LG C1UVCL10C-2 Germicidal Light Kit Instruction Manual
- June 16, 2024
- LG
Table of Contents
C1UVCL10C-2 Germicidal Light
Kit Instruction Manual
IAQ – UV LIGHTS
508100-02
7/2023
Supersedes 508100-01
GERMICIDAL
LIGHT KIT
C1UVCL10C-2 Germicidal Light Kit
INSTALLATION INSTRUCTIONS FOR GERMICIDAL LIGHT KIT C1UVCL10C-2 (24M88;
106883-02) USED WITH LG/LC/LH/KG/KC/KH 156-300(S) UNITS
WARNING
Improper installation, adjustment, alteration, service or maintenance can
cause property damage, person l injury or loss of life. Installation and
service must be performed by a licensed professional installer (or
equivalent), service agency or the gas supplier.
WARNING
WARNING UV LIGHT SOURCE Ultraviolet (UVC) Radiation Hazard.
This cover is provided with an Interlock to reduce the risk of ultraviolet
radiation exposure. Any exposure will cause eye and skin damage.
Do not look into UV light source.
Access panels must be in place during appliance op eration. Disconnect all
power sources from UV Light, the Air Handling Equipment or Duct System.
Shipping & Packing List
Package 1 of 1 contains the following:
1 – Germicidal light
- 1- UVC light assembly
- 1- UVC lamp
- 1- UVC light shield
1 – Bag assembly containing:
- 1- Warranty sheet
- 1- UVC Danger label
- 58- Wire ties
- 10- Long wire ties
- 6- #10-16 x 5/8” sheet metal screws
- 2- Dual quick connect adapters
- 2- Wire harnesses
- 2- Wiring diagrams
- 1- Door switch
- 5- #10-16 x 5/8” Self drilling screws
- 1- UVC field kit label
- 1-Roll of aluminum foil tape
An additional, separately ordered T49 transformer is required on
LGH/LCH/KG/KC/KH, 460/575V units which do NOT have a T3 transformer (unless
powered directly).
NOTE Not all components provided in kit are used in each application.
Check packaging for shipping damage. Contact the last arrier immediately if
any shipping damage is found.
CAUTION
As with any mechanical equipment, contact with sharp sheet metal edges can
result in personal in jury. Take care while handling this equipment and wear
gloves and protective clothing.
General
Germicidal lights emit ultraviolet (UVC) energy that has been proven effective
in reducing microbial life forms (viruses, bacteria, yeasts, and molds) in the
air. UVC germicidal lamps greatly reduce the growth and proliferation of mold
and other bio-aerosols (bacteria and viruses) on illuminated surfaces.
Germicidal lamps are NOT intended to be used for removal of active mold
growth. Existing mold growth must be appropriately removed PRIOR to
installation of the germicidal lamp.
A door switch is provided which de-energizes the UVC light when the door is
opened.
IMPORTANT – Cotton gloves or a cotton cloth must be used when handling
the new UVC lamp.
Application
The UVC light kit is specifically designed for LG/LC/KG/KC/KH 156-300(S)
units. In addition, the light is equipped with shields to focus the UVC light
on the coil surface where it is needed and reduce the exposure of light on
other components and access panels for improved safety and overall
effectiveness.
Enhanced rapid start ballast provides UVC lamp operation at a full range of
operating conditions.
Lamps operate on 110-230V single‐phase power supply. A step‐down transformer
may be ordered separately for 460V and 575V rooftop units (factory-installed
in
LGM/LCM). Alternately, 110V power supply may be used to directly power the UVC
ballast(s).
WARNING
Potential Mold Spore Release.
Application of UVC lamps to existing mold growth can cause respiratory
irritation and allergic symp toms.
Do not use UVC lamps where active mold growth ex ists. Remove active mold
growth from surfaces prior to operation of UVC lamps.
NOTICE
Potential odor emissions.
Odors may be present when some materials are ex posed to UV light.
These materials may include Technicoated or ECoated Coils. Other materials may
include chemi cals, solvents, polymers and organic materials.
Some occupants may notice irritation or discomfort. If odors are present, the
UV Lights should be turned off and fresh air should be introduced into the
occu pied space immediately. Contact your Independent Lennox Dealer.
CAUTION
Potential Risk of Degradation of Materials.
Potential of degraded wire insulation may cause hu man injury through
electrical shock.
UVC light may damage plastics and rubber materi als. May cause fabric
discoloration.
Avoid UVC light exposure to plastic drain pans, wire insulation, flex duct or
other plastic/rubber compo nents.
Before installation, confirm that any corrosion‐re sistant coating (if
applied to the coil) will not be nega tively impacted by the UVC light
exposure.
Specifications
Lamp Assembly| 49″ L x 3″ W x 4.5″ H (1245mm x 76mm x 114mm)
Sheet metal panel| 31″ L x 5″ W x 1″ H (787mm x 127mm x 125mm)
Electrical power supply| 10/230V, 50/60Hz, 0.7A
NOTE – For 460V & 575V rooftop units, order separate step-down transformers
(except for LGM/LCM models).
Power consumption| 75 Watts
Lamp/Ballast Operating Environment (All models)
Temperature (outside of duct): Relative humidity| 5°F to 140°F (-15°C to 60°C)
<95%.
Specifications subject to change without notice.
Part No.| Replacement Part Description
---|---
54W66| UVC lamp
X7625| Enhanced ballast
- Turn off power to the rooftop unit.
- Open access to the control box, blower compartment and the filter section.
WARNING
Electric shock hazard.
Can cause injury or death.
Disconnect all remote power supplies before opening any unit access panels.
Unit may have multiple power supplies. Do not operate without access panels in
place.
UVC Exposure Protection
The UVC light is equipped with a unique directional shield to focus the UVC
light on the coil surface and drain pan where it is needed and reduce the
exposure of light on other components such as wiring, plastic parts etc. For
shielding of electrical wiring in the rooftop unit, black convoluted tubing is
provided in the unit. However, if there is any concern, aluminum foil tape can
be used to cover up any exposed component.
WARNING
Potential Risk of Fire.
Dust, lint and other debris may cause fire if allowed to come in contact with
illuminated UVC lamp. Remove any dust, lint or other debris from lamps and
surrounding duct system.
Install UVC Light Assembly
The lamp for the UVC light assembly comes separately packaged in a foam sleeve. Install the lamp in the UVC assembly before installing it in the unit.
- Wear cotton gloves or use a cotton cloth when handling the new lamp. To install the lamp, remove two black plastic splash guards from the lamp holders on each end of the UVC assembly. Gently but firmly push in the splash guards on each end of the lamp. See figure 1.
- Align and insert the splash guards (now connected to the lamp) back onto the UVC assembly lamp holders. Click into place.
- Carefully place the UVC assembly on the blower deck. Line up the mounting holes on the UVC assembly with the mounting holes on the blower deck. See figure 2. Use the self tapping screws provided to secure the UVC assembly in place.
Wiring Connections
- Route the UVC cable wires as shown in figure 3.
- Wire tie the cable at multiple locations along the existing wire harness.
- Make wiring connections in the control section as shown in:
Figure 4 – 230V LGH/LCH/KG/KC/KH with T1
Figure 5 – 460/575V LGH/KG with T49
Figure 6 – 575V LGH/KG with T13
Figure 7 – 230V LGM/LCM
Figure 8 – 460/575V LGM/LCM
Install Convoluted Tubing
Install convoluted tubing (included in the kit) to shield electrical wiring
and components. The tubing is split type making it easy to slip on the wiring.
Black wire ties are provided to tie the tubing in place. See figure 9 and 10.
In addition, aluminum tape (not provided) can be used if needed to further
shield any other surface of concern.
Note – The cable should not extend past the UVC assembly to be in direct
line of sight of UVC lamp. Install UV Shield
To block the UVC light from reaching the filter access door, install the
sheet-metal panel. See figure 11.
Install Door Switch
Install the door switch bracket onto the UV shield. Clip the switch onto the
bracket and wire as shown in figure 3. Finish Installation
Close all access doors before powering UVC lamp. Apply UVC Danger label and
UVC Field Kit label to blower access door so that it is clearly visible. See
figure 12.
Configure M4 For UVC Light
- Use the following mobile service app menu to configure the Unit Controller. SETUP > INSTALL > RTU INFORMATION > CONFIGURATION ID2
- Set position 6 to to the appropriate setting to enable the UVC:
2=UV Lamp Only Installed
3=Both UV Lamp and Ionizer Installed
M3 Unit Controller Configuration
Configure the Unit Controller to enable the UVC Lamp using the following menu:
SETUP . INSTALL
Navigate through the various setup questions until Configuration ID 2 appears.
Set position six to the following to enable the UVC feature:
1=UV Lamp only installed
3=BOTH UV Lamp and Ionizer installed.
Operation
For optimal performance, continuous operation of the UVC germicidal lamp is recommended.
Maintenance
For all maintenance, contact a licensed HVAC technician. If UVC lamp does not come on:
-
Check Power Wiring: Disconnect 1/4” QC (quick connects) of the UVC cable near the UVC assembly.
With Power ON, use multimeter to test 110-230V at the 1/4”QC quick connects from the control panel. -
Check Lamp: Carefully remove the UVC assembly out of the rooftop unit. Use multimeter to test for continuity across each pair of pins at each end of the lamp.
-
Check Lamp Installation: Make sure that lamp’s pins snap properly into the lamp holder.
Lamp Disposal
Hg-LAMP Contains Mercury.—Manage in accordance with local, state and federal
disposal laws. Refer to www.lamprecycle.org.
Proper Clean-up Technique in Case of Lamp Breakage
Wear protective gloves, eye wear and mask.
Sweep the broken glass and debris into a plastic bag, seal the bag, and
dispose of properly. Contact your local waste management office for proper
disposal.
Do not use a vacuum cleaner. Do not incinerate.