BreathSafe DR540 Rotary Drill Owner’s Manual
- June 1, 2024
- BreathSafe
Table of Contents
- BreathSafe DR540 Rotary Drill
- Product Information
- Product Usage Instructions
- INSTALLATION
- SAFETY
- CRITICAL PARTS & MAINTENANCE SCHEDULE
- OPERATOR GUIDE
- SPECIFICATIONS HIGH-CAPACITY HEPA PRESSURISER
- PARTS LIST
- TECHNICAL DETAILS
- Wiring Diagram
- CABIN SEALING TEST PROCEDURE
- USER SETTINGS INSTRUCTIONS
- DATA DOWNLOAD
- INPRESS TL WARRANTY
- Documents / Resources
BreathSafe DR540 Rotary Drill
Product Information
Specifications
-
Kit Part Number: 700458
-
Contact: +61 7 3276 7833 | www.breathe-safe.com.au sales@breathe-safe.com
-
Address: 62 Mica Street, Carole Park, 4300, QLD
-
Manufacturer: SANDVIK
-
Type: DR540 / 560 Drill
-
Features: HEPA H14 Variable Speed Pressuriser, INPRESS TS Cabin
Display with CO2 Sensor, HEPA Return Air Filter -
Controlled Document: M0095
-
Issue Date: 31/08/23
-
Revision: 1
Product Usage Instructions
Installation Overview
For installing the SANDVIK DR540 / 560 Drill, follow the steps below
- Install the HEPA H14 Variable Speed Pressuriser.
- Set up the INPRESS TS Cabin Display with Data Recorder.
- Install the HEPA Return Air Filter.
Safety Instructions
When using the product, adhere to the following safety guidelines:
- Qualified staff must wear proper personal protective equipment.
- Avoid working on the pressurized system without following safe work procedures and electrical safety measures.
- Ensure all safety guards are in place when the system is running.
- HEPA filters cannot be cleaned and must be replaced at the end of their lifecycle or if damaged.
Maintenance Schedule
Follow the maintenance schedule outlined below:
- Inspect every 500 hours and replace when the filter is full.
- Data download is required to claim the 3-year warranty on Brushless Blower Motor.
- Regularly check the Turbo Pre-cleaner, Pressuriser Blower, HEPA filters, and other components as per the maintenance schedule.
FAQ
Q: Can HEPA filters be cleaned?
A: HEPA filters cannot be cleaned and must be replaced at the end of their lifecycle or if the filter media has been damaged.
Q: What safety precautions should be taken during installation?
A: Qualified staff must wear proper personal protective equipment, follow safe work procedures, and ensure all safety guards are in place.
INSTALLATION
INSTALLATION OVERVIEW
Manufacturer| SANDVIK
Type| Drill
Model| DR540 / 560
Cabin Pressure Max|
Set Auto Cabin Pressure|
SAFETY
WARNING
- THE PRESSURISATION SYSTEM DESCRIBED IN THIS MANUAL HAS THE FOLLOWING AREAS THAT MAY BE DANGEROUS IF NOT TREATED WITH GREAT CARE.
- QUALIFIED STAFF MUST WEAR THE CORRECT PERSONAL PROTECTIVE EQUIPMENT WHEN CLEANING AND SERVICING THIS UNIT DUE TO DUST AND FIBRES WHICH MAY BE CAUGHT BY THE STAGES OF AIR FILTRATION DURING NORMAL UNIT OPERATION.
- THE ELECTRICAL POWER SYSTEM IS SUPPLIED BY 12V DC OR 24V DC AND NO WORK SHOULD BE CARRIED OUT ON THE PRESSURISER SYSTEM WITHOUT THE CORRECT SAFE WORK PROCEDURES AND ELECTRICAL SAFETY MEASURES BEING TAKEN, AND ALL RELEVANT CIRCUIT BREAKERS OPENED TO ISOLATE THE CIRCUIT.
- THE AIR FILTRATION SYSTEM MAY HAVE SEVERAL TYPES OF HIGH-SPEED ROTATING EQUIPMENT INSTALLED WITH VERY SHARP EDGES. ENSURE ALL SAFETY GUARD ARE IN PLACE WHILE THE SYSTEM IS RUNNING.
- Please be aware that HEPA filters cannot be cleaned and must be replaced at the end of their lifecycle or if filter media has been damaged.
Particulate Behaviour
- This is the length of time it takes for a particle to drop from a height of 1.5m in STILL air.
- Warehouses and workshops do not have still air, so hazardous airborne particulates may remain in the air for longer, increasing the chance for workers to breathe in dust. Ensure PPE is worn when installing this system.
CRITICAL PARTS & MAINTENANCE SCHEDULE
Maintenance Schedule
- The following tables show our suggested maintenance schedule for all units.
- Please note that site conditions may alter this. Excludes high corrosion environments.
- Data download is required to claim the 3-year warranty on Brushless Blower Motor.
Inspect every 500 Hours and replace when the filter is full
Component / System | Action Required |
---|---|
Turbo Pre-cleaner | Check the operation of the Turbo PreCleaner. |
Pressuriser Blower | Ensure the blower is operational. |
HEPA Primary Filter p/n: 500000 | Inspect filter capacity indicator. |
Replace the HEPA filter when 80% or greater. Vacuum out the housing before
replacing the filter elements.
HEPA Return Air Filter P/N: 5000| Vacuum inside the cabin floor before
replacing the filter.
Filter Frame Assembly, Mounts, Seals, and Filter Housing| Check door seals,
all bolts, screws, and all mounts are secure.
Check the filter canister & ensure it is correctly fitted.
Check latches are operational and in good order.
Replace / Re-tension fixtures and fittings required.
15,000 Hours / 36 months
Component / System | Action Required |
---|---|
500 Hour Inspection | All 500-hour inspection actions. |
Pressuriser’s Blower 200002 | Replace BRUSHLESS Pressuriser |
blower.
Critical Parts
Item| Part Number| Qty.| Description| Service
Interval
1| 500000| 1| Fresh Air HEPA H14 Filter (Tested as per
EN1822)
| 1000* Hours (>80%
fan capacity)
2| 5000| 1| HEPA Return Air Filter| 500* Hours
3| 200002| 1| Brushless Blower Motor – 24V| 15,000 Hours
4| 200027| 1| BreatheSafe Digital Display – Data
Recorder (INPRESS TS)
|
Filter service hours are subject to cab sealing efficiency, site conditions, and correct system use.
Suggested Schedule Servicing
Fan Capacity Indicator
- The filter is serviceable if the motor capacity is between 10% & 80%.
- We recommend that the filter be changed if the capacity is over 80%.
- Site dependent
OPERATOR GUIDE
OPERATORS CHECKLIST
PRE-START
1.| Visually inspect the BreatheSafe system for any damage.
2.| Visually inspect the cabin for any damage to doors, windows, or
seals.
3.| Please remove dust & debris from shoes and clothes before entering
the cabin.
4.| Ensure door(s) and windows are closed correctly.
5.| Start the engine and turn the HVAC on to speed 2 (medium speed).
6.| After a fixed speed delay, the BreatheSafe display will show 50
Pascals or a pre-set value.
The system is working correctly when the
Pascal value is green.
> > There is no further action required < <
NORMAL OPERATING CONDITION
Cab Air Conditioning
- BreatheSafe recommends OEM air conditioning fan is set at mid-speed or greater to circulate air around the breathing zone and minimize CO₂.
- The acceptable operating range for a BreatheSafe fan is 10-80%. >80% recommend maintenance.
ALERTS
Fixed Fan Start Delay
· Allows the operator to carry out pre-start checks – limiting at 30% fan speed, press the red text to disable.
CO₂ Level Alert (if equipped)
· Ensure the air conditioning fan is set at mid-speed or greater to circulate air and minimize CO₂.
Low-Pressure Alarm
· Cabin is not maintaining positive pressure – check doors and windows are closed correctly.
· Refer to the maintenance department to check filters and cabin sealing. Ensure filters are serviceable.
Check Filter
· Reminder to inspect or replace the filter. The service hour meter requires re-set.
· Refer to the maintenance department.
SPECIFICATIONS HIGH-CAPACITY HEPA PRESSURISER
- Blower : Brushless Blower P/N 200002.
- Protection: Locked Rotor Protection (Sub Zero Environments) Under Voltage, Under/Over Current & Over Temperature.
- Voltage : 24VDC.
- Current Draw: 11 amps (peak).
- Note: The motor has a slow start to stop the excessive in-rush current.
- Air Flow: Up to 30-300 m3/h or 50-215 CFM.
- Pre-cleaner: Integrated VLR (Very Low Restriction). Turbo Pre-Cleaner.
- Filter Element: BreatheSafe HEPA Primary Filter (H14=99.99% MPPS) TESTED AS PER EN1822 – P/N 500000.
- Plugs & Fittings: Mining Spec. Deutsch electrical plugs as standard.
- Construction: High-strength composite construction.
- Serviceability: Easy access HEPA filter with twist-lock (TL) dust cap single assembly.
- Mounting: Heavy-duty adjustable mounting brackets.
- Design: Fully designed in SolidWorks 3D CAD & Ansys Engineering Simulation Software.
- FEA Testing: Critical components FEA (Finite Element Analyst) tested in Solid Works Simulation.
- CFD Testing: CFD (Computational Fluid Dynamics) simulations in Flow Works to ensure optimum airflow through the system.
List of Abbreviations
DH| Dual HEPA
DHPR| Dual HEPA Powered Recirculation
DHAC| Dual HEPA Activated Carbon
DHACPR| Dual HEPA Activated Carbon Powered Recirculation
CPM| Cabin Pressure Monitor
CPU| Central Processing Unit
DB| Decibel Sensor
DPM| Diesel Particulate Matter
GAS| Gas Sensor
HEPA| High-Efficiency Particulate Air Filter
HPAFU| High-Pressure Air Filtration Unit
HRAF| HEPA Return Air Filter
HVAC| Heating Ventilation and Air Conditioning
MAF| Mass Air Flow
OEM| Original Equipment Manufacturer
PM| Particulate Mass
RH| Relative Humidity
TEMP| Temperature
TS| Touch screen
UI| User Interface
VMS| Vehicle Monitoring System
VS| Vibration Sensor
OGSP| OnGuard Sensor Pod
CO2s| CO2 Sensor INPRESS TS
PARTS LIST
TL4 24V DC PRESSURISER UNIT
PRESSURISER ASSEMBLY No: 200000
Kit Part Number: 700458
TECHNICAL DETAILS
Display Key Features
- Digital cabin pressure monitoring system
- Automatic cabin pressure control
- Intelligent fan speed output
- Data logger
- Alarm for low-pressure (RS20)
- Light sensor for automatic dimming of the screen
CO2 Sensor
- CO2 Sensor Type is NDIR (Non-Dispersive Infrared)
- Sample Rate is every 2 seconds
- 12-30V DC Operating Voltage
- Automatic Altitude Compensation
- Alarm Set points are adjustable
- No setup required
Connections: 200027
Item | Destination |
---|---|
1 | PIPE A – AMBIENT PRESSURE – OUTSIDE |
2 | PIPE B – POSITIVE PRESSURE – INSIDE |
3 | RJ45 CONNECTOR – CO2 SENSOR |
4 | OVERRIDE TOGGLE SW = MAX SPEED |
Item | Destination |
---|---|
1 | 12/24 VOLT POSITIVE SUPPLY |
2 | CAN H OPTION |
3 | CAN L OPTION |
4 | SERIAL TRANSMIT RS232 |
5 | MOTOR CONTROL VOLTS OUT |
6 | ALARM + OUTPUT |
7 | TEMP SENSOR |
8 | NO CONNECTION |
9 | SERIAL RECEIVE RS232 |
10 | DOOR INPUT (+) |
11 | WINDOW INPUT (+) |
12 | 0V NEGATIVE GROUND |
Wiring Diagram
- Do not handle until MSDS & all safety precautions have been read and understood. Use personal protective equipment as required.
- Before use, carefully read the product label. Safe work practices are advised to avoid eye or skin contact and inhalation.
- Observe good personal hygiene, including washing hands before eating.
- Prohibit eating, drinking, and smoking in contaminated areas. Avoid inhalation. Mechanical extraction ventilation is recommended when the removal of atmospheric contaminants is required.
- Maintain dust/fume levels below the recommended exposure standard. For small amounts, absorb with sand, vermiculite, or similar and dispose of at an approved landfill site.
WARNING
For Professional Use Only – keep out of reach of children.
Do not ignite near or around flammable materials.
Use only in well-ventilated areas, outdoors, and/or with proper respiratory
protection.
Persons with respiratory sensitivity should avoid exposure to any smoke.
Concentrated smoke may cause severe burns to the skin, eyes, or respiratory
system.
Improper use may result in sufficient inhalation of smoke to cause respiratory
tract irritation and lung damage.
Harmful if swallowed.
DANGER
- Use only as directed. Do not handle until all safety precautions, including the Safety Data Sheet, have been read and understood. The product contains hexachloroethane. Wear protective clothing.
- If exposed or concerned, get medical advice. Store in a cool, dry, secure location.
- KEEP OUT OF REACH OF CHILDREN. Dispose of contents/container per location regulations.
- When used as directed, exposure should be limited and usually poses no hazard because the hexachloroethane is consumed inside the tube as smoke is produced.
Directions: (Smoke Bomb)
1.| Ensure other workers nearby are informed of use. Place on a non-
combustible container, away from flammable materials.
2.| Place at Blower intake, upwind of the target area, or near the center of
space.
3.| Orient “Smoke Issues Here” toward the air stream, away from surfaces.
Place the candle on a flame/heat resistance plate – if not it will melt into
the plastic surface.
4.| Ensure smoke will not create any hazard where it is anticipated to go.
5.| Ignite the emitter inside the cabin using site approved device i.e.,
solder torch or ‘lighter’, and conduct the smoke test.
6.| Do not touch or hold the smoke generator after ignition – the item becomes
very hot & remains hot after use.
Smoke Emitter Cabin Pressure Leak Test
1.| The pressuriser system is switched on (TEST MODE).
2.| Hold the smoke emitter angled down.
3.| Ignite emitter using site approved ignitor i.e., solder torch or
‘lighter’.
4.| When the product ignites, remove the lighter.
5.| If the product flames up, blow out the flame.
6.| Place the emitter in a non-flammable container place it inside the cabin
at floor level and close the door/windows.
7.| Observe smoke leaks to indicate worn-out or broken seal locations. Check
leakage points outside the cabin.
8.| Do not come into contact with or inhale smoke haze.
9.| Wait until the smoke haze completely disperses before re-entering the
cabin. Open the door to allow sufficient ventilation of smoke before entering
the cabin.
- This SWP does not necessarily cover all possible hazards associated with this equipment and should be used in conjunction with other references.
- It is designed as a guide to be used to complement training and as a reminder to users before equipment use.
Link to MSDS: SMOKE GENERATOR TQ7621AT30S.pdf
CABIN SEALING TEST PROCEDURE
Cabin Sealing Efficiency Test Procedure
1| Start Engine – Pressuriser System is ON
2| Ensure all windows & door(s) are CLOSED correctly (no cabin pressure leaks)
NOTE: for a new cabin with effective seals, you may need to open a window slightly before closing the door to bleed the static cabin air pressure outwards. Once the door is fully closed then close windows to begin testing.
3| Enter the Settings menu via the touchscreen button.
4| Select and press the System Check button to go to System Test – Max-Fan.
5| Record/photograph the maximum cabin pressure achieved.
COMMISSIONING PROCEDURES – CABIN PRESSURE
Commissioning Procedures
- Follow each step of the installation guide that was supplied with the BreatheSafe kit.
- Cabin sealing is an integral part of RS20 & ISO 23875; you must ensure that cabin seals are adequate for maintaining positive pressure.
- In addition, the site (end-user) must have the correct procedure(s) for servicing OPERATOR enclosure seals in a proactive manner rather than reactive.
- Items such as door and window seals must be in good working order or new seals FITTED before the BreatheSafe system installation.
- Touch-screen cabin pressure display/controller Part# 200027:
- System Check Function: enter the Settings menu option and select “System Check – Set Max.
- The minimum BreatheSafe requirement for cabin sealing efficiency is 250 pascals; if this result is not met, it is essential to re-examine and find pressure leaks in the enclosure and apply new sealing measures.
- Submission for commissioning procedure as per the diagram below:
- Commissioning – BreatheSafe breathe-safe.com.au
The commissioning images required are:
- ID plate / Machine Serial Number / Asset Number or Call Sign
- INPRESS TL Pressuriser location
- HEPA Return Air Filter Location Option: Powered Return Air Filter
- Cabin Pressure Display Location – Including the “System Check” maximum cabin pressure result with motor output capacity %
Fill in the BreatheSafe Service Tag with the following details:
- Machine Serial Number and Installers details
- Date installed and System Check result (max cabin pressure)
- The set cabin pressure with actual pressure and motor percentage output
- Verify the 250-pascal threshold was achieved = pass OR not achieved = fail Please upload machine and installation details in conjunction with the required images.
- A Commissioning Certificate will be sent to the email address you nominate.
- Extended warranty for (RS20 & ISO 23875) BreatheSafe Systems is only applicable to operator enclosures meeting this requirement.
BREATHESAFE SYSTEM TROUBLE SHOOTING GUIDE *TOUCH CONTROL
FAULT| POSSIBLE CAUSE| SOLUTION
*ERR error code*| Poor sensor connection| Remove & refit pod
connection cable
Corrupted coding| Access factory setup – default reset – pin 6759
Check filter alarm| Service hour timeout| Access Check
Runtime menu – reset hours via 7597 code
Temperature / CO2 error| Sensor not connected| Fit sensor or
disable via site access CO2 & or temperature menu
Pressuriser running at full speed/noisy| Filter blocked|
Service filter
Door or window open| Ensure doors & windows are securely shut
Cabin sealing capacity not adequate| Perform pressure test procedure & seal
leak points as required
Sense pipe blocked| Ensure clear & not bent
Internal sensor damaged| Replace controller
**No need to change setpoint
Filter blocking quickly| Defective cabin sealing| Perform
pressure test procedure & seal leak points as required
Pre-cleaner failed| Check operation & replace if necessary
Display blank| Poor power supply| Check the mains supply fuse &
correct voltage
Check voltage & 20AMP supply/connections at pin 1 @ monitor
Check earth continuity at controller pin 12
Failed controller| Replace monitor
Controller shows 0.0 pressure| Fresh air filter blocked|
Check filter condition & replace if required.
Low-pressure alarm| Door or window open| Ensure doors & windows
are securely shut
Cabin sealing capacity not adequate| Perform pressure test procedure & rectify
cab sealing
Pressuriser not operating| Ensure the correct voltage of 12v or 24v to
pressurizer motor pin A
Check 1.6V – 10V present at motor Pin C
Check the 20A Supply fuse
Check earth continuity Pin B
Pressure sense tube blocked| Unplug at monitor & ensure clear flow to the
external of the cabin
Ensure the pressure tube is fitted correct port A
**No need to change setpoint
Pressuriser not working| Poor power supply| Check the 20A mains
fuse & correct voltage
Ensure adequate wire size & no voltage drop
Ensure the correct voltage of 12v or 24v to pressurizer motor pin A
Check 1.6V – 10V present at motor Pin C
Poor earth| Check earth continuity @ motor pin B
Motor faulty| Replace TL4M
Access Codes:| Site Access: 7597| Factory
Setup: 6759**
USER SETTINGS INSTRUCTIONS
ENTER SET-UP MODE
- Start-Up Screen > Main Screen > Settings Button > Settings Screen > Site Access Button > Insert Pin > Site Menu
- To enter the Setup mode, press the SETTING button.
- Then enter SITE ACCESS MENU. Type in a 4-number pin and press ENTER.
SET UP PARAMETERS
- Placing the BreatheSafe 200027 unit into Setup mode allows the adjustment of the following parameters.
- Time (hours/minutes/seconds)
- Date (day/month/year)
- Pressure alarm setpoint
- Preferred cabin pressure
- Alarm delay/ intervals of alarm
- Calibration and system settings
- Resetting the data logging
- Service reminders interval gap
- Reset current runtime between services
- CO2 settings and alarms
PRESSURE SETPOINT
- The pressure setpoint changes the pressure that the cabin will be maintained. INPRESS TS maintains the pre-set pressure within the cabin compared to outside.
- Enter Setup mode and select the ADJUST SETPOINT button. Then, use the onscreen UP and DOWN buttons to change the corresponding fields.
PRESSURE ALARM SETTING
- The mining industry benchmark for cabin pressure is 50 pascals and low pressure is set at 20 pascals.
- After a delay, the alarm will activate if cabin pressure remains below the pre-set value.
- Enter Setup mode and select the ADJUST SETPOINT button. Then, use the onscreen UP and DOWN buttons to change the corresponding fields.
SERVICE INTERVAL
- Use the onscreen UP and DOWN buttons to change the service interval setpoint.
- To reset the current runtime to zero, press the RESET CURRENT RUNTIME button and enter the site access pin.
DATE & TIME SETTINGS
- Change the recorded date displayed and measured by the INPRESS TS.
ALARM BUZZER SETTINGS PRESSURE ALARM BUZZER SETTING
- To disable the buzzer, toggle through to the ENABLED and DISABLED buttons.
CALIBRATE ZERO SENSOR
- Over a long runtime, the 200027 may need recalibration. This screen allows the sensor to be recalibrated if more than 5 Pascals are out.
- To recalibrate, open windows and doors, turn off air conditioning, and any other device that may alter cabin pressure. Then, press the AUTO ZERO SENSOR button and leave the cabin while measuring. This process will reset the Zero Pressure.
CO2 SETTINGS CO2 MODULE ENABLE/DISABLE
- Enable or disable to CO2 module used for measuring CO2 levels within the cabin.
CO2 PRIMARY ALARM POINT
- The first alarm will sound when CO2 levels inside the enclosure reach this point.
CO2 SETTINGS CO2 ALARM DELAY
- After CO2 (concentration in ppm) within the cabin reaches the 1000 ppm setpoint, the alarm will sound after this designated amount of time.
- The Alarm Delay adjusts the time between the INPRESS TS measuring CO2 concentration and sounding the alarm.
- Use the onscreen ADJUST buttons to change the corresponding fields. For example, press to toggle through Disabled / 1 – 10 minutes.
CO2 CRITICAL ALARM MUTE RESET
- The critical alarm is set at 2500 PPM and cannot be changed. The mute delay, however, can be configured.
DATA DOWNLOAD
Data Download – Setting up RS232 Connection
- Plug the RS232/USB adaptor into a free USB port on your computer
- Open up TeraTerm software.
- (TeraTerm is an open-source software tool and easily accessible via online search)
- Use the following settings in TeraTerm: Serial and choose the correct port connection
- Hint: Click on the COMxx Port with the “USB serial Port” connection from the drop-down menu.
- Example: COM 21
- This connection may be different on your computer.
- Click OK once the correct communication port has been identified.
- Go to SETUP and click on Serial Port.
- Change the COM ports to the following configuration:
- Baud
- Rate: 57600 Data: 8 bit
- Parity: EVEN
- Stop: 2 bit
- Flow Control: NONE
- Data Download – Setting up RS232 Connection
- If required, you may choose to save the COM port settings. Go to Settings and click Save the setup.
- Hint: From the drop-down menu, click on the Save Setup.
- Name the file and save it.
- The next time a download is required, you may restore the setup, and the required COM PORT settings will be loaded, ready to download the data file from the 200027 unit.
- From the drop-down menu, click on the Save setup.
- Click Restore setup.
- Choose the file name you have already saved.
- From the drop-down menu, click on the Edit menu function.
- Press “Select All”.
- Select “Copy table”.
- Open a blank Excel document and click on the page. Then, right-click to paste the copied table.
- Fields are Date, time, motor (volts) output, cabin pressure (Pa), cabin pressure pre-set (Pa), and low cabin pressure alarm (Pa).
Excel Data Instructions – Unformatted
- Open an Excel sheet and select the first cell A-1. Next, press and hold down the CTRL button on your keyboard and then press the letter V on the keyboard.
- This procedure will paste the copied data onto that Excel sheet. Once that data has been pasted onto the Excel sheet, click on ‘DATA’ on the pull-down menu, followed by ‘Text to Columns’.
- Next, select ‘Delimited’ on the newly opened window and click on Next.
- Only select the ‘Comma’ button in the next window and then click ‘Finish’.
- Then, the Excel fields will update such that each piece of data is placed in the correct columns.
- The data is now ready for archiving.
Data Logging Formats
- BU No: X (the device number unique to each unit and used for identification – format = 000000)
- Time: [09:25]
- Date: [25/07/12]
- Pressure: 32 (Pascals) as an example.
Alarm Type
0| = No alarm
1| = Low-pressure alarm
2| = Window open
3| = Door open
INPRESS TL WARRANTY
Express Warranty
- All BreatheSafe products carry a warranty against defects in materials or workmanship, provided the defects are not from factors outside of BreatheSafe’s control (including neglect, lack of maintenance, improper installation or operation, unauthorized servicing repair, etc.). BreatheSafe will replace goods defective in material or workmanship at our Queensland factory or designated branch*. All parts deemed as failed or faulty must be returned to BreatheSafe for evaluation unless otherwise stated in writing.
- Note- Systems must be installed and commissioned as per BreatheSafe installation and commissioning instructions. Once commissioned, the online commissioning sheet must be filled in, extending the components warranty as below. In addition, the system must be serviced and maintained correctly and by trained and qualified personnel. This requisite includes BreatheSafe technicians, qualified automotive air-conditioning technicians, or qualified auto electricians.
Warranty period – Standard
- 1 year or 10,000 hours (whichever occurs first).
- Controllers – 1 year no extended warranty option.
- Warranty Period Extension when commissioning documents are registered online within 28 days of installation
- Extended warranty** only offered if commissioning maximum pressure test reaches at least 250Pa.
- Brushless motor fixed speed two years, or 10,000 hours (whichever occurs first).
- Variable speed brushless motor 15,000 hours, or 3 years** (whichever occurs first).
- Must be supplied with a variable speed pressure controller, data download required for 3-year warranty option. Link to online Commissioning and Extended Warranty Registration form https://www.breathe-safe.com.au/commission/
What is not covered under Express Warranty?
- Failures are due to incorrect application.
- Damage resulting from neglect, misuse, lack of maintenance, improper installation, or operation, inappropriate or abnormal use, accidental or unauthorized servicing repair.
- Failures are due to parts not being sold or approved by BreatheSafe.
- Failures arise from any other cause that is not directly related to a defect in material or workmanship.
BreatheSafe responsibilities
- If there is a defect in material or workmanship not caused by the excluded failures during the warranty period, BreatheSafe will either replace the defective goods at our Queensland factory, or designated branch. *
- Alternatively, BreatheSafe may elect to provide new replacement parts, BreatheSafe-approved repair parts, or assembled components needed to repair the defect.
- BreatheSafe reserves the right to provide a refund of the purchase price in place of replacement or repair at BreatheSafe’s discretion. The replacement or repaired product will be sent to you via freight prepaid by the customer or made available for pick-up on-site.
Users Responsibilities
- The customer should ensure that the system is maintained according to BreatheSafe service requirements and only authorized parts must be used to service and maintain BreatheSafe systems.
- In the event of a suspected warranty claim, BreatheSafe should be contacted in the first instance to arrange the repair or to assist with diagnosis. Claims should be made within one week of the repair.
- After contacting BreatheSafe, you may be required to deliver or send the parts to BreatheSafe’s
- Queensland factory or designated branch. * Link to online Warranty claim form https://www.breathe-safe.com.au/warranty/
Exclusion and Limitations on Damages and Remedies
- This warranty is provided in place of all other warranties, written or oral, whether expressed by affirmation, promise, description, drawing, model, or sample.
- To the extent allowed by law, all warranties other than this warranty, whether express or implied, including implied warranties of fitness for a particular purpose, are disclaimed.
- The maximum liability of BreatheSafe under this warranty shall not exceed the original purchase price of the product.
- Interference with the equipment by or abuse, or by operating the equipment at ambient temperatures or with electrical power characteristics outside the ranges indicated in our specification shall be excluded from this warranty, as shall consequential damages.
- Excluded from any express warranty are costs incurred concerning service outside our factory our designated service branch, including traveling time, waiting time, transport costs, and mechanical and overtime payments required.
- As per Australian Consumer Law: You are entitled to choose a refund or replacement for major failures with goods.
- If a failure with the goods or service does not amount to a major failure, you are entitled to have the failure rectified in a reasonable time.
- If this is not done, you are entitled to a refund for the goods to cancel the contract for the service, and to obtain a refund of any unused portion.
- You are also entitled to be compensated for any other reasonably foreseeable loss or damage from a failure in the goods or service.
- This express warranty gives you specific legal rights, and you may also have other rights that vary from country to country.
- +61 7 3276 7833
- www.breathe-safe.com.au
- sales@breathe-safe.com
- 62 Mica Street, Carole Park, 4300, QLD
Documents / Resources
|
BreathSafe DR540 Rotary
Drill
[pdf] Owner's Manual
DR540 Rotary Drill, DR540, Rotary Drill, Drill
---|---
References
- BreatheSafe - Intelligent HEPA H14 Cabin Air Filtration
- Home - Safe Software
- BreatheSafe - Intelligent HEPA H14 Cabin Air Filtration
- Commissioning - BreatheSafe
- Commissioning - BreatheSafe
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>