LECTRON Energy Meter 100 Amp Power Consumption Meter User Manual
- June 3, 2024
- LECTRON
Table of Contents
LECTRON Energy Meter 100 Amp Power Consumption Meter
About the Lectron Energy Meter
The Lectron Energy Meter allows you to measure how much electricity is used by
your Lectron
V-BOX Charging Station.
In the Box
Warnings
- During normal operation, hazardous voltages may be present in some of the terminals of this unit. Always use with caution.
- Ensure all parts are de-energized before attempting to connect.
- Never touch or adjust terminals after installation.
- Only install in a dry and safe environment.
Disclaimer
- Installation should only be done by a qualified professional, following all local regulations.
- This energy meter should never be used as the sole means of fault protection.
- Install this energy meter after your main power supply.
- Only use this energy meter with the Lectron
V- BOX charging station.
LCD Display
-
energy measurement value
-
total value
-
import / export energy
-
maximum demand (loading current)
-
PF (power factor); Hz (frequency)
-
measurement of kVArh (reactive power)
measurement of kWh (active power) -
power level
-
time/duration
-
lock device
How to Install
Install the energy meter by connecting it between your electrical panel and your V-BOX.
- Connect the ground wire from the electrical panel to the V-BOX.
- Insert the neutral wire from the electrical panel into the no. 1 port at the top of the energy meter. Flip open the top compartment and tighten the screw using a Phillips screwdriver (not included).
- Insert the neutral wire from the V-BOX into the no. 4 port at the bottom of the energy meter. Flip open the bottom compartment and tighten the screw.
- Insert the live wire from the electrical panel into the no. 2 port at the top of the energy meter. Tighten the screw and close the compartment.
- Insert the live wire from the V-BOX into the no. 3 port at the bottom of the energy meter. Tighten the screw and close the compartment.
Scrolling Between Functions
Click the scroll button to go through the functions, and press the enter
button to select the function.
Buttons:
Note: When the energy meter is powered on, it will initiate a self check. After that, it will display the total kWh (active power).
- total kWh
- import kWh
- export kWh
- resettable kWh
- total kVArh
- import kVArh
- export kVArh
- resettable kVArh
- max power demand
- voltage
- current
- W (watt)
- speed of data exchange 13. VAr (volts-amps reactive) 14. VA (volt-ampere) 15. power factor 16. frequency 17. DI 1 (digital input) 18. DI 2 19. modbus ID 20. baud rate* 21. continuous running time
Order| Display
(example)
| Function / Description
---|---|---
1
| |
total active energy
2
| |
import active energy
3
| |
export active energy
4
| |
total resettable energy
5
| |
total reactive energy
---|---|---
6
| |
import reactive energy
7
| |
export reactive energy
8
| |
total resettable reactive energy
9
| |
total max. power demand
10
| |
voltage
---|---|---
11
| |
current
12
| |
active power
13
| |
reactive power
14
| |
apparent power
15
| |
power factor
---|---|---
16
| |
frequency
17
| |
DI 1 -counting
18
| |
DI 2 -counting
19
| |
modbus address
20
| |
baud rate
---|---|---
21
| |
continuous running time (in total)
Setup Mode
To go into setup mode and adjust the settings of your energy meter, press and hold the “enter” button for 3 seconds.
Order| Display
(example)
| Value / Description
---|---|---
1
|
|
Password
You will first be asked to enter a password.
The Default password is: 1000
2
| |
Address ID Default ID is 001 Range: 001 – 247
---|---|---
2.1
|
|
Press the “enter” button and the red digit will flash.
Press the “scroll” button to change the value.
Then, press and hold the “enter” button to confirm.
3
|
|
Baud rate
Default value: 2400bps Range: 1200, 2400,
4800, 9600,
19200 bps.
3.1
|
|
Press the “enter” button and the red digit will flash.
Press the “scroll” button to change the value.
Then, press and hold the “enter” button to confirm.
---|---|---
4
| | Parity
Default: None Option:None, Even,
Odd
4.1
|
|
Press the “enter” button and the red digit will flash.
Press the “scroll” button to change the parity option. Then, press and hold the “enter” button to confirm.
5
|
|
Demand Integration **Time***
Default: 15 minutes Option: OFF / 5 / 10 /
15 / 30 / 60 min
*energy consumption period
---|---|---
5.1
|
|
Press the “enter” button and the red digit will flash.
Press the “scroll” button to change the DIT option. Then, press and hold the “enter” button to confirm.
6
| |
Automatic Scroll Time Interval
Default: 0 seconds
Option: 0 – 30 sec
6.1
|
|
Press the “enter” button and the red digit will flash.
Press the “scroll” button to change the time interval option. Then, press and hold the “enter” button to confirm.
---|---|---
7
|
| Backlight duration: Default: 60 minutes Option: OFF / 5 / 10 /
20 / 30 / 60 min
Press and hold the “enter” button to adjust backlight duration.
7.1
| | Press the “scroll” butto to change the backlight duration. Then, press and hold the “enter” button to confirm.
8
| |
Clear
Press and hold the “enter” button to clear the interface.
---|---|---
8.1
| |
To clear the max demand of active power, press and hold the “enter” button.
8.2
|
|
To clear the resettable energy, press the “scroll” button to go into the energy reset page. Then, press and hold the “enter” button to confirm.
9
| |
Password
Default: 1000
9.1
|
|
Resetting the Password Press the “enter” button and the red digit will flash.
Press the “scroll” button to change the value.
After selecting a new password, press and hold the “enter” button to confirm.
---|---|---
10
| |
DI- filtering time
Default: 100 mS
10.1
|
| Press the “enter” button and the red digit will flash.
Press the “scroll” button to change the value.
After selecting a new filtering time, press and hold the “enter” button to confirm.
Specifications
- Voltage: 100 – 240 V AC
- Frequency: 50 / 60 Hz (±10%)
- Base current: 10 A
- Maximum current: 100 A
- Display: LCD with white backlight
- Maximum reading: 999999.9 kWh / kVArh
- Power consumption: <2W / 10VA
- Operating temp: -13 ºF to 158 ºF
- Weatherproof rating: IP51 (indoor)
- Dimensions: 14.2 x 39 x 25 in
- Certification: UL94
Get More Support