PHILIPS SEG101 PIR Wireless WH EcoSet Basic Control System Instruction Manual

June 9, 2024
Philips

PHILIPS-SEG101-PIR-Wireless-WH-Ec PHILIPS SEG101 PIR Wireless WH EcoSet Basic Control System

PIR sensing range

  1.  Surface Installation
  2.  Installation height: 2.5-4m (typical value: 3m) Sensing distance (Figure 1-1): radius 3M (typical installing height: 3m, according to NEMA test specifica-on). The inspection distance will be reduced at other heights.

Environment

  • Storage temperature : -25–85℃;
  • Battery storage temperature: 5-30 ℃;
  • Working temperature: -20–50℃;
  • The sensor parameters in this paper are based on ta25 ℃.

Product Description

Installation method

  1. Remove installing cover
  2. Fix the installing cover to the required position with screws
  3. Release the screw and remove the battery back cover
  4. Install batteries
  5. Installing the rear cover of the battery and fix the screws
  6. Mount the sensor housing on the installing cover.
  7. The fixed position shall be able to bear a weight of ≥ 680g.
  8. Product protection grade: IP20/IP65

Note: If multiple lamps are used in one area, the minimum distance between the two sensors should be 1.5m. It can prevent false triggering.

Procedure For replacing a battery

Battery Precautions

Sensor function setting

  • After powering on, the sensor will warm up for 1 minute and enter working mode.
  • Adjust the DIP switch. Dip switches with different bit numbers control different functions.
  • Dip switches 1 and 2 adjust the holding time of the sensor.
  • Dip switches 3 and 4 adjust the background brightness when the sensor is on standby status.
  • Dip switches 5 and 6 adjust the Bluetooth transmitting power on the default network.

Note: Exit Default hold on time Settings for the sensor is 3 Min, and the background brightness is 20%.Pressing the button triggers different functions for different durationsRefer to the application guide
Note: after installing the battery, please avoid pressing the function button by mistake

Technical parameters

  • Supply: 2pcs AA battery
  • Induction angle: Maximum 360° (high hanging ceiling)
  • Mounting height: 2.5-4m (typical height 3m)
  • Induction distance: radius 3m (at height 3m, Ta 25℃)
  • Duration of held on time: 4 switches can be adjustable (3/ 10/15/30min)
  • External brightness level: 4 switches can be adjustable (20%/30%/50%/70%)
  • Dustproof and waterproof grade: IP20 (For indoor use only )

Please Pay Attention

  1. The sensor should be installed at least 2 meters away from the heat source, including air conditioning, heater, fireplace, and other heating equipment.
  2. The sensor installation should be more than 2 meters away from the location of the air outlet, which includes the air outlet of the ventilation pipe, air conditioning air outlet, fan, and other air outlet equipment
  3. There can be no shelter within the sensing range. In winter, if people wear too thick clothes, hats and gloves may not be able to sense, if people wear fewer clothes, the sensing distance will become far, summer temperature is close to the human body temperature, the sensing distance will become close.
  4. There can be no shelter within the sensing range.
  5. In winter, if people wear too thick clothes, hats and gloves may not be able to sense, if people wear fewer clothes, the sensing distance will become far, summer temperature is close to the human body temperature, the sensing distance will become close.
  6. The sensor should be installed far away from large equipment, the strong electromagnetic radiation and surges of large equipment may interfere or damage with the sensor
  7. If too much dust accumulates on the induction probe, it will affect the induction distance. It is recommended to wipe the lens gently with a soft, dry cloth.
  8. Please read this manual carefully before installing or using this product.
  9. The sensor should be installed far away from the door or window where there is wind speed and convection, otherwise, it may be triggered frequently by mistake. It is recommended that sensors be installed at a ceiling height of 3m to ensure motion coverage and detection range.
  10. Keep sensors away from routers and other signal devices (Zigbee, WIFI, etc.).
  11. Switch switching time is more than 5s to avoid incomplete recovery of the relay during the use of the product.
  12. Do not collide the lens with hard objects.
  13. Do not press the lens by hand.
  14. If the lens is deformed, contact the dealer to replace it.
  15. If an effective induction signal is generated during the lighting, the lighting time will be postponed. If someone adjusts the time during the light, it takes effect immediately.
  16. Do not cover the sensor. Do not cover or block the wireless antenna on the sensor.
  17. Considering the influence of metal structure on wire-less signal, ensure that the sensor is far away from the surrounding metal pipes and concrete steel structure in the field installation process, so as to reduce the negative impact of metal pipes and concrete steel structure on wireless communication. If there are metal pipes, concrete steel structures, and other partitions between the sensor and the lamp, the transmission distance of the wireless signal will be affect-ed.
  18. The sensors shall be installed by a qualified electrician.
  19. Sensors must not be used or stored in corrosive environments where hazardous materials such as Sulphur, Chlorine, phthalates, etc, are present.
  20. The product is IPX0 & as such is not protected against water ingress & as such we strongly recommend that the environment in which the luminaire is to be installed is suitably checked If the above advice is not taken and the luminaires are subject to water ingress, Philips / Signify cannot guarantee safe failure & product warranty will become void.
  21. When the product is low in power, please replace the battery in time. After replacing the battery, ensure that the battery is properly installed. If the suspension buckle is cracked or deformed, stop using it.
  22. If the product is not used for a long time, please remove the battery.
  23. The product contains complimentary batteries. If you find any problems such as battery swelling, leakage, or failure to work, please buy and replace them yourself.

Signify Luminaires (Shanghai) Co., Ltd.
Address:2F, Building 1, No. 2555 Hechuan Road, Minhang District, Shanghai, P.R. China Postalcode:200233

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals