EMERSON XCM25D Controller Replacement User Guide

June 3, 2024
Emerson

EMERSON XCM25D Controller Replacement

Controller replacement

  • This manual describes the required working steps to replace a XCM-25D in case of controller damage on a ZX/CF unit.

  • The spare part kit contains 3 “Hot Keys”, one for each unit family (ZXM/CFM, ZXL/CFL & ZXD/CFD).
    Choose correct “Hot Key” depending on unit family, upload the parameters from the “Hot Key” to the controller, and adjust the values for electrical protection according to following instructions.

  • Interrupt the power supply of the unit. Disconnect the protection connectors and connect them on the new controller at the same terminals as before. Disconnect all the wires at the upper and lower parts of the controller.

EMERSON XCM25D Controller Replacement-FIG2

  • Open the cover of the cable guidance. Cut the cable ties, disconnect the grey and brown cables from the compressor contactor.
    Pull out the cables from the current sensors of the controller.

  • Unlock the 4 controller locks. Remove the old controller and mount the new controller in its place.

Parameter uploading

Choose correct “Hot Key” depending on unit family, then upload the parameters from the “Hot Key” to the controller

  • Turn the controller off.

  • Insert a pre-programmed “Hot Key” into the 5-pin receptacle and turn the controller on.

  • The parameter list of the “Hot Key” will be automatically downloaded into the controller memory. The “doL” message will blink followed a by a flashing “End” label.

  • After 10 seconds, the controller will restart working with the new parameters.
    Remove the “Hot Key”.

  • NOTE: The message “Err” is displayed in case of a failed programming operation. In this case turn the unit off, then on again if you want to restart the download, or remove the “Hot Key” to abort the operation.

Parameter setting

  • In order to adjust a dedicated unit with the proper settings, parameters have to be modified.
  • For units with the TFD motor version, modify parameters H07 and H09.
    For the required values refer to Tables 1, 2 and 3.

Table 1: ZXME & CFME > TFD (400V/3Ph/50Hz)

ZX M E-TFD & CF M E-TFD

Parameter/Paramètre| 020| 025| 030| 040| 050| 060| 075
H07| 7.0| 9.1| 8.5| 10.5| 13.5| 16.1| 17
H09| 5.4| 5.4| 8.0| 10.4| 13.4| 14.5| 15.4

Table 2: ZXLE & CFLE > TFD (400V/3Ph/50Hz)

ZX L E-TFD & CF L E-TFD

Parameter/Paramètre| 020| 030| 040| 050| 060| 075
H07| 7.9| 7.8| 12.1| 14.0| 16.0| 19.3
H09| 6.3| 7.4| 10.2| 13.1| 15.1| 16.1

Table 3: ZXDE & CFDE > TFD (400V/3Ph/50Hz)

ZX D E*-TFD & CF D E**-TFD

Parameter/Paramètre| 040| 050| 060| 075
H07| 10.1| 13.9| 12.9| 16.3
H09| 8.7| 12.5| 12.6| 15.4
For units with the PFJ (230V/1Ph/50Hz) motor version, modify parameters H07, H09, H13, H14 and H25.

For the required values refer to Tables 4 and 5.

| Für Verflüssigungssätze mit PFJ Motor (230V/1~/50Hz) die Parameter H07, H09, H13, H14 und H25 ändern.

Die Werte sind den Tabellen 4 & 5 zu entnehmen.

| Version moteur PFJ (230V/1Ph/50Hz) : régler les paramètres H07, H09, H13, H14 et H25 selon les valeurs données aux Tableaux 4 et 5.
---|---|---

Table 4: ZXME & CFME > PFJ (230V/1Ph/50Hz)

ZX M E-PFJ & CF M E-PFJ

Parameter/Paramètre| 020| 025| 030| 040
H07| 18.5| 20.5| 23.0| 28.0
H09| 14.1| 13.7| 18.1| 25.9
H13| 190| 190| 190| 190
H14| 260| 260| 260| 260
H25| NO| NO| NO| NO

Table 5: ZXLE & CFLE > PFJ (230V/1Ph/50Hz)

ZX L E-PFJ & CF L E-PFJ

Parameter/Paramètre| 020| 025| 030
H07| 18.5| 20.5| 23.0
H09| 15.0| 17.2| 19.6
H13| 190| 190| 190
H14| 260| 260| 260
H25| NO| NO| NO

How to program the parameters (Pr1 and Pr2)

  • Access pre-program level
    Press simultaneously for about 3 seconds to access the pre-programming level. The message rtC (real time clock) appears.

  • Access program level

Press the Up or Down key until the message PAR appears.

  • Access Pr1

Press the SET button to enter the program level. First parameter C01 appears.

  • Access Pr2

Go to t18 label using the arrows. Press the SET button. The blinking PAS label will be displayed; wait for a few seconds.
The display will show “0 – -” with blinking 0. Insert the password [321] using the and keys and confirm every digit with the key.

  • Select item

Select the parameter or submenu using the arrows.

  • Show value

Press the SET button.

  • Modify
    Press the SET button: the value will blink for 3 seconds, then the display will show the next parameter.

  • EXIT

Press simultaneously to exit the programming mode, or wait for 30 seconds (MTO) without pressing any key.

UK & IRELAND
Unit 17, Theale Lakes Business Park Reading, Berkshire RG7 4GB
Tel. +44 1189 83 80 00
Fax +44 1189 83 80 01
uk.sale s@emerson.com

For more details, see www.climate.emerson.com
Connect with us: facebook.com/EmersonClimateEurope

Emerson Commercial & Residential Solutions
Emerson Climate Technologies GmbH – Pascalstrasse 65 – 52076 Aachen, Germany
Tel. +49 (0) 2408 929 0 – Fax: +49 (0) 2408 929 570 – Internet: www.climate.emerson.com
The Emerson logo is a trademark and service mark of Emerson Electric Co. Emerson Climate Technologies Inc. is a subsidiary of Emerson Electric Co.
Copeland is a registered trademark and Copeland Scroll is a trademark of Emerson Climate Technologies Inc.. All other trademarks are property of their respective owners. Emerson Climate Technologies GmbH shall not be liable for errors in the stated capacities, dimensions, etc., as well as typographic errors. Products, specifications, designs and technical data contained in this document are subject to modification by us without prior notice. Illustrations are not binding.
© 2017 Emerson Climate Technologies, Inc.