PeakTech 2675 Analog Insulation Tester User Manual

June 3, 2024
PeakTech

Unser Wert ist messsbar
Analogue Insulation Tester
Operation Manual
****

Safety Precautions

This product complies with the requirements of the following directives of the European Union for CE conformity: 2014/30/EU (electromagnetic compatibility), 2014/35/EU (low voltage), 2011/65/EU (RoHS).
Overvoltage category III 600V; pollution degree 2.
CAT II: For local level, appliances, main wall outlets, portable equipment
CAT III: Supplied from a cable under earth; fixed installed switches, automatic cut-off or main plugs
CAT IV: Units and installations, which are supplied overhead lines, which are stand in a risk of persuade of a lightning, i.e. main-switches on current input, overvoltage-diverter, current use counter.
To ensure safe operation of the equipment and eliminate the danger of serious injury due to short-circuits (arcing), the following safety precautions must be observed.
Damages resulting from failure to observe these safety precautions are exempt from any legal claims whatever.

  • This Instrument must only be used and operated by a competent trained person and in strict accordance with the instructions. We will not accept liability for any damage or injury caused by misuse or non compliance with instructions an safety procedures
  • This instrument must not be used on live circuits. Ensure all circuits are de-energised before testing.
  • Never open your analogue insulation tester except for battery replacement (see battery replacement section)
  • Check test leads and probes for faulty insulation or bare wires before connection to the equipment.
  • Always inspect you analogue insulations tester and test leads before use for any sign of abnormality or damage. If any abnormal conditions exist (broken test leads, cracked case, display faulty etc. …) do not attempt to take any measurement or use the tester. Return your analogue insulation tester to your nearest distributor for service.
  • Never replace the protective fuse with any other than the specified or approved equivalent.
  • Your analogue insulation tester has been designed with your safety in mind. However, no design can completely protect against incorrect use. Electrical circuits can be dangerous and / or lethal when a lack of caution or poor safety practice is used. Use caution in the presence of voltage above 24V as these pose a chock hazard.
  • Pay attention to cautions and warnings which will inform you of potentially dangerous procedures.
  • Your analogue isolation tester has a live circuit warning beeper. If it is connected to an AC live circuit, a beep of twice the frequency of the voltage present will be heard.
  • DOT NOT proceed to test and immediately disconnect the instrument from the circuit. In addition, the warning light will lit if the voltage is above 100V DC or 70VAC. When AC voltage is present, before testing, it’s value is displayed on the AC scale.
  • Do not exceed the maximum permissible input ratings (danger of serious injury and/or destruction of the equipment).
  • Replace a defective fuse only with a fuse of the original rating. Never short-circuit fuse or fuse holding.
  • Disconnect test leads or probe from the measuring circuit before switching modes or functions.
  • To avoid electric shock, disconnect power to the unit under test and discharge all capacitors before taking any resistance measurements.
  • To avoid electric shock, do not operate this product in wet or damp conditions. Conduct measuring works only in dry clothing and rubber shoes, i. e. on isolating mats.
  • Never touch the tips of the test leads or probe.
  • Comply with the warning labels and other info on the equipment.
  • Always start with the highest measuring range when measuring unknown values.
  • Do not subject the equipment to direct sunlight or extreme temperatures, humidity or dampness.
  • Do not subject the equipment to shocks or strong vibrations.
  • Do not operate the equipment near strong magnetic fields(motors, transformers etc.).
  • Keep hot soldering irons or guns away from the equipment.
  • Allow the equipment to stabilize at room temperature before taking up measurement (important for exact measurements).
  • Do not turn the rotary function switch during voltagemeasurement, otherwise the meter could be damaged.
  • Use caution when working with voltages above 35V DC or 25V AC. These Voltages pose shock hazard.
  • Replace the battery as soon as the battery indicator “BAT” appears. With a low battery, the meter might produce false reading that can lead to electric shock and personal injury.
  • Fetch out the battery when the meter will not be used for long period.
  • Periodically wipe the cabinet with a damp cloth and mid detergent. Do not use abrasives or solvents.
  • The meter is suitable for indoor use only
  • Do not operate the meter before the cabinet has been closed and screwed safely as terminal can carry voltage.
  • Do not store the meter in a place of explosive, inflammablesubstances.
  • Do not modify the equipment in any way
  • Opening the equipment and service- and repair work must only be performed by qualified service personnel
  • Measuring instruments don’t belong to children hands.

Cleaning the cabinet
Clean only with a damp, soft cloth and a commercially available mild household cleanser. Ensure, that no water gets inside the equipment to prevent possible shorts and damage to the equipment.

Features

  • High quality taut band movement
  • Three insulation test voltages (100 MΩ, 250 V; 200 MΩ, 500 V; 400 MΩ, 1000 V)
  • Two continuity test on „Low Ohms“ 3/500Ω
  • Small and Lightweight
  • AC voltmeter with linear scale up to 600VAC
  • 205mA continuity short circuit current
  • 1mA test current on insulation test at nominal voltage
  • Automatic discharge of capacitance and inductive circuit off charge stored in the circuit under test.
  • Live Warning and display of external voltage presence
  • Fuse and overload protected
  • On line battery monitoring shows if batter is ok
  • Very low battery consumption
  • On-Load battery check (+/- 205mA load for worst case)
  • Operates on 8 dray batteries AA, R6P type
  • Mirrored scale for easy and accurate reading
  • Push and turn locking switch for long and hand free testing
  • Supplied with high quality test leads

Specifications

2.1. General Specifications

Measurement| Insulation:
100 MΩ, 250 V
200 MΩ, 500 V
400 MΩ, 1000 V
ACV: 0 … 600V
OHMS: 3/500Ω- range
---|---
Operating Temperature| 0 to 40°C (0 to 104°F)
Operating Humidity| less than 80% R.H.
Power Supply| DC 12 V, 1,5 V AA (UM-3) battery x 8 pcs.
Dimensions| 85 x 175 x 75 mm with housing front cover
Weight| 650 g
Standard accessories| carrying case, test leads, 8 x 1,5 V-batteries and manual

2.2. Electrical Data (23°C +/- 5°C)

Test voltage 250V 500V 1000V
+ 10% / -0%
Mirror scale 100MΩ 200MΩ 400MΩ
Mid scale 1 MΩ 2 MΩ 4 MΩ
Scale Multiplier X 0,5 X 1 X 2
Accuracy +/-5% FS
Output short-circuit current +/-1,3 mA
Regulated output voltage (up to 1mA current) 263,5V 525V 1052V

Continuity

LowΩ 3Ω / 500Ω
Accuracy +/-1,5% of scale length
Output short-circuit current 205 mA

AC Voltage

Range 600V
Accuracy +/-3% of scale length

Front Panel Description

  1. Test Button Switch
  2. Function Selector
  3. Battery OK indicator
  4. Mirror Scale
  5. Live Circuit Warning Light
  6. Test Leads and Fuse Zeroing Knob

Precautions & Preparation for Measurements

  1. Remove the power from the circuit when making the measurement. If any voltage is present in the testing circuit, then it could damage the units.
  2. Ensure, that the batteries (8 x 1,5 V AA battery) are connected correctly to the right position into the battery compartment.
  3. Rotate the “Function-/Selector” to the right position before making measurement.

Measuring Procedure

5.1. Functions
5.1.1. Battery Check

  • Turn the function selector to Battery Check.
  • This function has a load which draw about 205mA when test is performed, and therefore it is doing a worst case battery test.
  • Then press the test button, the pointer should be in the BAT.OK area.
  • During the test, the BAT.OK lead (on line battery check) must lit if the pointer is in the BAT.OK area.

5.1.2. DC Warning
The DC warning buzzer will beep continuously when DC voltage is higher than 30 VDC on the test probes and the test button is not pressed. The neon light “circuit live” will lit when the voltage on the test probes is higher than 90 VDC and the test button is not pressed.
5.1.3. AC Warning
The AC warning buzzer will beep continuously when AC voltage is higher than 20VAC on the test probes and the test button is not pressed. The neon light “circuit live” will lit when the voltage on the test probes is higher than 65VDC and the test button is not pressed.
5.1.4. AC Measurement
The AC measurement is automatic on this instrument. As soon as AC voltage is present on the test leads, the instrument will display the AC voltage from 20 to 600 VAC on the linear scale.
5.1.5. Low Ohms Measurement 0-3Ω/500Ω
Always check for voltage before testing and measuring on a circuit. This instrument is intended for measuring low Ω and Insulation resistance on un- energized circuits only.
The first procedure to follow, is to zero the test leads and the fuse resistance. The instrument is equipped with a zero Ω Knob. First, short circuit the test leads by connecting them together, then press the test button and adjust the zero Ω knob until the pointer is precisely on the “=” of the 3Ω/500Ω scale.
Use the mirror scale to be precise with the pointer. connect the test leads to the circuit to be measured. For short test, press button and keep pressed. For long test or hand free measurements, press and turn the test button.

5.1.6. Insulation Resistance Measurement at 250VDC
Always check for voltage before testing and measuring on a circuit.
This instrument is intended for measuring low Ω and Insulation resistance on un-energized circuits only.
Check the test leads and fuse resistance by zeroing the test leads and fuse. Connect the test leads to the circuit to be measured and wait for a few seconds. The instrument will automatically discharge any remaining energy which could be present on the circuit and will check for voltage at the same time.
Once you are sure that the circuit to be tested is not energized, then press the button for a short test duration or press and turn the button for a long test. Once your end the test , allow a few seconds for the Instrument to automatically discharge the circuit

Battery & Fuse Replacement

6.1. Battery Replacement
Your Analogue insulation tester’s battery is situated under the tester. The BAT.OK will not lit when battery need to be replaced. Disconnect the test leads from the Instrument, remove the battery cover and the batteries. Replace with eight 1,5 VR6 or L6 batteries, taking care to observe the correct polarity.
6.2. Fuse replacement
The fuse is located next to the batteries. To replace fuse, proceed as per battery replacement to pen the battery cover, then remove and replace the fuse located under the battery holder. Only replace with same specification fuse (0,5A/600V)
6.3. Statutory Notification about the Battery Regulations
The delivery of many devices includes batteries, which for example serve to operate the remote control. There also could be batteries or accumulators built into the device itself. In connection with the sale of these batteries or accumulators, we are obliged under the Battery Regulations to notify our customers of the following:
Please dispose of old batteries at a council collection point or return them to a local shop at no cost. The disposal in domestic refuse is strictly forbidden according to the Battery Regulations. You can return used batteries obtained from us at no charge at the address on the last side in this manual or by posting with sufficient stamps.
Batteries, which contain harmful substances, are marked with the symbol of a crossed-out waste bin, similar to the illustration shown left. Under the waste bin symbol is the chemical symbol for the harmful substance, e.g. „Cd“ for cadmium, „Pb“ stands for lead and „Hg“ for mercury.You can obtain further information about the
Battery Regulations from the Bundesministerium für Umwelt, Naturschutz und Reaktorsicherheit (Federal Ministry of Environment, Nature Conservation and Reactor Safety).
All rights, also for translation, reprinting and copy of this manual or parts are reserved. Reproductions of all kinds (photocopy, microfilm or other) only by written permission of the publisher.
This manual is according the latest technical knowing. Technical changings which are in the interest of progress, reserved.
We herewith confirm that the units are calibrated by the factory according to the specifications as per the technical specifications.
We recommend to calibrate the unit again, after 1 year.
© PeakTech®
07/2021 Ho/Th./Mi/Ehr.

PeakTech Prüf- und Messtechnik GmbH – Gerstenstieg 4 –
DE-22926 Ahrensburg / Germany
+49-(0) 4102-97398 80 +49-(0) 4102-97398 99
info@peaktech.de www.peaktech.de

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals