ZUBR 3F Overvoltage Protection Instruction Manual
- June 3, 2024
- ZUBR
Table of Contents
Technical passport and installation and operation manual
3F
Overvoltage protection for professionals
Voltage relay ZUBR 3F is intended to protect industrial and household three-
phase electrical equipment (including three-phase electric motors) from
blackout, exceeding of permissible voltage limits, phase (voltage) unbalance.
The voltage relay also monitors the order of the phase sequence and has an
adjustable tripping time for phase (voltage) unbalance.
SUPPLY PACKAGE
Voltage relay UBR 3F | 1 piece |
---|---|
Guarantee card technical passport and manual, | 1 piece |
Shipping box | 1 piece |
TECHNICAL DATA
Maximum load current | 5 А |
---|---|
Maximum load power | 1 00 А 0 V |
A skew (asymmetry) phases | 10–80 V |
Voltage limit | upper 220–280 120–210 V lower V |
Break-time at increasing | not more then 0,04 sec |
Break-time at lower: > V 120 120 < V | not more then se 1 с not more then |
0,04 с se
Power Volt| not less then V 100 420 not more then V
Load switch-on delay|
The number of operating cycles without load of| not less cycles 00 000 20 0
cycles
Relay type| electromagnetic
Connection| not more then mm 2,5 2
Маss| 0,1 5 kg ±10 %
Overall dimensions ( ) w h d х х| 52 67 90 х х mm
IP to GOST 14254| IP20
READ BY THE END OF THIS DOCUMENT,
before the installation and operation of the device.
This will help to avoid possible danger, mistakes and misunderstandings.
IT IS NECESSARY TO USE A CONTACTOR (not included in the scope of supply) for
switching threephase equipment.
RELAY CAN BE USED AS A FULL-FLEDGED
SINGLE-PHASE PROTECTION then for the normal operation of the relay, one phase
and zero is enough.
CONNECTION SCHEME
The phases for measurement and supply are determined by the indicator and fed
to the relay.
Terminals 1, 2 or 3, 4 are required to control a three-phase contactor.
No zero voltage relay will not work.
Scheme Option of wiring diagram of ZUBR 3F and contactor with 230 V winding
Scheme Option of wiring diagram of ZUBR 3F and contactor with 400 V winding
Scheme Option of the connection diagram of ZUBR 3F and contactor with 230 V winding.
INSTALLATION
The appliance is intended for installation inside residences.
The risk of moisture or humidity in the installation site should be
minimal.The ambient temperature during the installation should be within
–5…+45 ° .
The appliance is installed in a special box with standard mounting rail 35 mm
film (DIN rail) and takes in width of three standard module on 18 mm. The
height of a device has to be in the range from 0,5 to 1,7 m from the floor.
The appliance is installed and activated after installation and inspection of
the voltage.
For protection against short circuit and abuse power load in the chain must
always be in front of the appliance set the automatic circuit-breaker ( QF
cheme ) ( s 1 ). , 2 To protect person from electric shock leak is set afety
shutdown device (QD) .
Terminals of the device designed for wire cross section up 2,5 mm to ². . It
is advisable to use a soft wire. Tighten terminal with derived average 0,5
Н·m. Clean the end wires of 8 ±0,5 mm Wires protracted in terminals with a
screwdriver with a shank width not more than 3 mm. Screw with shank width more
than 3 mm may apply mechanical damage to terminals. This could result in loss
of warranty.
GUARANTEE TERMS
The warranty for ZUBR devices is valid for 60 months from the date of sale,
provided that the instructions are followed. The warranty period for products
without a warranty certificate is counted from the date of production.
If your device is not working properly, we recommend that you first read the
section «Possible problems». If you cannot find an answer, contact Service
Center. In most cases, these actions resolve all issues.
If you continue to have issues with the device, please send it to a Service
Center or to the store where you purchased the device. If your device is
defective due to our fault, we will repair or replace it under warranty
within 14 business days.
Please see the full text of the warranty and the data you need to send to your
Service Center. The website address can be found in the instructions in the
Contacts section.
GUARANTEE CARD
serial number:…………………………………………………………….
date of purchase agreements:…………………………………….
seller, stamp:……………………………………………………………
an owner contact for a service center:……………………..
EXPLOITATION
3F will immediately begin to display the voltage in three phases. If the voltage is normal, the voltage will be applied to the load after the set time and the red indicator will light up.
Use the middle button to navigate through the menu (table ). Use the 1 «+ » «
–» and buttons to change the parameters. After pressing the button for the
first time the parameter will flash, after pressing it for the second time the
parameter will change. In 5 sec after the button was pressed the indicator
will return to displaying the system voltage.
All settings are stored. in NON-VOLATILE MEMORY When setting the voltage
limits USE THE PROTECTED EQUIPMENT TECHNICAL DOCUMENTATION.
Setting trip limits ( factory setting V V 242 / 198 ) To view the upper limit,
press the «+» button, lower — «–» . To change the limit as necessary use the
and «+» «–» .
**Delay in the load starting after a failure( control is described in able t
- ** During a short-time voltage jump before the countdown for 2 sec, an emergency situation will be displayed, then for 2 seconds the current and remaining time before the load is switched on. Screen during the delay countdown:
current phase voltage time to turn on the voltage in seconds current phase number
FOR PROTECTION OF REFRIGERATION
EQUIPMENt, where there is a compressor, it is recommended to set a delay of
turning on load 120–180 sec. It will allow to increase the service life of the
compressor .
Factory reset
Hold the three buttons at the same time until message appears. After releasing
the buttons, the settings will be reset and the device will restart. «dEF»
Log for 100 accidents
The device stores in non-volatile memory the voltage values at which the load
was interrupted. To enter the log, press the « » button. ≡ Log entries are
displayed in order from the last to the oldest («n 0» is the last entry, «n99»
is the oldest).
To move through the log and view previous alarms, use the » or «+ « »–
buttons. In the first 2 seconds, the relay wil display the number and type of
the alarm. In the next 2 econds, it will display the value.
Examples of alarms log entries:
Phase unbalance alarm. The imbalanced phases will blin.
| the record №1
voltage imbalance
imbalance value: 45 — V
---|---
| the record №1
voltage imbalance
imbalance value: 45 — V
Upper limit alarm.
| the record №2
exceeding the limit
---|---
| the voltage value that has exceeded the limit will flash alternating with
if the lower limit is exceeded, and with , if the upper limit is
exceeded.
Phase sequence failure alarm.
| the record №3
sticking, phase sequence disturbance
---|---
| phase sequence at the time of power cut.
To clear the log file, enter it by pressing the middle button once. Then hold the middle button for 3 seconds until the message appears «Err» . Keep holding the middle button until the message appears «Err rSt» . After releasing the button, the log file will be cleared. If the log file is empty, after pressing the middle button, the relay screen will display _ « » .
Table 1.
FUNCTION MENU| Press « »≡| Screen| Notes
---|---|---|---
View the log for 100 accidents| 1 time| | The log stores the cause of the load
shedding. If several faults occur simultaneously, the log entries will be
made according to the following priority :
1. Three-phase fault or incorrect phase sequence.
2. Voltage imbalance.
3. Exceeding the upper or lower limit.
Delay in the load starting after a failure (factory setting se 3 с, 3– 600 с
a range of change se )| 2 times| | It is used to protect compressor equipment.
It is recommended to set a delay of turning on load 120–180 sec. It will allow
to increase the service life of the compressor.
Phase unbalance voltage ( 20 , 10–80 factory setting V a range of change
V)| 3 times| | To disable, increase the unbalance value until the «oFF»
message appears. If the load is switched off due to a violation of the phase
unbalance voltage limit, the v current phase voltages will alternate on the
screen and current phase unbalance in volts numbers of the phases with
unbalance
The phase unbalance disconnection time ( 1 с, 0–30 с) factory setting se a
range of hange se| times| | Permissible time of excessive voltage
imbalance.
If the protection trips frequently, increase the time or the value of the
phase- alteration voltage so that the protected equipment is tolerant.
Phase sequence (factory setting on ) « »| 5 times (4 times, if «Phase
unbalance voltage» is off)| | If the phase sequence is violated, the current
phase sequence and the voltage across them will alternate on the screen. The
phase sequence is always determined relative to phase L1.
No-phase control (factory setting on ) « »| 6 times (5 times, if «Phase
unbalance voltage» is off)| | No-phase control is only possible when the
«Phase Unbalance Voltage» menu is off. When the function is disabled, the
device will not interrupt the load when there is no voltage on the phase(s).
Professional model of the tripping time when the voltage goes beyond the
limits (factory setting «oFF» )| 7 times (6 times, if «Phase unbalance
voltage» is off)| | Does not disable the protected equipment at safe voltage
deviations in value and duration.
More details about the tripping time model when the voltage is out of range
see Table 2.
Correction of voltage ( 0 , ±20 ) factory setting V a range of change V| 8
times (7 times, if «Phase unbalance voltage» is off)| | You can use
correction if voltage indications on the screen of the device and your
reference device differ.
To switch between the corrections for each phase, use the « »≡
button, the fourth press brings you back to the function menu
number of the current phase
correction in volts
Hysteresis (factory setting 1 V, a range of change 0–5 V)| 9 times (8 times,
if «Phase unbalance voltage» is off)| | It is necessary to reduce the number
of the device operations by the limit, when the voltage in the network is
close to the limit and is not stable.
Maximum number of protection operations in sequence (factory setting 3
operations, a range of change 1–5)| 10 times ( times, if «Phase unbalance 9
voltage» is off)| | Limits the number of repeated trips of the device by the
limit, if no more than 20 seconds have elapsed between shutdown at the limit
and turn on the load. To disable this function, select «oFF».
Enable/disable the screen in the standby mode (factory setting «on»)| 11
times ( times, if «Phase unbalance voltage» is off) 10| | To disable this
function, select «oFF». Turns off the screen after 30 seconds after the last
interaction with the device and in the absence of an emergency situation. In
the event of an emergency situation the screen will flash. To exit the sleep
mode, press one of the buttons once.
Type of voltage on-delay ( factory setting «tAr»)| 12 times ( times, if
«Phase unbalance voltage» is off) 11| | «tAr» time after voltage recovery —
delay is counted from the moment of voltage recovery. «tAo» time after
switching off — delay is counted from the moment the relay is turned off.
This type of delay takes into account response time of the emergency in the
total on-delay time.
Viewing of calculated linear stresses
Hold the button « »≡ for 3 sec. At the corresponding screens, the phase
numbers will appear, between which linear voltages are calculated. When
releasing the screens for 30 sec calculated linear voltages will be displayed
with an accuracy of 2-3 V.
A tripping counter
(not discharged) Hold the button « »≡ for 15 sec
Viewing of firmware version
Hold the button « »≡ 2 for 1 sec. The manufacturer reserves the right to
modify the firmware to enhance the device technical characteristics.
Table Models shutdown exit time voltage beyond 2.
The usual default | Upper limit | 220–280 V | 1 сse |
---|---|---|---|
Lower limit | 120–210 V | 0,04 сse | |
< V 120 | 0,04 сse | ||
Professional | Upper limit | > V 264 | 0,04 сse |
220–264 V | 0,5 сse | ||
Lower limit | 176–210 V | 10 сse | |
154–176 V | 0,5 сse | ||
< V 154 | 0,04 сse |
POSSIBLE PROBLEMS, CAUSES AND WAYS TO OVERCOME THEM
At turning on neither indicator nor screendo not shine
Possible cause: there is no power supply voltage.
It is necessary to:ensure supply voltage presence.
After turning on on the screennormal voltage level, but load is not turning on
Possible cause: the current voltage in the network is close to the established
limits and not stable.
It is necessary to: check the values of the limits; increase their values so
that the protected equipment is tolerated to them.
In other cases, please, address to a service centre.
Frequent load trip
Possible cause: underestimated (overestimated) value of the upper (lower)
limit.
It is necessary to: increase the value of the limits so that the protected
equipment is tolerant of their values.
ADDITIONAL INFORMATION
Do not fire and do not throw away the device with the household waste.
After the end of its service life, the product must be disposed of in
accordance with applicable law.
Transportation of goods carried in the package, ensuring the safety of the
product.
The deive is transported by any kind of transport (rail, sea, motor, air
transportation).
Date of manufacture is on the back side of device.
Application time is unlimited.
The device does not contain harmful substances.
If you have any questions or you something will not clear, call the Service
centre the telephone number listed below.
SAFETY INSTRUCTIONS
Carefully read and become aware of yourself these instructions.
Connection of the device must be done by a qualified electrician.
Before the installation (dismantling) and connection (disconnection) of the
device, turn off voltage supply and also act according to the «Rules of an
arrangement of electric installations».
Turning on and off or and configure the device should be with dry hands.
Do not connect the device to the network disassembled.
Avoid hitting of water or moisture to the device.
Do not expose the device to extreme temperatures (higher than 40 º or below
-5°C) and high humidity.
Never clean the device with the use of chemicals such as benzene, solvents.
Do not store the device and do not use it in areas with the dust.
Do not attempt to disassemble and repair the device.
Do not exceed the landmarks value adaptor and power.
To protect against overvoltage caused by lightning discharges, use a lightning
protector.
Protect the children from games with the working device, it is dangerous
Low
Voltage Directive 2014/35/E U 1 30 U
EMC Directive 20 4/ /E
Manufacturer and vendor: DS ELECTRONICS, LTD
04136, Ukraine, Kyiv region, Kyiv, 1–3 Pivnichno-Syretska str.
+38 (0 ) 228-73-46,44 service center : +38 (050) 450-30-15
support@dse.com.ua www.ds-
electronics.com.ua/en/