ZUBR I25 Current Control Relays Instruction Manual

June 8, 2024
ZUBR

ZUBR-I25-Current-Control-Relays-logo

ZUBR I25 Current Control Relays

Installation and operation manual

ZUBR-I25-Current-Control-Relays-01

Low Voltage Directive 2014/35/EU
EMC Directive 2014/30/EU

Before the installation and use of the device, please refer to the end into this document.
This will help avoid possible, danger, mistakes and misunderstanding.

Purpose

Current control relays is designed to protect electrical AC overload current or deviation from the set limits.
Using the control relays current can limit power, which is consumed, remote equipment, as well as to control the normal work of single-phase motors.
Current relay with a polarized relay (see Specification) does not disconnect the load when the supply voltage fails.
The load is only disconnected when the set current limits are exceeded.

Warning! It is forbidden to use to protect equipment, which runs from the sources of modified sine, uninterruptible power supply output voltage sinusoid are not Long operation (more than 5 minutes) from the following sources voltage may damage and lead to not warranty repair.

Supply package

  • Current control relays 1 pieces
  • Guarantee certificate and card 1 pieces
  • Technical passport, manual 1 pieces
  • Shipping box 1 pieces
Connection scheme

Supply voltage (100-400 V, 50 Hz), which will be controlled by current, served on terminals 1 and 2, while phase (L) is determined by the indicator and activated on terminal 2, and zero (N) — terminal 1.

The connecting voltage wires connected to terminal 3 and zero terminal block (not included).

DONOT connect voltage with surge zero in terminal 1!

Scheme 1.
The simplified internal circuit and connection scheme

Installation

The appliance is intended for installation inside residences. The risk of moisture or humidity in the installation site should be minimal. When installing in the bathroom, toilet, kitchen, pool appliance must be located in a shell with protection degree not below IP55 per GOST 14254 (partial protection from dust and weatherproof in any direction).

Technical data

№| Parameters| ZUBR I25| ZUBR I32| ZUBR I40| ZUBR I50| ZUBR I63
---|---|---|---|---|---|---
1| Rated load current| 25 А (max 30 А in 10 minutes)| 32 А (max 40 А in 10 minutes)| 40 А (max 50 А in 10 minutes)| 50 А (max 60 А in 10 minutes)| 63 А (max 80 А in 10 minutes)
2| The main current limit| 0,1–25 А| 0,1–32 А| 0,1–40 А| 0,1–50 А| 0,1–63 А

3

|

Current measurement accuracy

|

0,5–32А ± 0,1 А

|

0,5–32А ± 0,1 А
32–40А ± 0,2 А
40–50А ± 0,3 А

| 0,5–32А ± 0,1 А
32–40А ± 0,2 А
40–50А ± 0,3 А
50–63А ± 0,5–0,6 А
4| Rated power| 5 500 VА| 7 000 VА| 8 800 VА| 11 000 VА| 13 900 VА
5| Consumption current at 230 V| not more than 78 mA| not more than 65 mA
6| The number of operating cycles under load of not less cycles| 100 000 cycles| 10 000 cycles
7| The number of operating cycles without load of not less cycles| 1 000 000 cycles| 500 000 cycles
8| Relay type| electromagnetic| polarized
№| Parameters| Value|
9| The delay time of the load off| 0–240 sec
10| The delay time of the load on| 3–600 seс
11| Power Volt| not less than 100 V not more than 420 V
12| Device weight| 0,21 kg ±10 %
13| Overall dimensions| 70 × 85 × 53 mm
14| Connection| not more than 16 mm²
15| IP to GOST 14254| IP20
16| Power consumption| not more than 1,5 kW/m

be within –5…+45 °С.
The appliance is installed in a special box, which allows to conduct the easy installation and operation. It should be equipped with standard mounting rail 35 mm width (DIN rail). The appliance takes in width of three standard module on 18 mm.
The height of the appliance should be in the range from 0,5 to 1,7 m from the floor. The appliance is installed and activated after installation and inspection of the voltage.
The relay is installed after the protective circuit breaker (CB), which backs up protective function. The circuit breaker (CB) is installed in the phase cable break as shown on Layout 2. It must be designed for the rated load current of your current relay.
To protect person from electric shock leak is set SSD (safety shutdown device).

To connect your device:

  • fix the appliance on the mounting rail (DIN);
  • take a wire;
  • make the connection according to the passport.

Terminals of the device designed for wire cross section up to 16 mm2. To reduce mechanical load on the terminals it is desirable to use soft wire, for example, vinyl-insulated wire, flexibility class 3. Clean the end wires of 10 ±0.5 mm. If end is longer, it can cause a short circuit, and if short — cause unreliable connection. Use the cable lugs. Undo the screws of the terminals and insert tipped end of the wire in terminal.

Scheme 2. Connection of the circuit breaker and SSD
Tighten terminal with derived average 2.4 Н·m. Low tight may lead to low contact and over-heating terminals and wires and over tight — damage terminals and wires.
Wires protracted in terminals with a screwdriver with a shank width not more than 6 mm. Screw with shank width more than 6 mm may apply mechanical damage to terminals. This could result in loss of warranty. Crossing the wires wiring to which connects should meet the size of electric current, consumed load.

Exploitation

Enabling
When the power supply to terminals 1 and 2, after a preset time delay device include turns on load and control current.
If the current exceeds the set limits, the screen starts flashing, and after the set shutdown time turns off the load.

In 5 sec after the last pushing buttons current control relay return to indication of main voltage.

The main current limit « 1 »
(factory settings 10A)
To view the basic limits of current «I1» push on the «+» or «–» button.
Flashing values can change with buttons «+» or «–».

ZUBR-I25-Current-Control-Relays-04
Minimal » 0 and additional « 2 » limits currents
If the menu depth settings involved minimal «I0» and additional «I2» limits currents, the main boundary current «I1» can be set no lower than «I0» and not above «I2».

ZUBR-I25-Current-Control-Relays-05

Function menu (table 1)
Use the middle button to navigate through the menu.
Use the «+» and «–» buttons to change the parameters. After pressing the button for the first time the parameter will flash, after pressing it for the second time the parameter will change.

An example of using minimal and additional current limits
Let’s assume that in order to protect the electric motor, we want to limit its operation at maximum power, and in case of overload, stop its operation.
For this purpose, we configure the current relay as follows:
The main current limit «ı1» is the current consumed under maximum load;
Switch-off delay «toF» – is operating time at maximum load;
Additional current limit «ı2» is motor overload current;
Set the response time when current exceeds additional limit «t2» is so as to limit the overload;
Minimum current limit «ı0» is maximum current of motor without load.
We recommend to use it in order to limit the operation of the electric motor without load (idling mode); «t0» is time of current action below the minimum limit.

Table 1. Navigating through the Function menu

Menu section| Login through middle button| Screen| Factory setting| Change with

«+» and «–»

| Notes
---|---|---|---|---|---
Viewing the alarm log file Emergency records are stored in non-volatile memory.| click 1 time| | The log is capable of storing the last 25 emergency or overheat alarms. Log entries are displayed in order from the last to the oldest («n 0» is the last entry, «n 1» is the penultimate one, and «n24» is the oldest). To move through the log use the «+» or «–» buttons. When viewing the

emergency, the relay will briefly display the emergency alarm number in 1 second.
To rese t the log, while viewing it, hold down the middle button for 6 seconds until «rSt.» message appears. After releasing the button, the log will be cleared and the screen will display:«—».

Load delay (delay time to on)|

click 2 times

| | | 3–600 sec,

step 3 sec

| It is used for compressor equipment protection. It is recommended to set a delay of turning on load 120–180 sec. It will allow to increase the service life of the compressor.
Delay time to off

operation time at max. load

| click

3 times

| | | 0–240 sec,

step 1 sec

| In 5 seconds after the last button pressing, the current relay will return to «toF» display, then it turns to current indication after 5 s.
Advanced settings| hold for 3 sec
Maximum number of tripping events in a row|

Move from one item to the other one by briefly pressing the middle buttons

| | 3 times| 1–5 times or oFF|
Correction of readings on the screen.

Available at measurable current of more than 1 A

| | 0.0 А| ±20 %| For example:
With a measured current of 10 A, Max. correction range ± 2 A.
Minimum current limit «ı0»| | oFF| 0,1– «ı1» А

or oFF

| For example, it is max operation current of motor without load
Current action time is lower « ı limit.

It will be displayed after activation «ı0»

| | 6 sec| 0–240 sec| If the current is lower than «ı0» , the load will be off after set period of time «t0».
Additional current limit «ı2»| |

oFF

| «ı1» –is max basic current limit or oFF 1-5 times or oFF| For example, this is motor overcurrent.
Response time upon exceeding « ı

limit

Will be displayed after activation «ı2»

| |

10 sec

|

0– «toF» sec

| If the current is higher than «ı2» , the load will be off after set time «t2»

Firmware version

| hold for 12 sec| |

to view

| Attention! The manufacturer reserves the right to modify the firmware to enhance the device technical characteristics.

POSSIBLE PROBLEMS, CAUSES AND WAYS TO  OVERCOME THEM

At turning on neither indicator nor led do not shine.
Possible cause: There is no power supply voltage.
It is necessary to: Ensure supply voltage presence.

The «Err» sign flashes on the display.
Possible cause: operation of the protection system exceeded the set value.

The device was blocked.
Required measure: unblock the device by pressing any button.
Check the cause of the protection operation, check the device settings.
In other cases, contact the Service center.

Delay time of load turning on (table 1)

The delay control is described in Table 1.
The countdown will always be accompanied by a flashing dot at the far right of screen and time remaining until switching

on the load. «t» symbol will appear in far; left site of screen when less than 100 seconds remain.

Reset to factory settings

ZUBR-I25-Current-Control-Relays-07To reset the factory settings, hold the three buttons at the same time for more than 12 s. until «dEF» message appears on the screen. After release, reset to factory settings and reboot will take place.

Protection from inner overheating

In case if the temperature inside the exceed 80 °C, will be emergency lockout of loading.
On the screen 1 time/s (overheat) will be displayed.
At this time, pressing the middle button will display the temperature of the thermal protection.
If protection triggers more than 5 times in a row, the current relay will be blocked until the temperature inside the case drops to 60 ° C and the «+» or «-» buttons are pressed to unlock the relay. «oht» inscription will stop blinking.
At breakout or short circuit of temperature sensor, device continues to operate normally, but every four seconds the message «Ert», indicating the problem with sensor. In this case, control over inner overheating will not be done sensor.
The device will be unlocked in case if the temperature inside will decrease to 60 °C.

Safety instructions

  • Carefully read and become aware of yourself these instructions.
  • Connection of the device must be done by a qualified electrician.
  • Before the installation (dismantling) and connection (disconnection) of the device, turn off voltage supply and also act according to the «Rules of an arrangement of electric installations».
  • Turning on and off or and configure the device should be with dry hands.
  • Do not connect the device to the network disassembled. Avoid hitting of water or moisture to the device.
  • Do not expose the device to extreme temperatures (higher than 40 ºС or below -5°C) and high humidity.
  • Never clean the device with the use of chemicals such as benzene, solvents.
  • Do not store the device and do not use it in areas with the dust.
  • Do not attempt to disassemble and repair the device.
  • Do not exceed the landmarks value adaptor and power.
  • To protect against overvoltage caused by lightning discharges, use a lightning protector.
  • Protect the children from games with the working device, it is dangerous.

Do not fire and do not throw away the device with the household waste.
Device used must be taken in accordance with current legislation.

Transportation of goods carried in the package, ensuring the safety of the product.
The device is transported by any kind of transport (rail, sea, motor, air transportation).
Date of manufacture is on the back side of device.
If you have any questions call the Service center the telephone number listed below.

vi35_200514
Manufacturer and vendor: DS ELECTRONICS, LTD
04136, Ukraine, Kyiv region, Kyiv, 1–3 Pivnichno-Syretska str.
phone: +38 (044) 485-15-01 www.zubr.ua support@zubr.ua

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals