IDEAL INDUSTRIES L22 Lever Wire Connectors Installation Guide

July 25, 2024
IDEAL INDUSTRIES

Models L22, L23 & L25
Lever Wire Connectors

Installation Instructions:

To be sold only with installation instructions.
Warning
Improper use or installation of this product may cause fire, electrocution, serious personal injury or death. Shut off power to the circuit or remove fuse before using this product. Use only connectors properly sized to the wiring being used. Consult local building codes for installation requirements.

  1. Wiring must comply with all applicable electrical codes.
  2. Turn OFF power before removing or installing connectors.
  3. Cleanly strip wires 7/16” (12mm).
  4. Open lever of desired port.
  5. Insert conductor into open port making sure the conductor is fully inserted into the back of the connector. Use only one conductor per port.
  6. While holding wire in port, close and secure the lever.
  7. Verify conductor is fully inserted to the back of the connector.
  8. Connector is reusable. If reusing connector, cut and re-strip conductors.
  9. To remove a wire, open lever and remove wire.

Wire Ranges
Solid 12 – 24 AWG
Stranded 12 – 24 AWG
CAUTION: TO BE USED ONLY WITH COPPER-TO-COPPER WIRE COMBINATIONS. NOT FOR USE WITH ALUMINUM WIRE. For use in dry locations only. Consult IDEAL for a complete table of UL Listed and CSA Certified Combinations.
For use on insulation types TFN, TFFN, THHN, XHHW, T90 nylon or equivalent.
Temperature Rating: 105°C (221°F) maximum.
Voltage Rating : 600V maximum building wire. 1000V in signs and lighting fixtures.
WARNING: Cancer and Reproductive Harm – www.P65Warnings.ca.gov.
WARRANTY: www.idealind.com

IDEAL INDUSTRIES, INC.
Sycamore, IL 60178, U.S.A.
800-435-0705 Customer Assistance
www.idealind.com
IS 0050-2 Made in Austria