FieldLogger is an analog and digital variables data logger module. It has
8 universal analog inputs and 8 digital I/Os. It can act as a Modbus RTU
network master and read registers from other slaves in order to log them into
memory or make them available on its other interfaces. Capable of performing
mathematical operations on the input channels, it has fast reading and logging
rates, a large storage memory, accepts SD card and thumb drive and has a full
set of connectivity options.
The full version of FieldLogger operating and installation manual, available
on the product page, presents to the user all the information necessary for
proper use of all features.
UNPACKAGE
When unpacking, besides this Quick Guide, you will also find:
- One FieldLogger module;
- One USB cable.
INITIAL CONFIGURATION AND SOFTWARE INSTALLATION
FieldLogger configuration is executed through the Configurator application.
FieldLogger Configurator downloading and running the
FieldLoggerConfigsetup.exe file
available at our website:
www.novusautomation.com/en/fieldlogger.
Before connecting the FieldLogger to the computer USB port, please install the
Configurator application and the USB drivers. In order to make the first
configuration, please follow these steps:
- Unpack the FieldLogger and USB cable.
- Install the Configurator application in the computer (USB communication drivers will be installed as well).
- Power on the FieldLogger and connect it to the computer through the USB cable. In case the drivers have not yet been installed and a window pops up indicating that a new hardware has been found, check in the manual the right proceeding to install it.
- Run the Configurator application and read the equipment configuration. If it succeeds, you are able to configure and use your FieldLogger. On any error, check the manual and follow the hints and instructions given by the Configurator application.
FieldLogger is set with the following factory default configuration:
- RS485 Interface enabled as SLAVE: 19200 bps, no parity, 1 stop bit and Modbus address 1;
- Ethernet Interface disabled;
- Data logging disabled;
- All analog channels disabled;
- All digital channels disabled (all configured as inputs);
- All virtual channels disabled;
- No alarms configured;
- Download via thumb drive disabled;
- HMI access set only for reading.
SPECIFICATIONS
Analog Inputs| 8 analog inputs:
· Thermocouple J, K, T, E, N, R, S and B (IEC-584).
· Pt100, Pt1000 (IEC-751), 0-20 mA, 4-20 mA, 0- 20 mV, 0-50 mV, 0-60 mV, –
20-20 mV, 0-5 V and 0-10V.
---|---
Analog Accuracy| · Thermocouple J, K, T, E and N: 0.2 % of range ± 1 °C.
· Thermocouple R, S and B: 0.2 % of range ± 3 C.
· Pt100, P11000, 0-20 mA, 4-20 mA, 0-20 mV, 0- 50 mV, 0-60 mV, – 20-20 mV, 0-5
V and 0-10 V: 0.15 % of maximum range.
Digital Inputs /Outputs| 8 digital channels that can be individually
configured as inputs or outputs.
Relay Outputs| 2 Relays SPST-NO/NC, 3 A / 250 Vac
RS485 Interface| Can be used as a Modbus RTU slave or master (can read up to
64 slaves).
Ethernet Interface| 10/100 Mbps.
Supported Protocols and Services| TCP/IP, DHCP, HTTP, SMTP, SNMP, Modbus
RTU, Modbus TCP, FTP server and client.
Internal Memory| 2 MB.
SD Card| Up to 16 GB.
Operating Environment| 0 to 50 °C. Relative Humidity (Maximum): 80 % up to 30
°C. For temperatures above 30 °C, decrease 3 % per °C. Installation category
II. Pollution degree 2.
Altitude < 2000 m.
Enclosure| ABS + PC
Dimensions| 165 x 117 x 70 mm; Weight: 400 g. (no HMI)
Power Supply| · 100 to 240 Vac/dc (50 / 60 Hz)
· 24 Vddac (50 / 60 Hz)
Protection| IP20
Configuration Software Operation Environment| Software for Windows® XP, Vista
and 7. Menus in Portuguese, Spanish or English.
Certifications| CE, UL and UKCA
Table 01
(Complete manual in www.novusautomation.com/en/fieldlogger )
QG 5000965 V1.7x
Documents / Resources
|
NOVUS 5000965 Industrial Multichannel Data Logger
FieldLogger
[pdf] User Guide
5000965 Industrial Multichannel Data Logger FieldLogger, 5000965, Industrial
Multichannel Data Logger FieldLogger
---|---
References
- Data Logger Industrial Multicanais FieldLogger - data logger wi-fi, data logger sem fio, data logger wireless, registrador wi-fi, registrador sem fio, registrador wireless, wifi, wi fi, - Controladores, Transmissores, Data Logger, Termostatos, Indicadores
- Industrial Multichannel Data Logger FieldLogger - Data Loggers - Controllers, Thermostats, Data Loggers, Solid State Relays, Sensors, Transmitters, SCADA, Data Acquisition and Temperature Controllers
- Registrador de datos industrial multicanales FieldLogger - Data Loggers - Controladores, Transmisores, Data Logger, Termostatos, Indicadores y Sensores
- Industrial Multichannel Data Logger FieldLogger - data logger wireless, data logger wi-fi, wi-fi data recorder, wireless data recorder, wifi, wi fi, - Controllers, Thermostats, Data Loggers, Solid State Relays, Sensors, Transmitters, SCADA, Data Acquisitio
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>