TRANE BAYLOAM301 Foundation Packaged Rooftop Units Instruction Manual
- June 9, 2024
- Trane
Table of Contents
TRANE BAYLOAM301 Foundation Packaged Rooftop Units
SAFETY WARNING
Only qualified personnel should install and service the equipment. The
installation, starting up, and servicing of heating, ventilating, and air-
conditioning equipment can be hazardous and requires specific knowledge and
training. Improperly installed, adjusted or altered equipment by an
unqualified person could result in death or serious injury. When working on
the equipment, observe all precautions in the literature and on the tags,
stickers, and labels that are attached to the equipment.
Warnings, Cautions, and Notices
Read this manual thoroughly before operating or servicing this unit. Safety
advisories appear throughout this manual as required. Your personal safety and
the proper operation of this machine depend upon the strict observance of
these precautions.
The three types of advisories are defined as follows:
- WARNING Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
- CAUTION Indicates a potentially hazardous situation which, if not avoided, could result in minor or moderate injury. It could also be used to alert against unsafe practices.
- NOTICE Indicates a situation that could result in equipment or property-damage only accidents.
Important Environmental Concerns
Scientific research has shown that certain man-made chemicals can affect the
earth’s naturally occurring stratospheric ozone layer when released to the
atmosphere. In particular, several of the identified chemicals that may affect
the ozone layer are refrigerants that contain Chlorine, Fluorine and Carbon
(CFCs) and those containing Hydrogen, Chlorine, Fluorine and Carbon (HCFCs).
Not all refrigerants containing these compounds have the same potential impact
to the environment. Trane advocates the responsible handling of all
refrigerants-including industry replacements for CFCs such as HCFCs and HFCs.
Important Responsible Refrigerant Practices
Trane believes that responsible refrigerant practices are important to the
environment, our customers, and the air conditioning industry. All technicians
who handle refrigerants must be certified according to local rules. For the
USA, the Federal Clean Air Act (Section 608) sets forth the requirements for
handling, reclaiming, recovering and recycling of certain refrigerants and the
equipment that is used in these service procedures. In addition, some states
or municipalities may have additional requirements that must also be adhered
to for responsible management of refrigerants. Know the applicable laws and
follow them.
WARNING
Proper Field Wiring and Grounding Required!
Failure to follow code could result in death or serious injury. All field
wiring MUST be performed by qualified personnel. Improperly installed and
grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these
hazards, you MUST follow requirements for field wiring installation and
grounding as described in NEC and your local/state/national electrical codes.
WARNING
Personal Protective Equipment (PPE) Required!
Failure to wear proper PPE for the job being undertaken could result in death
or serious injury. Technicians, in order to protect themselves from potential
electrical, mechanical, and chemical hazards, MUST follow precautions in this
manual and on the tags, stickers, and labels, as well as the instructions
below:
-
Before installing/servicing this unit, technicians MUST put on all PPE required for the work being undertaken (Examples; cut resistant
gloves/sleeves, butyl gloves, safety glasses, hard hat/bump cap, fall protection, electrical PPE and arc flash clothing). ALWAYS refer to appropriate Safety Data Sheets (SDS) and OSHA guidelines for proper PPE. -
When working with or around hazardous chemicals, ALWAYS refer to the appropriate SDS and OSHA/GHS (Global Harmonized System of Classification and Labeling of Chemicals) guidelines for information on allowable personal exposure levels, proper respiratory protection and handling instructions.
-
If there is a risk of energized electrical contact, arc, or flash, technicians MUST put on all PPE in accordance with OSHA, NFPA 70E, or other country-specific requirements for arc flash protection, PRIOR to servicing the unit. NEVER PERFORM ANY SWITCHING, DISCONNECTING, OR VOLTAGE TESTING WITHOUT PROPER ELECTRICAL PPE AND ARC FLASH CLOTHING. ENSURE ELECTRICAL METERS AND EQUIPMENT ARE PROPERLY RATED FOR INTENDED VOLTAGE.
WARNING
Follow EHS Policies!
Failure to follow instructions below could result in death or serious injury.
- All Trane personnel must follow the company’s Environmental, Health and Safety (EHS) policies when performing work such as hot work, electrical, fall protection, lockout/tagout, refrigerant handling, etc. Where local regulations are more stringent than these policies, those regulations supersede these policies.
- Non-Trane personnel should always follow local regulations.
Copyright
This document and the information in it are the property of Trane, and may not
be used or reproduced in whole or in part without written permission. Trane
reserves the right to revise this publication at any time, and to make changes
to its content without obligation to notify any person of such revision or
change.
Trademarks
All trademarks referenced in this document are the trademarks of their
respective owners.
Revision History
Model number updates in Used With information.
Inspection
Remove the contents of the kit from the shipping package and inspect for
possible damage. If any damage is found, report it immediately, and file a
claim against the transportation company. Any missing parts should be
immediately reported to your supplier and replaced with authorized parts only.
Parts List
Qty | Description |
---|---|
1 | Speed Controller |
1 | Temperature Sensor |
1 | Pressure Tap |
2 | Screws |
5 | Wire Harnesses |
1 | Pressure Transducer |
13 | Wire Ties |
1 | Grommet |
1 | Gasket |
1 | Airflow Sleeve |
1 | Installers Guide |
1 | Installed Accessory Label |
2 | Motors (only in Kit BAYLOAM302**) |
2 | Fans (only in Kit BAYLOAM302**) |
Installation
Electrical, temperature and pressure ratings
Volts, AC | 208, 240, 380, 415, 480, 600 |
---|---|
Control Voltage | 18-30 VAC |
Frequency | 50-60 Hz |
Operating Temperature | -40ºF + 140ºF (-40ºC to 60ºC) |
Full Load Amps | 10 Amps |
Transducer Pressure Control Range | 0-500 psi |
Controller
WARNING
Hazardous Voltage!
Failure to disconnect power before servicing could result in death or serious
injury.
Disconnect all electric power, including remote disconnects before servicing.
Follow proper lockout/tagout procedures to ensure the power can not be
inadvertently energized. Verify that no power is present with a voltmeter.
- Prepare the unit for installation.
- Disconnect all power from the unit.
- Remove the compressor and control box access panel(s).
- Refer to Figure 1 and Figure 2 to determine the mounting location and position of the controller inside the control box.
- Mount the controller in the appropriate position using two screws. If airflow sleeve is not installed, install it with the gasket using two screws as shown in Figure 3. If airflow sleeve is installed then proceed to next step.
- Install temperature sensor in airflow sleeve with grommet provided, as shown in Figure 3.
Figure 1. Low ambient controller location in control box – CV units
Figure 2. Low ambient controller location in control box – VFD units
Figure 3. Airflow sleeve and sensor location
Transducer and Tee
- Remove cap nut from the unit high pressure service port on the discharge lines that run from each compressor. See Figure 4.
- Install the transducer onto the tee port. See Figure 5.
- Place the tee flare nut with valve core depressor on the unit high pressure tap, where the cap nut was located.
- Tighten flare nut securely to the high pressure service port and check for leaks.
- Ensure that the transducer and tee do not come into contact with the access panel.
Figure 4.High pressure service port
Figure 5. Transducer to tee
Figure 6. Tee and transducer installed on high pressure service port
Outdoor Motor change (only for BAYLOAM302*)
WARNING
Hazardous Voltage!
Failure to disconnect power before servicing could result in death or serious
injury.
Disconnect all electric power, including remote disconnects before servicing.
Follow proper lockout/tagout procedures to ensure the power can not be
inadvertently energized. Verify that no power is present with a voltmeter.
Figure 7. Tee and transducer installed on high pressure service port
- Confirm all power to the unit has been disconnected and locked out.
- The power harness connector must be disconnected from the terminal plug on the motor, prior to removing motor.
- Remove the fan tightening screw and slide the fan out.
- Loosen the motor securing nut and bolt from bellyband and slide the motor out.
- Replace the motor with the one from kit.
- While tightening the bolt, confirm the stops on the motor shell are resting on the top edge of bellyband (in all four positions – 90 degree from center of terminal plug), and the terminal plug is opposite to the mounting bolt.
- The bolt and nut assembly, (holding the bands around motor) shall be torqued to 100 – 120 in-lb.
WARNING
Risk of Motor Falling!
Motor is mounted in such a position that it could fall when bolts are removed.
To avoid possible injury, the motor should be supported prior to removing the
bolts.
NOTICE
Equipment Damage!
Failure to follow instructions below could result in equipment damage.
Proper alignment of the motor is important to ensure optimal unit operation.
Improper alignment, over tightening or under tightening the can result in
motor slippage, fan misalignment, bearing damage and possible failure of fan
motor mounts.
-
Assemble the fan on the motor shaft with a fan tightening screw while maintaining a 3 inch distance from top cover to top of fan hub. Note: Fan hub to shaft set screw to be torqued to 130 – 150 in-lb.
WARNING
Rotating Components!
Failure to disconnect power before servicing could result in rotating components cutting and slashing technician which could result in death or serious injury.
During installation, testing, servicing and troubleshooting of this product it may be necessary to work with live and exposed rotating components. Have a qualified or licensed service individual who has been properly trained in handling exposed rotating components, perform these tasks.
Important: Dimension from bottom of grille to the highest point of fan blade shall not be less than one inch. -
Use a tool to rotate fan manually to check for minimum clearance of 0.12 inches between fan and orifice.
-
Connect the power harness female connector to the terminal plug on the motor.
Figure 8. Jumper position
Controller Operation
This electronic control will be used on an air conditioner system to reach and
maintain head pressure within an acceptable range when ambient temperature
falls below 50°F. It reads discharge pressure from a pressure transducer and
accordingly turns on and off the outdoor fan motor to maintain discharge
pressure at the selected set point.
For Constant Volume Units
Outdoor fan cycling will occur when the ambient temperature is below 50°F.
Both outdoor fans will energize and cycle at the same time. Above 50ºF, the
outdoor fans will energize at the same time without cycling.
For Units Equipped with an Optional VFD
The outdoor fans are staged based on outdoor ambient temperature. In ambient
temperatures below 50ºF, only 1 fan will energize and cycle. When the ambient
temperature reaches above 50ºF, the controller will no longer cycle outdoor
fans. The unit will stage the outdoor fans based on the unit temperature
sensor. For ambients above 60ºF +/-5ºF, both outdoor fans should be energized.
Below 60ºF +/-5ºF, single fan operation is normal.
Setting the Pressure Setpoint
When using a pressure transducer, the control will maintain condenser pressure
between 15 psig above and 15 psig below dialed pressure setpoint.The dial
pressure setpoint range is 35 psig to 465 psig. The pressure setpoint should
be adjusted to 250 psig initially. Monitor the condenser discharge pressure
and adjust the pressure setpoint so the condenser fan operates at full speed
when the ambient temperature is greater than 50°F and modulates speed when the
ambient temperature is below 50°F.
Note: There is no exact correlation between dial temperature and pressure
scales on the control.
Figure 9. Pressure setpoins
Troubleshooting
Before leaving the installation, observe for correct operation through the desired pressure range. See Table 3.
Table 3. Troubleshooting guide
Problem | Possible Cause | Possible Solution |
---|---|---|
No fan operation | No 24 volt control voltage | Check for 24 VAC at control and |
verify correct wiring. If wired correctly, check voltage across the
transformer.
No line voltage| Check voltage across the black, red, and blue OD motor leads.
If no line voltage is present, verify all wiring is correct.
Improper fan operation| Heat pump jumper not configured correctly| Refer to
the IOM or correct hook-up diagram and verify the heat pump jumper is
configured correctly.
Control is not wired correctly| See wiring diagrams. Ensure that the 24 VAC
power supply is connected in-phase with the motor power supply.
Problem| Possible Cause| Possible Solution
---|---|---
No fan modulation| No need to modulate the fan| If pressure is equal to or
greater than the head pressure control setpoint, the fan will be operating at
full speed.
No input pressure to control| Check for proper transducer and Tee
installation. Schrader valve depressor must depress Schrader valve enough to
allow refrigerant into pressure transducer.
Miswired| Check that the 24 VAC signal and the transducer are wired
up correctly into the controller.
Erratic fan operation| Control is not wired correctly| See wiring diagrams.
Pressure transducer problem| Check for proper transducer and Tee installation.
Schrader valve depressor must depress Schrader valve enough to allow
refrigerant into pressure transducer.
Dirty or blocked condenser coil| Clean condenser coil.
Fan motor is cycling on thermal overload| Dirty or blocked condenser coil|
Clean condenser coil.
Wrong motor for fan speed control application. Verify new motor was installed.
Replace with motor| Verify new motor was installed. Replace with motor
approved for fan speed control application.
Unit fails to start| Incorrect/No voltage present| Using an AC voltmeter,
measure the voltage between the 24VAC terminals. It should read approximately
24 volts. Measure line voltage between LINE1, LINE2 and LINE 3 to confirm that
line voltage is present.
Transducer malfunction or not installed| If lights are flashing alternatively,
then no probe is connected or the probe is malfunctioning. When using a
pressure transducer, with power applied to the control, use a voltmeter to
measure volts DC between COMM and P1 or P2, where the wire is connected. The
reading should be according to Table 3 below.
Table 4. Pressure vs. voltage
Pressure (psig) | Voltage (Vdc) |
---|---|
0 | 0.5 |
50 | 0.9 |
100 | 1.3 |
150 | 1.7 |
200 | 2.1 |
250 | 2.5 |
300 | 2.9 |
350 | 3.3 |
400 | 3.7 |
450 | 4.1 |
500 | 4.5 |
Trane and American Standard create comfortable, energy efficient indoor
environments for commercial and residential applications. For more
information, please visit trane.com or
americanstandardair.com.
Trane and American Standard have a policy of continuous product and product
data improvement and reserve the right to change design and specifications
without notice. We are committed to using environmentally conscious print
practices.
ACC-SVN210D-EN 03 Dec 2022 Supersedes ACC-SVN210C-EN (Nov 2020)
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>