Aeotec MultiSensor Gen5 ZW074-A Manual
- June 8, 2024
- Aeotec
Table of Contents
- Aeotec
- MultiSensor Gen5
- SKU: ZW074-A
- Quickstart
- Important safety information
- What is Z-Wave?
- Product Description
- Prepare for Installation / Reset
- Inclusion/Exclusion
- Communication to a Sleeping device (Wakeup)
- Quick trouble shooting
- Association – one device controls an other device
- Special Operations as Z-Wave Controller
- Configuration Parameters
- Parameter 101: Which report needs to be sent in Report group 1
- Parameter 102: Which report needs to be sent in Report group 2.
- Parameter 103: Which report needs to be sent in Report group 3.
- Parameter 111: The interval time of sending reports in Report group 1
- Parameter 112: The interval time of sending reports in Report group 2.
- Parameter 113: The interval time of sending reports in Report group 3
- Parameter 2: Enable/Disable waking up for 10 minutes when re-power on
- Parameter 252: Enable/disable all configuration parameters to be locked
- Parameter 255: Reset to default factory setting
- Parameter 3: Timeout of the motion sensor
- Parameter 4: Enable/disable the function of motion sensor.
- Parameter 40: Enable/disable the selective reporting only when
- Parameter 41: Threshold change in temperature to induce an automatic
- Parameter 42: Threshold change in humidity to induce an automatic report.
- Parameter 43: Threshold change in luminance to induce an automatic
- Parameter 44: Threshold change in battery level to induce an automatic
- Parameter 46: Enable/disable to send the alarm report of low temperature
- Parameter 5: Which command would be sent when the motion sensor
- Technical Data
- Controlled Command Classes
- Explanation of Z-Wave specific terms
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Aeotec
MultiSensor Gen5
SKU: ZW074-A
Quickstart
This is a ****
Alarm Sensor
for
U.S. / Canada / Mexico.
To run this device please connect it to your mains power supply.
To add this device to your network execute the following action:
N/A
Please refer to the
Manufacturers
Manual
for more information.
Important safety information
Please read this manual carefully. Failure to follow the recommendations in
this manual may be dangerous or may violate the law.
The manufacturer, importer, distributor and seller shall not be liable for any
loss or damage resulting from failure to comply with the instructions in this
manual or any other material.
Use this equipment only for its intended purpose. Follow the disposal
instructions.
Do not dispose of electronic equipment or batteries in a fire or near open heat sources.
What is Z-Wave?
Z-Wave is the international wireless protocol for communication in the Smart
Home. This
device is suited for use in the region mentioned in the Quickstart section.
Z-Wave ensures a reliable communication by reconfirming every message ( two-
way
communication) and every mains powered node can act as a repeater for other
nodes
( meshed network ) in case the receiver is not in direct wireless range of
the
transmitter.
This device and every other certified Z-Wave device can be used together
with any other
certified Z-Wave device regardless of brand and origin as long as both are
suited for the
same frequency range.
If a device supports secure communication it will communicate with other
devices
secure as long as this device provides the same or a higher level of security.
Otherwise it will automatically turn into a lower level of security to
maintain
backward compatibility.
For more information about Z-Wave technology, devices, white papers etc.
please refer
to www.z-wave.info.
Product Description
TheAeotecbyAeonLabsMultiSensorGen5lookslike a motion sensor and itacts like one too.But its also so much more. Installing this 1 piece of Z-Wave technology isthe same as installing 4pieces ofZ-Wavetechnology.Your home control network will immediately understand motion, temperature, humidity and light readings wherever Multisensor installed. Those intelligent readings will equate to intelligenceautomation. And intelligent automation will give you the perfect, smart home.
Prepare for Installation / Reset
Please read the user manual before installing the product.
In order to include (add) a Z-Wave device to a network it must be in factory
default
state. Please make sure to reset the device into factory default. You can do
this by
performing an Exclusion operation as described below in the manual. Every
Z-Wave
controller is able to perform this operation however it is recommended to use
the primary
controller of the previous network to make sure the very device is excluded
properly
from this network.
Reset to factory default
This device also allows to be reset without any involvement of a Z-Wave
controller. This
procedure should only be used when the primary controller is inoperable.
Press and hold the Z-Wave button that you can find in back of the product for 20 seconds and then release. This procedure should only be used when the primary controller is inoperable.
Safety Warning for Mains Powered Devices
ATTENTION: only authorized technicians under consideration of the country-
specific
installation guidelines/norms may do works with mains power. Prior to the
assembly of
the product, the voltage network has to be switched off and ensured against
re-switching.
Inclusion/Exclusion
On factory default the device does not belong to any Z-Wave network. The
device needs
to be added to an existing wireless network to communicate with the
devices of this network.
This process is called Inclusion.
Devices can also be removed from a network. This process is called
Exclusion.
Both processes are initiated by the primary controller of the Z-Wave network.
This
controller is turned into exclusion respective inclusion mode. Inclusion and
Exclusion is
then performed doing a special manual action right on the device.
Inclusion
N/A
Exclusion
N/A
Communication to a Sleeping device (Wakeup)
This device is battery operated and turned into deep sleep state most of the
time
to save battery life time. Communication with the device is limited. In order
to
communicate with the device, a static controller C is needed in the
network.
This controller will maintain a mailbox for the battery operated devices and
store
commands that can not be received during deep sleep state. Without such a
controller,
communication may become impossible and/or the battery life time is
significantly
decreased.
This device will wakeup regularly and announce the wakeup
state by sending out a so called Wakeup Notification. The controller can then
empty the mailbox. Therefore, the device needs to be configured with the
desired
wakeup interval and the node ID of the controller. If the device was included
by
a static controller this controller will usually perform all necessary
configurations. The wakeup interval is a tradeoff between maximal battery
life time and the desired responses of the device. To wakeup the device please
perform
the following action:
Press and hold the Z-Wave button for 3 seconds will trigger sending the Wake up notification command. If press the Z-Wave button 3 times, the MultiSensor will wake up for 10 minutes.
Quick trouble shooting
Here are a few hints for network installation if things dont work as expected.
- Make sure a device is in factory reset state before including. In doubt exclude before include.
- If inclusion still fails, check if both devices use the same frequency.
- Remove all dead devices from associations. Otherwise you will see severe delays.
- Never use sleeping battery devices without a central controller.
- Dont poll FLIRS devices.
- Make sure to have enough mains powered device to benefit from the meshing
Association – one device controls an other device
Z-Wave devices control other Z-Wave devices. The relationship between one
device
controlling another device is called association. In order to control a
different
device, the controlling device needs to maintain a list of devices that will
receive
controlling commands. These lists are called association groups and they are
always
related to certain events (e.g. button pressed, sensor triggers, …). In case
the event happens all devices stored in the respective association group will
receive the same wireless command wireless command, typically a ‘Basic Set’
Command.
Association Groups:
Group NumberMaximum NodesDescription
1| 5| Group 1 is assigned to the Lifeline association group and every device
has 5 nodes to associate.The Motion sensor, Humidity sensor, thermometer and
light sensor reports will be sent to the associated nodes in Group 1.
---|---|---
Special Operations as Z-Wave Controller
As long as this device is not included into a Z-Wave network of a different
controller
it is able to manage its own Z-Wave network as primary controller. As a
primary controller
the device can include and exclude other devices in its own network, manage
associations,
and reorganize the network in case of problems. The following controller
functions
are supported:
Inclusion of other devices
Communication between two Z-Wave devices only works if both belong to the same
wireless network. Joining a network is called inclusion and is initiated by a
controller.
The controller needs to be turned into the inclusion mode. Once in this
inclusion mode
the other device needs to confirm the inclusion – typically by pressing a
button.
If current primary controller in your network is in special SIS mode this and
any other secondary controller can also include and exclude devices.
To become
primary a contoller have to be resetted and then include a device.
Turn the primary controller of Z-Wave network into inclusion mode, short press the products Z-Wave button that you can find in the back of the product.
Exclusion of other devices
The primary controller can exclude devices from the Z-Wave network. During
exclusion
the relationship between the device and the network of this controller is
terminated.
No communication between the device and other devices still in the network can
happen
after a successful exclusion. The controller needs to be turned into the
exclusion mode.
Once in this exclusion mode the other device needs to confirm the exclusion –
typically
by pressing a button.
Attention: Removing a device from the network means that it is turned
back
into factory default status. This process can also exclude devices from it’s
previous
network.
Turn the primary controller of Z-Wave network into exclusion mode, short press the products Z-Wave button that you can find in back of the product.
Configuration Parameters
Z-Wave products are supposed to work out of the box after inclusion, however
certain configuration can adapt the function better to user needs or unlock
further
enhanced features.
IMPORTANT: Controllers may only allow configuring
signed values. In order to set values in the range 128 … 255 the value sent in
the application shall be the desired value minus 256. For example: To set a
parameter to 200 it may be needed to set a value of 200 minus 256 = minus
56.
In case of a two byte value the same logic applies: Values greater than 32768
may
needed to be given as negative values too.
Parameter 101: Which report needs to be sent in Report group 1
This parameter is used to configure to send the Humidity sensor,
thermometer, light sensor and battery reports automatically in Report group
1.Note: The values corresponding to the first four bits of the parameter value
may be combined to create different combinations of reports that you wish to
have sent.For example, the temperature sensor report is the value 32 and the
battery report is the value 1, so setting parameter 101 to a value of 33 will
result in both temperature sensor report and battery report to be reported.See
the full description of the parameter values for other possible settings.
Size: 4 Byte, Default Value: 255
SettingDescription
1 | The battery report is selected. |
---|---|
32 | The temperature sensor report is selected. |
64 | The humidity sensor report is selected. |
128 | The light sensor report is selected. |
Parameter 102: Which report needs to be sent in Report group 2.
This parameter is used to configure to send the Humidity sensor,
thermometer, light sensor and battery reports automatically in Report group
2.Note: The values corresponding to the first four bits of the parameter value
may be combined to create different combinations of reports that you wish to
have sent.For example, the temperature sensor report is the value 32 and the
battery report is the value 1, so setting parameter 102 to a value of 33 will
result in both temperature sensor report and battery report to be reported.See
the full description of the parameter values for other possible settings.
Size: 4 Byte, Default Value: 0
SettingDescription
1 | The battery report is selected. |
---|---|
32 | The temperature sensor report is selected. |
64 | The humidity sensor report is selected. |
128 | The light sensor report is selected. |
Parameter 103: Which report needs to be sent in Report group 3.
This parameter is used to configure to send the Humidity sensor,
thermometer, light sensor and battery reports automatically in Report group
3.Note: The values corresponding to the first four bits of the parameter value
may be combined to create different combinations of reports that you wish to
have sent.For example, the temperature sensor report is the value 32 and the
battery report is the value 1, so setting parameter 103 to a value of 33 will
result in both temperature sensor report and battery report to be reported.See
the full description of the parameter values for other possible settings.
Size: 4 Byte, Default Value: 0
SettingDescription
1 | The battery report is selected. |
---|---|
32 | The temperature sensor report is selected. |
64 | The humidity sensor report is selected. |
128 | The light sensor report is selected. |
Parameter 111: The interval time of sending reports in Report group 1
This parameter is used to configure the interval time of the sensor report
in Report group 1.
Size: 4 Byte, Default Value: 1800
SettingDescription
5 – 2678400 | The range of interval time is 5 to 2678400. |
---|
Parameter 112: The interval time of sending reports in Report group 2.
This parameter is used to configure the interval time of the sensor report
in Report group 2.
Size: 4 Byte, Default Value: 1800
SettingDescription
5 – 2678400 | The range of interval time is 5 to 2678400. |
---|
Parameter 113: The interval time of sending reports in Report group 3
This parameter is used to configure the interval time of the sensor report
in Report group 3.
Size: 4 Byte, Default Value: 1800
SettingDescription
5 – 2678400 | The range of interval time is 5 to 2678400. |
---|
Parameter 2: Enable/Disable waking up for 10 minutes when re-power on
(battery mode) the MultiSensor.
This parameter is used to enable/disable waking up for 10 minutes when re-
power on (battery mode) the MultiSensor.1. Value = 0, disable.2. Value
=others, enable.
Size: 1 Byte, Default Value: 0
SettingDescription
0| Disable waking up for 10 minutes when re-power on (battery mode) the
MultiSensor.
---|---
1| Enable waking up for 10 minutes when re-power on (battery mode) the
MultiSensor.
Parameter 252: Enable/disable all configuration parameters to be locked
This parameter is used to enable/disable all configuration parameters to be
locked.(0 =disable, 1 = enable)
Size: 1 Byte, Default Value: 0
SettingDescription
0 | Disable all configuration parameters to be locked. |
---|---|
1 | Enable all configuration parameters to be locked. |
Parameter 255: Reset to default factory setting
This parameter is used to reset product to default factory setting. (There
are just 2 values can be used).
Size: 4 Byte, Default Value: 0
SettingDescription
1431655765| Reset the product to default factory setting and be excluded from
the Z-wave network.
---|---
1| Resets all configuration parameters to default setting.
Parameter 3: Timeout of the motion sensor
This parameter is used to set the timeout for the motion sensor.Note:(1),
The time unit is second if the value range is in 1 to 255. (2), If the value
range is in 256 to 15300, the time unit will be minute and its value should
follow the below rules:a),Interval time =Value/60, if the interval time can be
divided by 60 and without remainder.b), Interval time= (Value/60) +1, if the
interval time can be divided by 60 and has remainder.(3), Other values will be
ignored.
Size: 2 Byte, Default Value: 240
SettingDescription
1 – 255 | The unit of timeout is second. |
---|---|
256 – 15300 | The unit of timeout is minute. |
Parameter 4: Enable/disable the function of motion sensor.
This parameter is used to enable/disable the function of motion sensor.1.
Value=0, disable.2. Value=1, enable.
Size: 1 Byte, Default Value: 0
SettingDescription
0 | Disable the function of motion sensor. |
---|---|
1 | Enable the function of motion sensor. |
Parameter 40: Enable/disable the selective reporting only when
measurements reach a certain threshold or percentage set in 41-44 below.
This parameter is used to enable/disable the selective reporting only when
measurements reach a certain threshold or percentage set in the parameter 41
to 44.This is used to reduce network traffic.(0 == disable, 1 == enable)
Size: 1 Byte, Default Value: 0
SettingDescription
0 | Disable the selective reporting. |
---|---|
1 | Enable the selective reporting. |
Parameter 41: Threshold change in temperature to induce an automatic
report.
Threshold change in temperature to induce an automatic report. Note:1. When
the unit is Celsius, threshold=Value.2. When the unit is Fahrenheit,
threshold=Value*1.8The accuracy is 0.1.
Size: 2 Byte, Default Value: 256
SettingDescription
0 – 65535 | Threshold of temperature. |
---|
Parameter 42: Threshold change in humidity to induce an automatic report.
Threshold change in humidity to induce an automatic report.
Size: 2 Byte, Default Value: 5
SettingDescription
0 – 100 | Threshold of humidity |
---|
Parameter 43: Threshold change in luminance to induce an automatic
report.
Threshold change in luminance to induce an automatic report.
Size: 2 Byte, Default Value: 100
SettingDescription
0 – 1000 | Threshold of luminance |
---|
Parameter 44: Threshold change in battery level to induce an automatic
report.
Threshold change in battery level to induce an automatic report.
Size: 2 Byte, Default Value: 5
SettingDescription
0 – 100 | Threshold of battery level. |
---|
Parameter 46: Enable/disable to send the alarm report of low temperature
This parameter is used to enable/disable to send the alarm report of low
temperature( <-15)1, Value=0, disable.2, Value=1, enable(Note:The MultiSensor
will report the Multi Level Temperature CC with the value=0xFFFF to controller
if the current temperature is less than -15).
Size: 1 Byte, Default Value: 0
SettingDescription
0| Disable to send the alarm report of low
temperature(&amp;amp;amp;amp;lt;-15)
---|---
1| Enable to send the alarm report of low
temperature(&amp;amp;amp;amp;lt;-15)
Parameter 5: Which command would be sent when the motion sensor
triggered.
This parameter is used to configure that which command would be sent when
the motion sensor triggered.1. Value=1, send Basic Set CC.2. Value=2, send
Sensor Binary Report CC.
Size: 1 Byte, Default Value: 1
SettingDescription
1 | Send Basic Set CC. |
---|---|
2 | Send Sensor Binary Report CC. |
Technical Data
Hardware Platform | ZM5101 |
---|---|
Device Type | Notification Sensor |
Network Operation | Reporting Sleeping Slave |
Firmware Version | HW: 4A FW: 1.02 |
Z-Wave Version | 6.51.01 |
Certification ID | ZC10-14110008 |
Z-Wave Product Id | 0x0086.0x0102.0x004A |
Frequency | XXfrequency |
Maximum transmission power | XXantenna |
Controlled Command Classes
- Basic
Explanation of Z-Wave specific terms
-
Controller — is a Z-Wave device with capabilities to manage the network.
Controllers are typically Gateways,Remote Controls or battery operated wall controllers. -
Slave — is a Z-Wave device without capabilities to manage the network.
Slaves can be sensors, actuators and even remote controls. -
Primary Controller — is the central organizer of the network. It must be
a controller. There can be only one primary controller in a Z-Wave network. -
Inclusion — is the process of adding new Z-Wave devices into a network.
-
Exclusion — is the process of removing Z-Wave devices from the network.
-
Association — is a control relationship between a controlling device and
a controlled device. -
Wakeup Notification — is a special wireless message issued by a Z-Wave
device to announces that is able to communicate. -
Node Information Frame — is a special wireless message issued by a
Z-Wave device to announce its capabilities and functions.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>