EASTRON SDM630-EV DIN Rail Smart Meter for Single and Three Phase Electrical Systems User Manual
- June 3, 2024
- EASTRON
Table of Contents
SDM630-EV
DIN Rail Smart Meter for Single and
Three Phase Electrical Systems
User Manual
2022 V1.0
SDM630-EV DIN Rail Smart Meter for Single and Three Phase Electrical
Systems
- Measures kWh Kvarh, KW, Kvar, KVA, P, F, PF, Hz, dmd, V, A, etc.
- Bi-directional measurement IMP & EXP
- Pulse output
- RS485 Modbus
- Din rail mounting 35mm
- 100A direct connection
- Better than Class 1 / B accuracy
Introduction
The SDM630-EV V2 measures and displays the characteristics of single phase two
wires (1p2w), three phase three wires (3p3w,) and three phase four wires(3p4w)
supplies, including voltage, frequency, current, power ,active and reactive
energy, imported or exported. Energy is measured in terms of kWh, kVArh.
Maximum demand current can be measured over preset periods of up to 60
minutes. In order to measure energy, the unit requires voltage and current
inputs in addition to the supply required to power the product. SDM630-EV V2
supports max. 100A direct connection, saves the cost and avoid the trouble to
connect external CTs, giving the unit a cost-effective and easy operation.
Built-in interfaces provides pulse and RS485 Modbus RTU outputs. Configuration
is password protected.
1.2 Measured Parameters
The unit can monitor and display the following parameters of a single phase
two wire(1p2w), three phase three wire(3p3w) or four phase four wire(3p4w)
supply.
1.3 Voltage and Current
Phase to neutral voltages 100 to 289V a.c. (not for 3p3w supplies)
Voltages between phases 173 to 500V a.c. (3p supplies only)
Percentage total voltage harmonic distortion (THD%) for each phase to N ( not
for 3p3w supplies)
Percentage voltage THD% between phases (three phase supplies only) Current
THD% for each phase
1.4 Power Factor and
Frequency and Max. Demand Frequency in Hz Instantaneous power:
Power 0 to 99999 W Reactive Power 0 to 99999 VAr Volt-amps 0 to 99999 VA
Maximum demanded power since last Demand reset Power factor
Maximum neutral demand current, since the last Demand reset (for 3p4w supply
only)
1.5 Energy Measurements
- Imported active energy 0 to 999999.99 kWh
- Exported active energy 0 to 999999.99 kWh
- Imported reactive energy 0 to 999999.99 kVArh
- Exported reactive energy 0 to 999999.99 kVArh
- Total active energy 0 to 999999.99 kWh
- Total reactive energy 0 to 999999.99 kVArh
1.6 Measured Inputs
Voltage inputs through 4-way fixed connector with 25mm² stranded wire
capacity. single phase two wire(1p2w), three phase three wire(3p3w) or four
phase four wire(3p4w) unbalanced. Line frequency measured from L1 voltage or
L3 voltage.=
1.7 Accuracy
- Voltage 0·5% of range maximum
- Current 0·5% of nominal
- Frequency 0·2% of mid-frequency
- Power factor 1% of unity (0.01)
- Active power (W) ±1% of range maximum
- Reactive power (VAr) ±1% of range maximum
- Apparent power (VA) ±1% of range maximum
- Active energy (Wh) Class 1 IEC 62053-21 Class B EN50470-1/3
- Reactive energy (VArh) Class 2 IEC 62053-23
- Response time to step input 1s, typical, to >99% of final reading, at 50 Hz.
1.8 Interfaces for External Monitoring
Three interfaces are provided:
- 2 RS485 communication channels via protocol remotely.
- Pulse output indicating real-time measured energy.
1.9 Pulse Output
Pulse output is non-configurable. It is fixed up with active kWh. The constant
is 400imp/kWh.
1.10 RS485 Output for Modbus RTU
There 2 two channels of RS485 Modbus RTU.
For Modbus RTU, the following RS485 communication parameters can be configured
from the
Set-up menu: • 1st Modbus Output (configurable):
Baud rate 2400, 4800, 9600(default), 19200, 38400 Parity none
(default)/odd/even
Stop bits 1 or 2
RS485 network address nnn – 3-digit number, 001 to 247
• 2n Modbus Pitput (non-configurable): Baud rate 9600 Parity none
Stop bits 1 Modbus™ Word order Hi/Lo byte order is set automatically to normal
or reverse. It cannot be configured from the set-up menu.
1.11 Reference Conditions of Influence Quantities
Influence Quantities are variables that affect measurement errors to a minor
degree. Accuracy is verified under nominal value (within the specified
tolerance) of these conditions.
- Ambient temperature 23°C ±1°C
- Input frequency 50Hz(MID) 50 or 60Hz ±2% (non- MID)
- Input waveform Sinusoidal (distortion factor < 0·005)
- Magnetic field of external origin Terrestrial flux
1.12 Environment
- Operating temperature 3K6(-25°C to +55°C),Default 3K7(-40°C to +70°C)
- Storage temperature -40°C to +70°C*
- Relative humidity 0 to 90%, non- condensing
- Altitude Up to 2000m
- Warm up time 5S
- Vibration 10Hz to 50Hz, IEC 60068-2-6, 2g
- Shock 30g in 3 planes * Maximum operating and storage temperatures are in the context of typical daily and seasonal variation.
1.13 Unit Characteristics
The Unit can measure and display:
- Line voltage and THD% (total harmonic distortion) of all phases
- Line Frequency
- Currents, Current demands and current THD% of all phases
- Power, maximum power demand and power factor
- Active energy imported and exported
- Reactive energy imported and exported The unit has password-protected set-up screens for:
- Changing password
- Supply system selection 1p2w, 3p3w,3p4w
- Demand Interval Time(DIT)
- Reset for demand measurements
The pulse output indicates real-time energy measurement. 2 RS485 outputs allows remote monitoring from another display or a computer.
Start-up Screens
The interface performs a self-test and indicates the result if the test passes. The second screen indicates the firmware installed in the unit and its build number. *The build number(41 01.00) is for reference only The actual build number changes according to product requirements.
Meter SN, Modbus ID and baud rate setting
After a short delay, the screen will display active energy measurements.
2.1 Measurements
The buttons operate as follows:
| Selects the Voltage and Current display screens
In Set-up Mode, this is the “Left” or “Back” button.
---|---
| Select the Frequency and Power factor display screens
In Set-up Mode, this is the “Up” button
| Select the Power display screens
In Set-up Mode, this is the “Down” button
| Select the Energy display screens
In Set-up mode, this is the “Enter” or “Right” button
2.2 Voltage and Current
Each successive pressing of the button selects a new range:
| Phase to neutral voltages(3p4w)
---|---
Phase to neutral voltages(3p3w)
Current on each phase
Neutral current
2.3 Frequency and Power Factor and Demand
Each successive pressing of the button selects a new range:
| Power Factor
---|---
Maximum Current Demand
Maximum Power Demand
2.4 Power
Each successive pressing of the button selects a new range:
| Instantaneous Active Power in W
---|---
Instantaneous Reactive Power in VAr
Instantaneous Volt-amps in VA
Total W, VArh, VA
2.5 Energy Measurements
Each successive pressing of the button selects a new range:
| Total kWh and time will be showed when no charging
---|---
Total kWh and charged kWh will be showed when charging
CSID Numbers And current time will be showed when charging
Total active kWh, import active kWh, export active kWh
Total reactive kWh, import reactive kWh, export reactive kWh
2.6 Set-up
To enter set-up mode, pressing the button for 3 seconds, until the password
screen appears.
Setting up is password-protected so you must enter the correct password
(default ‘1000’) before processing. If an incorrect password is entered, the
display will show:
PASS Err
To exit setting-up mode, press repeatedly until the measurement screen is
restored.
Setting – Button operation
Set-up Entry Methods
Some menu items, such as password, require a four-digit number entry while
others, such as supply system, require selection from a number of menu
options.
3.1 Menu Option Selection
- Use the and buttons to select the required item from the menu. Selection does not roll over between bottom and top of list.
- Press to confirm your selection.
- If an item flashes, then it can be adjusted by the and buttons. If not, there maybe a further layer.
- Having selected an option from the current layer press to confirm your selection. The SET indicator will appear.
- Having completed a parameter setting, press to return to a higher menu level. The SET indicator will be removed and you will be able to use the and buttons for further menu selection.
- On completion of all set-up, press repeatedly until the measurement screen is restored.
3.2 Number Entry Procedure
When setting up the unit, some screens require the entering of a number. In
particular, on entry to the setting up section, a password must be entered.
Digits are set individually, from left to right.
The procedure is as follows:
- The current digit to be set flashes and is set using the and buttons.
- Press to confirm each digit setting. The SET indicator appears after the last digit has been set.
- After setting the last digit, press to exit the number setting routine.
3.3 Main set
System type| From the Set-up menu, use and buttons to select the System
option. The screen will show the currently selected system type.
---|---
Password| Use the and to choose the change password option.
Reset| Press to enter the selection routine. If succeed, the cursor will jump
back to Reset.
Press to exit the number setting routine and return to the Set-up menu. SET
will be removed.
3.4 Communication set
Addr | From the Set-up menu, use and buttons to select the Address ID. |
---|---|
Baud | From the Set-up menu, use and buttons to select the Baud Rate option. |
Parity | From the Set-up menu, use and buttons to select the Parity option. |
3.5 Time set
Data| From the Set-up menu, use and buttons to select the data.Use to move
cursor
---|---
Time| From the Set-up menu, use and buttons to select the data. Use to move
cursor
DMD| From the Set-up menu, use and buttons select the dmd. Setting options:
0, 5, 8, 10, 15, 20, 30, 60
ZONE| From the Set-up menu,use and buttons to select the ZONE. Setting
range:-12~12
Backlight| From the Set-up menu, use and buttons to select the Backlight.
Setting options: on,10, 30, 60, 120, off
use and buttons to select the time interval. Press to confirm the set-up.
3.6 Record
Record| From the Set-up menu, use and buttons to select record data. Max.:
lastest 10 records
---|---
use and buttonsto select the time interval.
Warnings
Important Safety Information is contained in the Maintenance section.
Familiarize yourself with this information before attempting installation or
other procedures. Symbols used in this document:
Risk of Danger : These instructions contain important safety information.
Read them before starting installation or servicing of the equipment.
Caution: Risk of Electric Shock
Wiring diagram
- Three Phase Three Wires
- Three Phase Four Wires • Single Phase Two Wires
Dimensions
Wiring Torque
Terminals| |
---|---|---
COMM/Pulse/2T| 0.5-1.5mm²| 0.4Nm
Load| 4-25mm²| 3Nm
MID Certificate
EU Declaration of Conformity
EU Declaration of Conformity
We, Zhejiang Eastron Electronic Co LTD
No.1369,Chengnan Rd. Jiaxing, Zhejiang, 314001, China
Ensure and declare that electricity meter types:
SDM630-EV with the measurement range
1. 3 x 230/400V 50Hz, 0.5-10(100)A 400imp/ kWh.
Are in conformity with the type as described in the EU-type examination
certificate
0120/ SGS0151
The fulfillment of the essential requirements set out in Annex I and in the
relevant instrument specific Annexes has been demonstrated.
The electricity meter types described above are in conformity with the
relevant Union harmonization legislation and satisfy the appropriate
requirements of the Directive 2014/32/EU with the following standards:
EN50470-1:2006, Electricity metering equipment (AC) part 1: General
requirements, tests and test conditions. Metering equipment (class indexes A,
B and C) EN50470-3:2006, Electricity metering equipment (AC) Part 3:
Particular requirements- Static meters for active energy (class indexes A, B
and C)
This Declaration of Conformity is issued under the sole responsibility of the
manufacturer.
Signed on behalf of Zhejiang Eastron Electronic Co., LTD.
Signature: Date: 2022-07-05
Position: General Manager
ZHEJIANG EASTRON ELECTRONIC,CO.,LTD
CONTACT US
If you have any question, please feel free to contact our sales team.
Eastron Europe Limited; Suite 20 Cornwallis House, Howard Chase, Basildon,
Essex SS14 3BB.
Tel: 0203 758 3494
Email:sales@eastroneurope.com
www.eastrongroup.com
If you have any question, please feel free to contact our sales team.
Tel: 0203 758 3494
Email:sales@eastroneurope.com
www.eastrongroup.com
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>