Allen-Bradley ControlLogix 5580 Controllers Modern Control System Instruction Manual

June 4, 2024
Allen Bradley

Allen-Bradley ControlLogix 5580 Controllers Modern Control System
logo

Allen-Bradley ControlLogix 5580 Controllers Modern Control System

ControlLogix 5580 Controllers

  • Standard Catalog Numbers:756-L81E, 1756-L81EK, 1756-L82E, 1756-L82EK, 1756-L83E, 1756-L83EK, 1756-L84E, 1756-L84EK, 1756-L85E, 1756-L85EK
  • No Stored Energy (NSE) Catalog Numbers: 756-L81E-NSE, 1756-L82E-NSE, 1756-L83E-NSE, 1756-L84E-NSE, 1756-L85E-NSE
  • ControlLogix-XT Catalog Numbers: 1756-L81EXT, 1756-L82EXT, 1756-L83EXT, 1756-L84EXT, 1756-L85EXT
  • Process Catalog Numbers:1756-L81EP, 1756-L83EP, 1756-L85EP

The ControlLogix 5580 controllers help enable faster system performance, capacity, productivity, and security to help meet the growing demands of smart machines and equipment for manufacturing.

  • Integrated Motion over Ether Net/IP for up to 256 axes.
  • 1 Gb embedded Ethernet port enables high performance, communications, I/O, and motion control.
  • Secure Digital (SD) card provides optional nonvolatile memory to store user program and tag data on the controller.
  • Digitally signed and encrypted firmware helps protect against malicious intent.
  • ControlLogix NSE controllers deplete their residual stored energy to specific levels.
  • ControlLogix Process controllers are optimized for process applications.
  • ControlLogix-XT and ControlLogix Process controllers are designed for temperature extremes.
  • ControlLogix Standard controllers with a K in the catalog number, ControlLogix NSE controllers, ControlLogix XT controllers, and ControlLogix Process controllers are conformal coated for extended protection in harsh, corrosive environments.

Product Advisories

ATTENTION

  • In case of malfunction or damage, no attempts at repair should be made. The module should be returned to the manufacturer for repair. Do not dismantle the module.
  • The USB port is intended for temporary local programming purposes only and not intended for permanent connection. The USB cable is not to exceed 3.0 m (9.84 ft) and must not contain hubs.
  • Use only a soft dry anti-static cloth to wipe down equipment.
  • Do not use any cleaning agents.
  • When ControlLogix 5580 Standard and ControlLogix 5580 NSE controllers are installed in a 1756 Series B Chassis, this equipment is certified for use only within the surrounding air temperature range of 0…50 °C (32…122 °F). The equipment must not be used outside of this range.
  • When ControlLogix 5580 Standard and ControlLogix 5580 NSE controllers are installed in a 1756 Series C Chassis, this equipment is certified for use only within the surrounding air temperature range of 0…60 °C (32…140 °F). The equipment must not be used outside of this range.
  • When ControlLogix-XT 5580 Controllers and ControlLogix 5580 Process controllers are installed in a 1756 Series B Chassis, this equipment is certified for use only within the surrounding air temperature range of -25…+50 °C (-13…+122 °F).
  • The equipment must not be used outside of this range.
  • When ControlLogix-XT 5580 Controllers and ControlLogix 5580 Process controllers are installed in a 1756 Series C Chassis, this equipment is certified for use only within the surrounding air temperature range of -25…+60 °C (-13…+140 °F).
  • The equipment must not be used outside of this range.
  • When ControlLogix-XT 5580 Controllers and ControlLogix 5580 Process controllers are installed in a ControlLogix-XT Series C Chassis, this equipment is certified for use only within the surrounding air temperature range of -25…+70 °C (-13…+158 °F).
  • The equipment must not be used outside of this range.

WARNING
When you press the reset button while power is on, an electric arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding. Do not use the USB port in hazardous locations.

North American Hazardous Location Approval

The following information applies when operating this equipment in hazardous locations. Products marked CL I, DIV 2, GP A, B, C, D are suitable for use in Class I Division 2 Groups A, B, C, D, Hazardous Locations and nonhazardous locations only. Each product is supplied with markings on the rating nameplate indicating the hazardous location temperature code. When combining products within a system, the most adverse temperature code lowest T number may be used to help determine the overall temperature code of the system. Combinations of equipment in your system are subject to investigation by the local Authority Having Jurisdiction at the time of installation.

WARNING
Explosion Hazard

  • Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous.
  • Do not disconnect connections to this equipment unless power has been removed or the area is known to be nonhazardous.
  • Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other means provided with this product.
  • Substitution of components may impair suitability for Class I, Division 2.
  • If this product contains batteries, they must only be changed in an area known to be nonhazardous.

European Hazardous Location Approval

The following applies to products marked

  • Are Equipment Group II, Equipment Category 3, and comply with the Essential Health and Safety Requirements relating to the design and construction of such equipment given in Annex II to Directive 94/9/EC. See the EC Declaration of Conformity at rok.auto/certifications for details.
  • The type of protection is for Ex nA IIC T4 Gc according to EN 60079-15.
  • Comply to standards: EN 60079-0:2012+A11:2013, EN60079-15:2010, reference certificate number DEMKO13ATEX1325026X.
  • Are intended for use in areas in which explosive atmospheres caused by gases, vapors, mists, or air are unlikely to occur, or are likely to occur only infrequently and for short periods.
  • Such locations correspond to Zone 2 classification according to ATEX directive 1999/92/EC.
  • Can have catalog numbers followed by a Kto indicate a conformal coating option.

IEC Hazardous Location Approval

The following applies to products with IECEx certification:

  • Are intended for use in areas in which explosive atmospheres caused by gases, vapors, mists, or air are unlikely to occur, or are likely to occur only infrequently and for short periods. Such locations correspond to Zone 2 classification to IEC 60079-0.
  • The type of protection is Ex nA IIC T4 Gc according to IEC 60079-15.
  • Such modules comply to Standards IEC 60079-0:6th Edition, IEC 60079-15:4th Edition, reference IECEx certificate number IECExUL14.0008X.
  • Can have catalog numbers followed by a “K” to indicate a conformal coating option.

Special Conditions for Safe Use

WARNING

  • This equipment is not resistant to sunlight or other sources of UV radiation.
  • This equipment shall be mounted in an ATEX/IECEx Zone 2 certified enclosure with a minimum ingress protection rating of at least IP54 as defined in EN/IEC 60529 and used in an environment of not more than Pollution Degree 2 as defined in EN/IEC 60664-1when applied in Zone 2 environments.
  • The enclosure must be accessible only by the use of a tool.
  • This equipment shall be used within its specified ratings defined by Rockwell Automation.
  • Provision shall be made to prevent the rated voltage from being exceeded by transient disturbances of more than 140% of the rated voltage when applied in Zone 2 environments.
  • The instructions in the user manual shall be observed.
  • This equipment must be used only with ATEX/IECEx certified Rockwell Automation backplanes.
  • Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous.
  • The USB port is intended for temporary local programming purposes only and not intended for permanent connection.
  • Do not use the USB port in hazardous locations.

Environment and Enclosure

ATTENTION: This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in EN 60664-1), at altitudes up to 2000 m (6562 ft) without derating. This equipment is not intended for use in residential environments and may not provide adequate protection to radio communication services in such environments. This equipment is supplied as open-type equipment for indoor use. It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that will be present and appropriately designed to prevent personal injury resulting from accessibility to live parts. The enclosure must have suitable flame-retardant properties to prevent or minimize the spread of flame, complying with a flame spread rating of 5VA or be approved for the application if non-metallic. The interior of the enclosure must be accessible only by the use of a tool. Subsequent sections of this publication may contain more information regarding specific enclosure type ratings that are required to comply with certain product safety certifications.
In addition to this publication, see the following

  • Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1, for more installation requirements.
  • NEMA Standard 250 and EN/IEC 60529, as applicable, for explanations of the degrees of protection provided by different types of enclosure.

IMPORTANT

Any illustrations, charts, sample programs, and layout examples that are shown in this publication are intended solely for the purposes of example. Since there are many variables and requirements that are associated with any particular installation, Rockwell Automation does not assume responsibility or liability for actual use based on the examples that are shown in this publication.

Parts List

The controller ships with these parts

  • A key for the mode switch
  • 2 GB Secure Digital Card (1784-SD2), pre-installed in the controller.

Required System Components

To use the controller, a chassis and power supply are required. For controller and chassis operating specifications, see the 1756 ControlLogix Controller Specifications Technical Data, publication 1756-TD001.

Component Catalog Number
ControlLogix Standard Chassis, series C and series B 1756-A4, 1756-A4K,

1756-A7, 1756-A7K, 1756-A10, 1756-A10K, 1756-A13, 1756-A13K, 1756-A17, 1756-A17K
Power supply, standard| 1756-PA72, 1756-PA72K, 1756-PA75, 1756-PA75K, 1756-PB72, 1756-PB72K,1756-PB75, 1756-PB75K,1756-PC75,

1756-PH75

Power supply, standard slim| 1756-PA50, 1756-PA50K, 1756-PB50, 1756-PB50K
Power supply, redundant| 1756-PA75R, 1756-PA75RK,1756-PB75R, 1756-PB75RK, 1756-PSCA2, 1756-PSCA2K
ControlLogix-XT Chassis, series C| 1756-A7XT, 1756-A10XT
ControlLogix-XT Power supply| 1756-PAXT, 1756-PBXT
ControlLogix-XT Slim Power supply| 1756-PA30XT, 1756-PB30XT
ControlLogix-XT Redundant Power supply| 1756-PAXTR, 1756-PBXTR

Product Dimensions

Allen-Bradley ControlLogix 5580 Controllers Modern Control System
1

Connectors and Status Indicators

Before you install the controller, make sure to follow the instructions in the ControlLogix Chassis and Power Supply Installation Instructions, publication 1756-IN005. When installing a ControlLogix controller, you can do the following

  • Place the controller in any slot.
  • Use multiple controllers in the same chassis.

You can install or remove a ControlLogix controller while chassis power is on and the system is operating.

ATTENTION
This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation. Follow these guidelines when you handle this equipment:

  • Touch a grounded object to discharge potential static.
  • Wear an approved grounding wrist strap.
  • Do not touch connectors or pins on component boards.
  • Do not touch circuit components inside the equipment.
  • Use a static-safe workstation, if available.
  • Store the equipment in appropriate static-safe packaging when not in use.

 Align the circuit board with the top and bottom guides in the chassis.

Allen-Bradley ControlLogix 5580 Controllers Modern Control System
2Slide the module into the chassis until it snaps into place. Verify that the controller is flush with the power supply or other installed modules.

Allen-Bradley ControlLogix 5580 Controllers Modern Control System
4

Install the SD Card

WARNING
When you insert or remove the SD memory card while power is on, an electric arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding. If the SD card is not already installed in the controller, then complete these steps to install the SD card

Verify that the SD card is locked or unlocked according to your

preference

Unlocked Locked For more information about the lock/unlock memory settings, ControlLogix 5580 Controllers publication 1756-UM543.

Remove the key

Allen-Bradley ControlLogix 5580 Controllers Modern Control System
6

To access the SD card slot, open the door on the controller key panel. Position the SD card so that the contact end goes into the controller,  with the contacts on the right and the label on the left. The beveled corner is on top.

SD Card

Insert the SD card into the card slot and gently press the card until it clicks into place. The card slides in easily, if it is oriented correctly. You can insert the card only one way.7. Close the door.

Close the door

Allen-Bradley ControlLogix 5580 Controllers Modern Control System
6

Reinsert the key, if desired.

Connect to an Ether Net/IP Network

WARNING
If you connect or disconnect the communications cable with power applied to this module or any device on the network, an electric arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding. If you are connecting the controller directly to an Ether Net/IP network, then connect an RJ45 cable to the Ethernet port on the controller.

ATTENTION
10 Mbps Ethernet automatic negotiations are functional. However, 10 Mbps Ethernet connections are not fully supported or intended for normal use. Use 10 Mbps Ethernet connections only if necessary during temporary setup.

Confirm Installation

After you have inserted the controller into the chassis and applied power, the 4-character display and status indicators display status information for the controller. Controllers User Manual, publication 1756-UM543, for information on how to interpret the 4-character display messages and the status indicators.

Specifications


Attribute

| 1756-L81E, 1756-L81EK,

1756-L82E,  1756-L82EK,

1756-L83E,  1756-L83EK,

1756-L84E,  1756-L84EK,

1756-L85E, 1756-L85EK

| 1756-L81E-NSE,

1756-L82E-NSE,

1756-L83E-NSE,

1756-L84E-NSE,

1756-L85E-NSE

| 1756-L81EXT,

1756-L82EXT,

1756-L83EXT,

1756-L84EXT,

1756-L85EXT

| 1756-L81EP,

1756-L83EP,

1756-L85EP

---|---|---|---|---
Temperature, operating

IEC 60068-2-1 Test Ad, Operating Cold), IEC 60068-2-2 Test Bd, Operating

Dry Heat,

IEC 60068-2-14 Test Nb, Operating Thermal Shock

| 0 °C < Ta < +60 °C +32 °F < Ta < +140 °F  for Standard Chassis, Series C

0 °C < Ta < +50 °C +32 °F < Ta < +122 °F for Standard Chassis, Series B

| -25 °C < Ta < +70 °C (-13°F < Ta < +158 °F) for XT Chassis,

Series C

-25 °C < Ta < +60 °C -13 °F < Ta < +140 °F for Standard

Chassis, Series C

-25 °C < Ta < +50 °C -13 °F < Ta < +122 °F for Standard

Chassis, Series B

Temperature, Surrounding Air max| 60 °C (140 °F) for Standard Chassis, Series C 50 °C (122 °F) for Standard Chassis, Series B| 70 °C 158 °F for XT Chassis, Series C

60 °C 140 °F for Standard Chassis, Series C 50 °C 122 °F for Standard Chassis, Series B

Corrosive Atmosphere(1)

•    ASTM B845-97 Method H Accelerated Test (20-Day Exposure)

| Severity Level G3(2) per ANSI/ISA 71.04–2013, Airborne Contaminant

Gases Severity Level CX(2)(3) per IEC 60721-3-3:2019, Chemically Active Substances

Enclosure type rating| None open style
Voltage and current ratings| 1200 mA 5.1V DC

5.0 mA  1.2V DC

Isolation Voltage| 50V (continuous), Basic Insulation type, USB port to Backplane, Ethernet port to Backplane, and USB Port to Ethernet port. Type tested at 1000V AC for 60 seconds
Weight, approx| 394 g 0.868 lb
Wire size| Ethernet cabling and installation according to IEC 61918 and IEC 61784-5-2
North American temp code| T4
ATEX Temp Code| T4
IECEx Temp Code| T4

    • These documents contain additional information concerning related products from Rockwell Automation.
      Resource| Description
      ---|---
      1756 ControlLogix Controller Specifications Technical Data, publication 1756-TD001| Provides controller specifications, including communication options, memory use, compatibilities, redundancy, and available accessories.
      1756 ControlLogix Power Supplies Specifications Technical Data, publication 1756-TD005| Provides technical specifications for ControlLogix power supplies.
      1756 ControlLogix Chassis Specifications Technical Data, publication 1756-TD006| Provides chassis specifications, including spacing requirements, mounting dimensions, and available accessories.
      ControlLogix Chassis Installation Instructions, publication 1756-IN621| Provides information on how to install ControlLogix chassis.
      ControlLogix Power Supply Installation Instructions, publication 1756-IN619| Provides information on how to install ControlLogix standard power supplies.
      ControlLogix Redundant Power Supply Installation Instructions, publication 1756-IN620| Provides information on how to install ControlLogix redundant power supplies.
      ControlLogix 5580 and GuardLogix 5580 Controllers User Manual, publication 1756-UM543| Provides information on how to configure, select I/O modules, manage communication, develop applications, and troubleshoot the ControlLogix 5580 controllers.
      Replacement Guidelines: Logix 5000™ Controllers Reference Manual, publication 1756-RM100| Compares ControlLogix 5580 controllers to ControlLogix 5560/5570 controllers, and provides guidelines on the features, functions, instruction updates, and differences between controllers.
      Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1| Provides general guidelines for installing a Rockwell Automation industrial system.
      Product Certifications website, rok.auto/certifications| Provides declarations of conformity, certificates, and other certification details.

Only applicable to modules that end with a K or XT.

  • Port Plugs must remain installed in unused ports at all times during storage and operation for the product to meet it’s corrosive atmosphere rating.
  • Up to 9.6 microns per year, corrosion rate of copper.

Additional ResourcesYou can view or download publications at rok

auto/literature.

Rockwell Automation Support

Use these resources to access support information.

Technical Support Center| Find help with how-to videos, FAQs, chat, user forums, and product notification updates.| rok auto/support
---|---|---
Knowledgebase| Access Knowledgebase articles.| rok auto/knowledgebase
Local Technical Support Phone Numbers| Locate the telephone number for your country.| rok auto/phonesupport
Literature Library| Find installation instructions, manuals, brochures, and technical data publications.| rok auto/literature
Product Compatibility and Download Center PCDC| Download firmware, associated files such as AOP, EDS, and DTM  and access product release notes.| rok auto/pcdc

Waste Electrical and Electronic Equipment WEEE
At the end of life, this equipment should be collected separately from any unsorted municipal waste. Rockwell Automation maintains current product environmental compliance information on its  at rok auto/pec. Your comments help us serve your documentation needs better. If you have any suggestions on how to improve our content, complete the form at rok auto/doc feedback.

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Allen Bradley User Manuals

Related Manuals