Nidec R220 AVR Automatic Voltage Regulator Installation Guide
- June 3, 2024
- Nidec
Table of Contents
Nidec R220 AVR Automatic Voltage Regulator
This manual concerns the alternator AVR which you have just purchased.
We wish to draw your attention to the contents of this maintenance manual.
SAFETY MEASURES
Before using your machine for the first time,it is important to read the whole
of this installation and maintenance manual.
All necessary operations and interventions on this machine must be performed
by a qualified technician.
Our technical support service will be pleased to provide any additional
information you may require.
The various operations described in this manual are accompanied by
recommendations or symbols to alert the user to potential risks of accidents.
It is vital that you understand and take notice of the following warning
symbols.
WARNING
Warning symbol for an operation capable of damaging or destroying the machine
or surrounding equipment.
Warning symbol for general danger to personnel.
Warning symbol for electrical danger to personnel.
All servicing or repair operations performed on the AVR should be undertaken by personnel trained in the commissioning, servicing and maintenance of electrical and mechanical components.
When the generator is driven at a frequency below 28 Hz for more than 30 seconds with an analogue AVR, its AC power supply must be disconnected.
WARNING
This AVR can be incorporated in a marked machine.
This manual is to be given to the end user.
© 2022 Moteurs Leroy-Somer SAS
Share Capital: 38,679,664 €, RCS Angoulême 338 567 258.
We reserve the right to modify the characteristics of this product at any time
in order to incorporate the latest technological developments. The information
contained in this document may therefore be changed without notice.
This document may not be reproduced in any form without prior authorization.
All brands and models have been registered and patents applied for.
WARNING
The R220 AVR cannot be used in dedicated single-phase 60 Hz.
The R220 is an IP00 product. It must be installed inside a unit so that this
unit’s cover can provide IP20 minimum total protection (it must only be
installed on our alternators in the appropriate location so that when viewed
externally, it has a higher degree of protection than IP20).
SUPPLY
SHUNT excitation system
The alternator with Shunt excitation is selfexcited with an R220 voltage
regulator.
The regulator monitors the exciter excitation current as a function of the
alternator output voltage. Very simple in design, the alternator with shunt
excitation has no sustaining short-circuit capacity.
R220 AVR
Characteristics
-
Storage: -55°C ; +85°C
-
Operation: -40°C ; +65°C
-
Voltage regulation: ± 0.5%
-
Voltage supply/sensing range 85 to 139 V (50/60 Hz)
-
Rapid response time (500 ms) for a transient voltage variation amplitude of ± 20%
-
Voltage setting P1
-
Stability setting P2
-
Power supply protected by 8 A fuse, slowblow action (tolerates 10 A for 10 s)
The fuse is impregnated in the resin, therefore it can not be replaced. -
Frequency: 50 Hz with ST3 jumper – 60 Hz without ST3 jumper.
-
The size of the screwdriver tip used to adjust the potentiometer is 2.5 mm.
AVR options
Potentiometer for remote voltage adjustment, 1000 Ω / 0.5 W min: adjustment
range ± 5%.
- Remove the ST4 jumper.
For wiring up the external potentiometer; the “earth” wires must be isolated as well as the potentiometer terminals (wires at the same voltage as the power).
INSTALLATION -COMMISSIONING
Electrical checks on the AVR
- Check that all connections have been made properly as shown in the attached wiring diagram.
- Check that the ST3 frequency selection jumper is on the correct frequency setting.
- Check whether the ST4 jumper or the remote adjustment potentiometer have been connected.
Settings
The machine is tested and set at the factory. When first used with no load,
make sure that the drive speed is correct and stable (see the nameplate).
After operational testing, replace all access panels or covers.
The only possible adjustments to the machine should be made on the AVR.
R220 setting (SHUNT system)
Initial potentiometer settings
-
P1 potentiometer (AVR voltage adjustment): fully anti‑clockwise.
-
Remote voltage adjustment potentiometer: centre position.
Run the alternator at its rated speed. If the voltage does not increase, the magnetic circuit should be remagnetized (see section 3.3). -
Turn the AVR voltage adjustment potentiometer P1 slowly until the output voltage-rated value is obtained.
-
Adjust the stability setting using P2.
Clockwise: increase the rapidity.
Anti-clockwise: decrease the rapidity.
Special type of use
WARNING
Excitation circuit E+, E- must not be left open when the machine is running : AVR damage will occur.
R220 field weakening (SHUNT)
The exciter is switched off by disconnecting the AVR power supply.
Contact rating : 16A – 250V AC.
The power supply contactor must only be closed when the alternator is not
being driven.
R220 field forcing
Battery must be isolated from the earth.
Exciter field may be at line potential.
Electrical faults
Fault | Action | Effect | Check/Cause |
---|
No voltage at no load on start-up
| ****
Connect a new battery of 4 to 12 volts to terminals E- and E+, respecting the polarity, for 2 to 3 seconds
| The alternator builds up and its voltage is still correct when the battery is removed| ****
– Lack of residual magnetism
The alternator builds up but its voltage does not reach the rated value when the battery is removed| – Check the connection of the voltage
reference to the AVR
– Faulty diodes
– Armature short-circuit
The alternator builds up but its voltage disappears when the battery is removed| – Faulty AVR
– Field windings disconnected
– Main field winding open circuit
– Check the resistance
Voltage too low
| ****
Check the drive speed
| ****
Correct speed
| Check the AVR connections (AVR may be faulty)
– Field windings short-circuited
– Rotating diodes burnt out
– Main field winding short-circuited
– Check the resistance
Speed too low
| Increase the drive speed
(Do not touch the AVR voltage pot. (P2) before running at the correct speed)
Voltage too high| Adjust AVR voltage
potentiometer
| Adjustment ineffective| – Faulty AVR
– 1 faulty diode
Voltage oscillations
| ****
Adjust AVR stability
potentiometer
| | – Check the speed : possibility of cyclic irregularity
– Loose connections
– Faulty AVR
– Speed too low when on load (or U/F bend set too high)
Voltage correct at no load and too low when on load (*)
| ****
Run at no load and check the voltage between E+ and E- on the AVR
| | – Check the speed (or U/F bend set too high)
– Faulty rotating diodes
– Short-circuit in the main field
– Check the resistance
– Faulty exciter armature
*() Caution :** For single-phase operation, check that the sensing wires coming from the AVR are correctly connected to
the operating terminals.
Voltage disappears during operation| Check the AVR, the surge suppressor, the rotating diodes and replace any defective components| ****
The voltage does not return to the rated value
| – Exciter winding open circuit
– Faulty exciter armature
– Faulty AVR
– Main field open circuit or short-circuited
Warning: after operational testing, replace all access panels or covers.
SPARE PARTS
Designation
Technical support service
Our technical support service will be pleased to provide any additional
information you may require.
For all spare parts orders or technical support requests, send your request to
service.epg@leroy-somer.com or your
nearest contact, whom you will find at
www.lrsm.co/support indicating the type and the
code number of the AVR.
To ensure that our products operate correctly and safely, we recommend the use
of original manufacturer spare parts.
In the event of failure to comply with this advice, the manufacturer cannot be
held responsible for any damage.
Disposal and recycling instructions
We are committed limiting the environmental impact of our activity. We
continuously monitor our production processes, material sourcing and products
design to improve recyclability and minimise our environmental footprint.
These instructions are for information purposes only. It is the user’s responsibility to comply with local legislation regarding product disposal and recycling.
Waste & hazardous materials
The following components and materials require special treatment and must be
separated from the alternator before the recycling process:
- electronic materials found in the terminal box, including the automatic voltage regulator (198), current transformers (176), interference suppression module and other semi-conductors.
- diode bridge (343) and surge suppressor (347), found on the alternator rotor.
- major plastic components, such as the terminal box structure on some products.
These components are usually marked with information concerning the type of plastic.
All materials listed above need special treatment to separate waste from reclaimable materials and should be entrusted to specialist recycling companies.
Service & Support
servicesOur worldwide service network of over 80 facilities is at your service.This local presence is our guarantee for fast and efficient repair, support and maintenance services.Trust your alternator maintenance and support to electric power generation experts. Our field personnel are 100% qualified and fully trained to operate in all environments and on all machine types.
We have a deep understanding of alternator operation, providing the best value service to optimise your cost of ownership.Where we can help:
Contact us:Americas: +1 (507) 625 4011
Europe & rest of the world: +33 238 609 908
Asia Pacific: +65 6250 8488
China: +86 591 88373036
India: +91 806 726 4867
Scan the code or go to:
service.epg@leroy-somer.com
www.lrsm.co/support
Linkedin.com/company/leroy-somer
Twitter.com/Leroy_Somer_en
Facebook.com/LeroySomer.Nidec.en
YouTube.com/LeroySomerOfficiel
References
- Somer Dental Labs | Quality, Experience, Consistency
- Trusted Partner in Helping to Solve the Biggest Challenges of Modern Life | Emerson US
- Leroy-Somer Alternators - Generators
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>