
|
1 byte
| AUTO ON RECONNECT TIMEOUT|
0
|
0 … 120
38
|
1 byte
| S1 INPUT HOLD CONTROL MODE|
2
|
0, 1, 2, 3
39
|
1 byte
| S1 INPUT CLICK CONTROL MODE|
1
|
0, 1, 2, 3, 4, 5
40
|
2 bytes
| RELAY TIMER DURATION|
0
|
0 … 43200
41
|
4 bytes
| RELAY CONTROL SCENARIO 1|
0
|
0, 1000000 … 1912359
42
|
4 bytes
| RELAY CONTROL SCENARIO 2
43
|
4 bytes
| RELAY CONTROL SCENARIO 3
44
|
4 bytes
| RELAY CONTROL SCENARIO 4
45
|
4 bytes
| RELAY CONTROL SCENARIO 5
46
|
4 bytes
| RELAY CONTROL SCENARIO 6
47
|
4 bytes
| RELAY CONTROL SCENARIO 7
48
|
4 bytes
| RELAY CONTROL SCENARIO 8
49
|
4 bytes
| RELAY CONTROL SCENARIO 9
50
|
4 bytes
| RELAY CONTROL SCENARIO 10
51 … 60
|
4 bytes
|
RESERVED BY MANUFACTURER
Protections and Notifications
Parameter 31 – Load Switched On Notification
If this function is enabled the device will send “AC Mains Re-Connected”
notification to the gateway each time when the relay output state changes to
On. To enable this notification, set the value of this parameter to 1.
The factory default value is 0 (notification is disabled).
Note: This function can be useful for informing in case of automatic
control of the load by schedule or scenario.
Parameter 32 – Load Switched Off Notification
If this function is enabled the device will send “AC Mains Disconnected”
notification to the gateway each time when the relay output state changes to
Off. To disable this notification, set the value of this parameter to 0.
The factory default value is 0 (notification is enabled).
Note: This function can be useful for informing when the device
automatically switches the output Off because of emergency case or in case of
automatic control of the load by schedule or scenario.
Parameter 33 – High Load Timeout Protection: Power Threshold
If the HLS01 is used to control an electric socket, you can configure the
device so that it automatically switch Off the socket if the potentially
dangerous high load is connected longer than allowable time (time to be set in
the Parameter
34), for example, if you left the iron switched On for too long. Set in this
parameter the threshold value in watts, reaching which the connected load will
be considered high. The value of this parameter can be set from 100 to 3500 in
watts.
Use the value 0 if there is a need to disable this function.
The factory default value is 0 (the function is disabled).
Note: If the connected load power is less than value of this parameter,
the protection will not be activated.
Note: If the Parameter 34 (time threshold) value is set to 0, the
protection will not be activated.
Note: The time counter is reset every time when the load consumption
drops to zero.
Note: We recommend activating the Load Switched Off notification (the
Parameter 32) to be informed when the device automatically switch Off the
socket.
Note: The protection works only if the device is AC powered.
Parameter 34 – High Load Timeout Protection: Time Threshold
If High Load Timeout Protection is activated (the Parameter 33 is set) use
this parameter to set the threshold value in minutes. If the load is connected
longer than this value, the device will automatically switch Off the socket.
The value of this parameter is in minutes and can be set from 1 to 1440. Use
the value 0 if there is a need to disable this function.
The factory default value is 0 (the function is disabled).
Note: If the value of this parameter is set 0, the protection will not be
activated.
Note: If the connected load power is less than value of the Parameter 33,
the protection will not be activated.
Note: The time counter is reset every time when the load consumption
drops to zero. If the connected load may change its consumption, make sure
that the time threshold will be reached before the load consumption drops.
Note: We recommend activating the Load Switched Off notification (the
Parameter 32) to be informed when the device automatically switch Off the
socket.
Note: The protection works only if the device is AC powered.
Auto On/Off function
Parameter 35 – Auto On/Off
If this function is enabled the device will switch Off the relay output when
there is no consumption and switch On the
output again when the load is reconnected. It is possible to set the delay for
Auto Off function (in the Parameter 36) and
for Auto On function (in the Parameter 37). To enable Auto On/Off function,
set this Parameter value to 1 and use the value 0 if there is a need to
disable the function.
The factory default value is 0 (the function is disabled).
Note: If the output is manually switched Off (from Gateway or External
Input toggle) Auto ON function will be blocked until the output switches back
to ON manually or the load disconnected.
Note: The function works only if the device is AC powered.
Parameter 36 – Auto Off Timeout
If Auto On/Off function (the Parameter 35) is enabled, it is possible to delay
the Auto Off function. The output will be switched Off when there is no
consumption for the interval defined in this parameter in minutes. The value
of this parameter can be set from 1 to 120 min. Set the parameter value to 0
if there is a need to switch Off the output immediately when consumption drops
to 0W.
The factory default value is 5 min.
Note: The function works only if the device is AC powered.
Parameter 37 – Auto On Reconnect Timeout
If Auto On/Off function (the Parameter 35) is enabled, it is possible to delay
the Auto On function. When the load is reconnected the relay output will be
switched On after the time defined in this parameter in minutes. The value of
this parameter can be set from 1 to 120 min. Set the parameter value to 0 if
there is a need to switch On the output immediately when the load is
reconnected.
The factory default value is 0 min.
Note: The function works only if the device is AC powered.
External Input Configuration
The HE-HLS01 can be connected to the dry output contacts of an external device
(i.e. security system or wall switch) to control the Switch output state
depending on the state of the external device.
Two different connection diagrams are possible for external input:
- Connect S1 to Sx through dry contact switch
- Connect S1 to electric network Line through dry contact switch
Note: In case of connecting S1 to electric network Line, it is MANDATORY to connect S1 terminal to the same wire connected to terminal L on the device (labeled as “IN”).
Parameter 38 – External Input: Hold Control Mode
0 – Hold function is disabled
1 – Operate like click (the Parameter 39)
2 – Momentary Switch: When the button on switch connected to external input is
held, (key closed) the relay output state is ON, as soon as the button is
released (key opened) the relay output state changes to OFF.
3 – Reversed Momentary Switch: When the button on switch connected to external
input is held, the relay output state is OFF, as soon as the button is
released the relay output state changes to ON.
The factory default value is 2.
Parameter 39 – External Input: Click Control Mode
0 – Click function disabled
1 – Toggle switch: relay inverts state (ON to OFF, OFF to ON).
2 – Relay switches to ON state only
3 – Relay switches to OFF state only
4 – Timer: On>Off Mode: Relay output switches to ON state (contacts are
closed) then after a specified time switches back to OFF state (contacts are
open). The time is specified in the Parameter 40.
5 – Timer: OFF>ON Mode: Relay output switches to OFF state (contacts are open)
then after a specified time switches back to ON state (contacts are closed).
The time is specified in Parameter 40.
The factory default value is 1.
Parameter 40 – Relay Timer Mode Duration
These parameters specify the duration in seconds for the Timer mode (values 4
or 5 in the Parameter 39). Press the button on the switch connected to
external input and the relay output goes to ON/OFF for the specified time then
changes back to OFF/ON. The time value can be configured from 0 sec to 43200
sec (12 hours).
The factory default value is 0.
Note: If the parameter value is set to “0” the relay output will operate
as a short contact (duration is about 0.5 sec).
Scenarios
Parameters 41-50 – Relay Control by Scenario
In these parameters, the relay state changes depending on day and time. For
these configurations, parameter values are encoded as 7-digit numbers
(ABCDEFG).
A: State. 0 = Disabled, 1 = Enabled
B: Day of week
0 = every day
1-7 = corresponding day (1 is Monday, 7 is Sunday)
8 = every weekday (Monday – Friday)
9 = every weekend (Saturday and Sunday)
C: Change state to
0 = Switch OFF
1 = Switch ON
DEFG: Time
DE represents Hour (from 0 to 23),
FG represents Minutes (from 0 to 59).
All other numbers are reserved and will not affect the operation. To disable
this option simply set this parameter to 0.
The factory default value is 0.
Example: Parameter value 1210350 means A=1 (the scenario is enabled), B=2 (Tuesday), C=1 (switch the relay On), DEFG=0350 (time 03:50). In this case each Tuesday at 03:50 the relay output will be switched On. To disable the scenario, change the first digit to 0. In this example it will be 0210350.
Note: The relays still can be controlled manually using External Inputs
or via controller/gateway.
Note: The logic will implement the operation when the time crosses the
value in the Parameter. Meaning, that if the logic switches On the relay and
you manually switch it Off, the relay will switch On next time when the value
crosses the set parameter.
Note: 10 different scenarios can be implemented (one scenario in each
parameter 50-59), but make sure you don’t use the same time (DEFG) in
different scenarios.
Parameters 51 – 60 – Reserved by Manufacturer
We reserved these parameters for future updates and new functionality.
Changing of these parameters will not have any effect to the device logic.
Device type “Thermostat”
Operation Modes
When the HE-HLS01 is included as Thermostat it has 6 Operating Modes:
- Heat – Comfort Mode
- Auto Change Over – Time Mode (schedule different Set Point per time and day)
- Dry – Floor Fast Drying Mode
- Energy saving – Power Efficient Mode
- Away – Vacation Mode
- Off – Thermostat IDLE Mode
Each operating mode has individual temperature Set Points. The HE-HLS01 will
operate automatically depending on the current Set Point. You may control Set
Points through your Z-Wave gateway software.
Note: The minimum Set Point is 1.0°C (or 34°F) and the maximum Set Point
is 110.0°C (or 230°F).
Heat Mode
This mode is recommended for normal comfort. The factory default set point is 25.0°C (77°F).
Auto Changeover Mode – Temperature Schedule Mode
The Temperature Schedule Auto Mode can adjust home temperatures automatically to align with your personal habits, saving energy while you are away, and maintaining a comfortable temperature while you are active at home.
The HE-HLS01 can have different Schedules for Morning, Daytime, Evening and Night. For example, the “Morning” Schedule could be set to 25.0°C (77°F) starting at 7:00. The “Day” Schedule could then be set to 11.0°C (or 52°F) at 9:00 when everyone has gone to work or school, and so on. Here are recommended Scheduled Set Points for heating during the work week – you may wish to change these on weekends depending on your family’s schedule (see example below):
Schedule Mode
| Set Time|
Set Point Temperature
---|---|---
Morning
| 6:00 (6:00am)|
24°C (75°F)
Day
| 9:00 (9:00am)|
20°C (68°F)
Evening
| 18:00 (6:00pm)|
23°C (73°F)
Night
| 23:00 (11:00pm)|
18°C (64°F)
Note: All four Schedules (Morning, Day, Evening, & Night) are the same
for all seven days of the week.
Note: Auto mode will only work properly if the correct current time and
date have been set. The time can be automatically corrected from your Z-Wave
gateway if the Parameter 04 value is set to 1. Or it can be set manually in
Parameters 05, 06, and 07.
Note: In Auto mode, the temperature Set Point will be automatically
changed depending on the Schedule. At any time, the Set Point can be adjusted
but it will be effective only until the next Schedule.
DRY – Fast Floor Drying Mode
This mode is recommended for use if a high floor temperature is required for a
limited period of time. For example, after washing the floor. By choosing DRY
Mode, the HE-HLS01 will increase the temperature to the selected Set Point for
the time specified in the “Dry Time” parameter (Parameter 36). A time range
from 1 to 720 minutes (12 hours) can be set. As the Dry Time passes, the HE-
HLS01 will automatically change to the Mode set in Parameter 37.
Note: Factory defaults for Dry Time are: 30 minutes at 30.0°C (86°F).
Energy Saving Mode
This Mode can be used if lower temperature and energy consumption is desired. It can also be used at night or when away from all or part of the property for a length of time. The factory default Set Point is 20.0°C (68°F).
Away Mode
Use Vacation Mode when you are planning to be away from home for some period.
The factory default temperature Set Point is 15.0°C (59°F).
Note: The minimum set point for each mode is 1.0°C (34°F) and the maximum
set point is 110.0°C (230°F).
Parameters
These parameters will take affect only in case if the device is included in the Thermostat mode. For more information about the different inclusion process see the section Z-Wave Network.
Number
| Size| Name| Default Value|
Available Values
---|---|---|---|---
31
|
1 byte
| LOAD ERROR NOTIFICATION|
0
|
0, 1
32
|
1 byte
| TEMPERATURE REGULATION HYSTERESYS|
50 for °C, 1 for °F
|
2 … 100 for °C,
1 … 18 for °F
33
|
1 byte
| BASIC SET MODE|
1
|
1, 2, 3, 4, 5
34
|
1 byte
| S1 INPUT MODE|
0
|
0, 1, 2, 3
35
|
1 byte
| S1 INPUT ACTION|
1
|
1, 2, 3, 4, 5
36
|
2 byte
| DRY TIME|
30
|
1 … 720
37
|
1 byte
| DRY MODE SWITCH|
1
|
1, 2, 4, 5, 6
38
|
2 bytes
| MORNING START TIME|
0600
|
0000 … 2359
39
|
2 bytes
| DAY START TIME|
0900
40
|
2 bytes
| EVENING START TIME|
1800
41
|
2 bytes
| NIGHT START TIME|
2300
42
|
2 bytes
| MONDAY MORNING TEMP|
240 for °C, 75 for °F
| 10 … 1100 for °C, 34 … 230 for °F
43
|
2 bytes
| MONDAY DAYTIME TEMP|
200 for °C, 68 for °F
44
|
2 bytes
| MONDAY EVENING TEMP|
230 for °C, 73 for °F
45
|
2 bytes
| MONDAY NIGHT TEMP|
180 for °C, 64 for °F
46 … 49
|
2 bytes
| TUESDAY MORNING TEMP
TUESDAY DAYTIME TEMP
TUESDAY EVENING TEMP
TUESDAY NIGHT TEMP|
Same as for Monday (42 – 45)
50…53
|
2 bytes
| WEDNESDAY MORNING TEMP
WEDNESDAY DAYTIME TEMP
WEDNESDAY EVENING TEMP
WEDNESDAY NIGHT TEMP|
Same as for Monday (42 – 45)
54…57
|
2 bytes
| THURSDAY MORNING TEMP
THURSDAY DAYTIME TEMP
THURSDAY EVENING TEMP
THURSDAY NIGHT TEMP|
Same as for Monday (42 – 45)
58…61
|
2 bytes
| FRIDAY MORNING TEMP
FRIDAY DAYTIME TEMP
FRIDAY EVENING TEMP
FRIDAY NIGHT TEMP|
Same as for Monday (42 – 45)
62…65
|
2 bytes
| SATURDAY MORNING TEMP
SATURDAY DAYTIME TEMP
SATURDAY EVENING TEMP
SATURDAY NIGHT TEMP|
Same as for Monday (42 – 45)
66…69
|
2 bytes
| SUNDAY MORNING TEMP
SUNDAY DAYTIME TEMP
SUNDAY EVENING TEMP
SUNDAY NIGHT TEMP|
Same as for Monday (42 – 45)
70…80
|
4 bytes
| RESERVED BY MANUFACTURER
Parameter 31 – Load Error Notification
The device can send the “Load Error” notification to the gateway when the
relay is On but there is no power consumption (meaning possible problems with
the heating system). Set the value 1 to enable “Load Error” notification or
the value 0 to disable.
The factory default value is 1 (the notification is enabled).
Note: The function works only if the device is AC powered.
Parameter 32 – Temperature Hysteresis
This Parameter defines the hysteresis value for temperature control. The HE
HLS01 will stabilize the temperature with selected hysteresis. For example, if
the SET POINT is set for 25°C and HYSTERESIS is set for 0.5°C the HE-HLS01
will change the state to IDLE when the temperature reaches 25.0°C, but it will
change the state to HEATING if the temperature drops lower than 24.5°C. The
hysteresis can be changed from 0.2°C to 10.0°C range in Celsius mode, and from
1°F to 18.0°F in Fahrenheit mode. The factory default value is 0.5°C and 1°F.
Parameter 33 – Basic Set Action
This Parameter defines which Operating Mode the HE-HLS01 reverts to if the
Basic Set command is received. If the Basic Set command value is 0 (OFF state)
the HE-HLS01 will go to Manual mode and switch Off the heating element (IDLE
mode). If the Basic Set command is value is 0xFF (ON state) the HE HLS01 will
change the Mode to the corresponding Parameter value as follows.
1: Heat Mode
2: Auto Mode
3: Dry Mode
4: Energy Saving Mode
5: Away Mode
The factory default value is 1
External Input Configuration
The HE-HLS01 can be connected to the dry output contacts of an external device
(i.e. security system or window sensor) to control the Thermostat operating
modes depending on the state of the external device.
Two different connection diagrams are possible for external input:
- Connect S1 to Sx through dry contact switch
- Connect S1 to electric network Line through dry contact switch
Note: In case of connecting S1 to electric network Line, it is MANDATORY to connect S1 terminal to the same wire connected to terminal L on the device (labeled as “IN”).
Parameter 34 – External Input Mode
0 – the input state changes will be ignored by the Thermostat logic.
1 – the external input will operate in “Toggle Switch” mode: if the external
input is shorted (with Sx or Line) the
Thermostat switches to the operating mode selected in the Parameter 35 and
switches to OFF mode when the external input is open.
2 – the external input will operate in “Toggle Switch Reverse” mode: if the
external input is shorted the Thermostat switches to OFF mode and switches to
the operating mode selected in the Parameter 35 when the input is open.
3 – the external input will operate in “Push Button (Momentary Switch)” mode:
each press of button (shorten of input) will consistently change the mode to
the operating mode selected in the Parameter 35 .
The factory default value is 0.
Parameter 35 – External Input Action
This Parameter allows selection of which Operating Mode the HE-HLS01 should
revert to when the external input is shorted. 1 = Heat, 2 = Auto, 3 = Dry, 4 =
Energy Saving, 5 = Away.
The factory default value is 1.
Parameter 36 – Dry Mode Timeout
By choosing Dry Mode, the device will increase the temperature to the selected
Set Point and keep it for the time specified in this parameter. A time range
of 1 to 720 minutes (12 hours) can be set. As the Dry Time passes, the
Thermostat will automatically change to the Mode set in the Parameter 37.
The factory default value is 30 minutes.
Parameter 37 – Mode to Switch After Dry Mode Operation Complete
This Parameter indicates the mode that will be set after Dry Time: 1 = Heat, 2
= Auto, 4 = Energy Saving, 5 = Away, 6 = Off.
The factory default value is 1.
Note: The value 3 (Dry mode) will be ignored for this parameter.
Parameters 38-41 – Schedule Time
Use these parameters to manual set the Morning, Day, Evening and Night times
for the Temperature Schedule.
The value of these parameters has format HHMM, e.g. for 08:00 use value 0800
(time without a colon). From 00:00 to
23:59 can be selected.
The factory default value for Morning (Parameter 38) is 0600.
The factory default value for Day (Parameter 39) is 0900.
The factory default value for Evening (Parameter 40) is 1800.
The factory default value for Night (Parameter 41) is 2300.
Parameters 42-69 – Schedule Temperature
Use these parameters to manual set the temperature for each day Schedule.
In Celsius scale the value of this parameter should be x10, e.g. for 22.5°C
use value 225. From 1°C (value 10) to 110°C (value 1100) in Celsius scale and
from 34°F (value 34) to 230°F (value 230) in Fahrenheit scale can be selected.
For the default and available values check the parameters list.
Parameters 70 – 80 – Reserved by Manufacturer
We reserved these parameters for future updates and new functionality.
Changing of these parameters will not have any effect to the device logic.
Power and Energy Consumption
HE-HLS01 monitors active power energy consumption and Voltage using advanced
micro-controller technology which assures maximum accuracy (±1% for loads
greater than 1000W). Real time consumption, cumulative consumption, and
network voltage are periodically reported to the Z-Wave controller.
Resetting cumulative consumption memory:
The Heating Thermostat allows to erase stored consumption data through z wave
network.
- Make sure the device is powered.
- Include the device to Z-Wave Gateway /Network
- Reset memory consumption data using Reset Command in COMMAND_CLASS_METER (see the controller’s manual).
Note: Turning the device main power off/on will not erase the consumption data as it is stored in nonvolatile memory.
Z-Wave Network
The HE-HLS01 may be operated in any Z-Wave network with other Z-Wave certified devices from other manufacturers. The HELTUN HE-HLS01 will act as a ‘repeater’ for other devices regardless of manufacturer or brand to increase the reliability of the overall network.
Including HE-HLS01 to an Existing Z-Wave Network
To add the HE-HLS01 to an existing Z-Wave network (i.e. “inclusion”), do the following:
-
Ensure the HE-HLS01 is Powered On and the LED indicator blinks red slowly (i.e. it is excluded).
-
Start the Inclusion Mode from the gateway/controller.
-
To start the inclusion process on the HE-HLS01:
a) if you want to use the device as a “Binary Switch”, double-press the service button on the device (with no more than a one-second interval between presses).
b) if you want to use the device as a “Thermostat”, press four times the service button on the device (with no more than a one-second interval between presses). -
The LED indicator will blink green quickly.
-
If the inclusion has been successful, the LED indicator will turn green for three seconds then continue slowly blinking green continuously while the HE-HLS01 is Powered On.
-
If the inclusion was not successful, the LED indicator will turn red for three seconds then continue slowly blinking red continuously while the HE-HLS01 is Powered On. In that case repeat the inclusion process (2-5) above.
Removing HE-HLS01 from Z-Wave network
To remove the HE-HLS01 from a Z-Wave network (i.e. “Exclusion”), do the following:
- Ensure the HE-HLS01 is Powered On and the LED indicator blinks green slowly (i.e. it is included in a Z-Wave network).
- Start the Exclusion Mode from the gateway/controller.
- To start the exclusion process on the HE-HLS01, double-press the service button on the device (with no more than a one-second interval between presses).
- The LED indicator will blink red quickly.
- If the exclusion has been successful, LED indicator will turn red for three seconds then continue slowly blinking red continuously while the HE-HLS01 is Powered On.
- If the exclusion was not successful, the LED indicator will turn green for three seconds then continue slowly blinking green continuously while the HE-HLS01 is Powered On. In that case repeat the exclusion process (2-5) above.
Note: If the HE-HLS01 has previously been part of a Z-Wave network and not Excluded since, Inclusion is not possible without first performing an Exclusion or Factory Reset procedure.
Security
S0, S2 unauthorized, and S2 authorized Inclusion Modes are supported. If you
use the S2 authorized Inclusion Mode the security key should be used during
the inclusion process. The Security Key is printed on a card located with this
quick start guide and also on the device.
Note: Be sure to save this key. Without the key, it is impossible to
perform an Inclusion in S2 authorized mode.
SmartStart
SmartStart-enabled products can be added to a Z-Wave network by scanning the Z-Wave QR Code shown on the product with gateways/controllers that provide for SmartStart inclusion. In this case, no further action will be required and the SmartStart product will be added automatically within ten minutes of being turned on in the vicinity of a network.
To add the HE-HLS01 to the Z-Wave network using SmartStart:
- Input the High Load Switch DSK to the controller’s Node Provisioning List (or scan the QR code)
- Power on the device.
- Wait for the adding process to complete.
- Successful adding will be confirmed by a message on the Z-Wave controller and the LED indicator on HE-HLS01 will turn green for three seconds then continue to slowly blink green continuously while the device is Powered On.
Note: The device security code (DSK) and SmartStart QR code are printed
on the rear and front of the HE-HLS01 plus on the additional Security Card
included in the packaging ( see Figure 6 ).
Note: During SmartStart inclusion the device will be included to the
gateway as a binary switch. If you want to use the device as a thermostat, use
manual inclusion process.
Associations
Association enables the HE-HLS01 to control other Z-Wave devices over the
network. An Association Group may include up to ten other devices from
different brands and/or manufacturers. The HE-HLS01 has four association
groups:
Group 1 – “Lifeline”: reports state of the device and used to communicate
with the Z-Wave gateway. Max supported nodes: 1
Note: It is not recommended to modify this group.
Group 2 – “Relay Basic Set”: is assigned to the HE-HLS01 relay state. It
sends a Basic Set command with value 255 (On) when relay goes to On state and
sends 0 (Off) when relay goes to Off state. Max supported nodes: 1
Group 3 – “S1 Basic Set”: is assigned to the HE-HLS01 external input
state. It sends a Basic Set command with value 255 (On) when external input is
shorted and sends 0 (Off) when input is open. Max supported nodes: 1
Group 4 – “Temperature Sensor”: is assigned to the HE-HLS01 external
temperature sensor and sends the sensor value when it changes. Max supported
nodes: 1
The device also can receive Basic Set command via associations. In the “Binary Switch” mode the device will change the relay state according to the value in Basic Set command. In the “Thermostat” mode the device will change the operating more according to the Parameter 33 value.
Z-Wave Plus V2 Specifications
Thermostat Generic Device Class: GENERIC_TYPE_THERMOSTAT
Thermostat Specific Device Class: SPECIFIC_TYPE_THERMOSTAT_GENERAL_V2
Binary Switch Generic Device Class: GENERIC_TYPE_SWITCH_BINARY
Binary Switch Specific Device Class: SPECIFIC_TYPE_NOT_USED
Supported Command Classes
Supported Command Classes
Command Class
| Version| Required Security Class| Binary Switch|
Thermostat
---|---|---|---|---
Z-Wave Plus Info|
V2
| none|
∨
|
∨
Association|
V2
| highest granted (S2 Authenticated, S2 Unauthenticated or S0)|
∨
|
∨
Association Group Info|
V3
| highest granted (S2 Authenticated, S2 Unauthenticated or S0)|
∨
|
∨
Multi Channel Association|
V3
| highest granted (S2 Authenticated, S2 Unauthenticated or S0)|
∨
|
∨
Thermostat Operating State|
V1
| highest granted (S2 Authenticated, S2 Unauthenticated or S0)|
Χ
|
∨
Thermostat Mode|
V3
| highest granted (S2 Authenticated, S2 Unauthenticated or S0)|
Χ
|
∨
Thermostat Setpoint|
V3
| highest granted (S2 Authenticated, S2 Unauthenticated or S0)|
Χ
|
∨
Switch Binary|
V2
| highest granted (S2 Authenticated, S2 Unauthenticated or S0)|
∨
|
Χ
Sensor Multilevel|
V11
| highest granted (S2 Authenticated, S2 Unauthenticated or S0)|
∨
|
∨
Meter|
V5
| highest granted (S2 Authenticated, S2 Unauthenticated or S0)|
∨
|
∨
Clock|
V1
| highest granted (S2 Authenticated, S2 Unauthenticated or S0)|
∨
|
∨
Transport Service|
V2
| none|
∨
|
∨
Security 0|
V1
| none|
∨
|
∨
Security 2|
V1
| none|
∨
|
∨
Version|
V3
| highest granted (S2 Authenticated, S2 Unauthenticated or S0)|
∨
|
∨
Manufacturer Specific|
V2
| highest granted (S2 Authenticated, S2 Unauthenticated or S0)|
∨
|
∨
Device Reset Locally|
V1
| highest granted (S2 Authenticated, S2 Unauthenticated or S0)|
∨
|
∨
Powerlevel|
V1
| highest granted (S2 Authenticated, S2 Unauthenticated or S0)|
∨
|
∨
Supervision|
V1
| none|
∨
|
∨
Indicator|
V3
| highest granted (S2 Authenticated, S2 Unauthenticated or S0)|
∨
|
∨
Configuration|
V4
| highest granted (S2 Authenticated, S2 Unauthenticated or S0)|
∨
|
∨
Application Status|
V1
| none|
∨
|
∨
Firmware Update Meta Data|
V5
| highest granted (S2 Authenticated, S2 Unauthenticated or S0)|
∨
|
∨
Basic|
V2
| highest granted (S2 Authenticated, S2 Unauthenticated or S0)|
∨
|
∨
Notification|
V8
| highest granted (S2 Authenticated, S2 Unauthenticated or S0)|
∨
|
∨
Meter Command Class
Meter Type
| Scale| Rate Type| Precision|
Size
---|---|---|---|---
Electric [0x01]
|
Electric_kWh [0x00]
|
Import [0x01]
|
2
|
4
Electric [0x01]
|
Electric_W [0x02]
|
Import [0x01]
|
0
|
2
Electric [0x01]
|
Electric_V [0x04]
|
Import [0x01]
|
0
|
2
Notification Types
Notification Type
|
Event/State
|
Binary Switch
|
Thermostat
---|---|---|---
Heat Alarm
| Overheat detected|
∨
|
∨
Rapid temperature rise|
∨
|
∨
System
| System hardware failure (manufacturer proprietary failure code provided)|
∨
|
∨
Power Management
| AC mains disconnected|
∨
|
Χ
AC mains re-connected|
∨
|
Χ
Over-current detected|
∨
|
∨
Over-voltage detected|
∨
|
∨
Over-load detected|
∨
|
∨
Surge detected|
∨
|
∨
Voltage drop/drift|
∨
|
∨
Load error|
Χ
|
∨
LIMITED WARRANTY
HELTUN warrants this product to be free from defects in workmanship or
materials, under normal use and service, for a period of one (1) year from the
date of purchase by the consumer (“Warranty Period”). HELTUN will extend this
Warranty Period to three (3) years from the date of consumer purchase for any
consumer who registers their warranty with HELTUN at this website page:
bonus.heltun.com. This Limited Warranty applies only to the first end-user of
the product and is not transferable.
If during the Warranty Period the product is determined to be defective or malfunctions due to workmanship or materials, HELTUN, at HELTUN’s option, shall either repair or replace the defective product. If the product is defective, (i) return it with dated proof of purchase to the place it was purchased; or (ii) contact HELTUN Customer Care by email at support@heltun.com. HELTUN Customer Care will make the determination whether the product should be returned or whether a replacement product will be sent to you.
EXCEPT AS MAY BE OTHERWISE PROVIDED BY APPLICABLE LAW, THIS LIMITED WARRANTY IS IN LIEU OF ALL OTHER COVENANTS AND WARRANTIES, EITHER EXPRESS OR IMPLIED, INCLUDING WITHOUT LIMITATION, ANY IMPLIED WARRANTIES OF MERCHANTIBILITY OR FITNESS FOR A PARTICULAR PURPOSE, OR NON-INFRINGEMENT. HELTUN MAKES NO OTHER WARRANTIES, EXPRESS OR IMPLIED.
THIS LIMITED WARRANTY DOES NOT COVER REMOVAL OR REINSTALLATION COSTS. THIS LIMITED WARRANTY SHALL NOT APPLY IF IT IS SHOWN BY HELTUN THAT THE DEFECT OR MALFUNCTION WAS CAUSED BY DAMAGE DONE BY A CONSUMER INCLUDING DURING INSTALLATION. THIS LIMITED WARRANTY IS VOID IF DEFECT(S) RESULT FROM A FAILURE TO HAVE THIS PRODUCT INSTALLED PROPERLY.
HELTUN’S SOLE RESPONSIBILITY AND THE CONSUMER’S SOLE REMEDY UNDER THIS LIMITED WARRANTY SHALL BE TO REPAIR OR REPLACE THE PRODUCT WITHIN THE TERMS STATED ABOVE. HELTUN SHALL NOT BE LIABLE FOR ANY LOSS OR DAMAGE OF ANY KIND, INCLUDING ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES RESULTING, DIRECTLY OR INDIRECTLY, FROM ANY BREACH OF ANY WARRANTY, EXPRESS OR IMPLIED, OR ANY OTHER FAILURE OF THIS PRODUCT. IN NO EVENT SHALL HELTUN’S LIABILITY EXCEED THE AMOUNT ACTUALLY PAID FOR THE PRODUCT WHETHER SUCH LIABILITY ARISES FROM A CLAIM BASED ON WARRANTY, TORT, OR CONTRACT. THESE LIMITATIONS ON LIABILITY SHALL REMAIN IN EFFECT EVEN IF HELTUN WAS ADVISED OF THE POSSIBILITY OF SUCH INJURIES, LOSSES, OR DAMAGES.
SOME JURISDICTIONS DO NOT ALLOW THE EXCLUSION OR LIMITATION OF INCIDENTAL OR CONSEQUENTIAL DAMAGES, SO THIS LIMITATION MAY NOT APPLY TO YOU. THIS LIMITED WARRANTY IS THE ONLY EXPRESS WARRANTY HELTUN MAKES ON THIS PRODUCT.
If you have any questions concerning this limited warranty, please write HELTUN Customer Care at support@heltun.com.
In the event of any conflict, discrepancy, contradiction, uncertainty or
ambiguity between English language version of this “User
Manual” and any subsequent translation into any other language thereof, the
English language version shall govern and prevail.
HELTUN, INC. A USA DELAWARE CORPORATION.
2/5 ARMENAKYAN STR., YEREVAN, 0047, ARMENIA
WWW.HELTUN.COM
SUPPORT@HELTUN.COM