TECE SH-CD6-230 Regelverteiler and Control Distributor User Guide
- June 21, 2024
- TECE
Table of Contents
SH-CD6-230 Regelverteiler and Control Distributor
User Guide
General information
1.1 Safety warnings and operating instructions
This product should be installed preferably by a qualified professional.
Subject to observation of the above terms, the manufacturer shall assume the
liability for the equipment as provided by legal stipulations. All
instructions in this Installation & Operation manual should be observed when
working with the controller.
Failures due to improper installation, improper use or poor maintenance are
voiding manufacturer liability. Any attempt to repair voids the responsibility
and the obligation to guarantee and replacement from the manufacturer.
2012/19/EU (WEEE directive): Products marked with this symbol cannot be
disposed of as unsorted municipal waste in the European Union. For proper
recycling, return this product to your local supplier upon the purchase of
equivalent new equipment, or dispose of it at designated collection points.
For more information see: www.recyclethis.info
1.2 Application
The controller has been designed for use in residential rooms, office spaces
and industrial facilities. Verify that the installation complies with existing
regulations before operation to ensure proper use of the installation.
Presentation
The Connecting box SH-CD is especially designed to control your Under Floor Heating and Cooling system. It allows easy and quick connection of thermostats and actuators. 4 versions are available:
| 230 V Ausführung| 24 V Ausführung
---|---|---
6 Zonen| SH-CD6-230| SH-CD6-24 (Externer 230 V / 24 V Transformator
erforderlich: SH-ST)
10 Zonen| SH-CD10-230| SH-CD10-24 (Externer 230 V/ 24 V Transformator
erforderlich: SH-ST)
2.1 Functions
It has integrated multiple functions:
- Wall mounted or mounter on DIN Rail.
- Push-in cable connections with strain relief.
- LED status indication and DIP switch for device setting.
- Manage 6 or 10 zones with 2 actuators per zone.
- Easy merging of the zones on the same thermostat.
- Multiple systems configuration.
- H&C input (230 V and volt free signal).
- Water temperature measurement (Probe not supplied) for humidity detection.
- Pump or boiler output (230 V and volt free signal).
- Anti-Grip management.
- contact for temperature limitation.
- Internal RF antenna, optional external antenna.
- Works with NC and NO actuators.
- USB connectivity for software update and data log.
2.2 Box content 2.3 First
installation
There are 2 ways to install the controller:
- Wall mounted using 2 screws.
- Mounted on a DIN Rail 35 x 7,5 (DIN EN 60715).
Product description
3.1 LED color meanings
LED | Bedeutung |
---|---|
LED Heizen und Kühlen (Rot/Blau) | Fix Rot = Heizbetrieb. |
Fix Blau = Kühlbetrieb.
Rot blinkend (bei Heizung) oder Blau blinkend (bei Kühlung) =
Sicherheitserkennung.
Rot / blau blinkend = RF-Verlust (mit SH-CD, SH-HCM, SH-CU, interne Antenne).
Im Falle eines RF-Verlusts schaltet das System in den Heizbetrieb.
LED Pumpe/Entfeuchter (Grün/Blau/Rot)| Fix Grün = Pumpe wird ausgelöst.
Rot blinkend = Systemfehler (Sicherheitserkennung / Fehler Feuchtesensor/…)
Blau blinkend = Globale Feuchteerkennung.
Blau blinkend = Problem mit der Feuchtekonfiguration.
LED Datalog (Rot/Grün)| Grün blinkend = Laufende Datenaufzeichnung.
LED pro Zone (Rot/Grün)| Grünes Blinken = RF-Übertragung/Empfang. Fix Rot =
Heiz- oder Kühlbedarf in der Zone.
Rot blinkend = RF-Fehler Verbindung mit dem Thermostat.
Rotes Blinken in allen Zonen = RF-Antennenfehler. Im Falle eines RF-Verlusts
mit SH-HCM oder SH-CU, schaltet das System in den Heizbetrieb.
3.2 Keys
3 capacitive keys are available. 3.3 DIP switch configuration
DIP switch number| **Function| Value (default: OFF)|
****Configuration| ****Description**
---|---|---|---|---
DIP1| Controller function| OFF| Local pump| See 4.3
ON| Global pump
DIP2| Actuator types| OFF| NC actuator| See 4.6
ON| NO actuator
DIP3| Pump start delay (for the first requested
drive) and drive stop delay (for the last requested drive)| OFF| 2 min/5 min|
See 4.3 and 4.6
ON| 5 min/20 min
DIP4 and DIP5| H&C switch control| OFF| OFF| Central unit SH-CU| See 4.2
OFF| ON| Master thermostat SH-DT
ON| OFF| SH-HCM
| ON| SH-CD
DIP6| Anti Grip| OFF| Enabled| See 6.1
ON| Disabled
DIP7| Humidity management| OFF| Safety approach| See 4.5
ON| Comfort approach
DIP8| Humidity sensor| OFF| ON/OFF sensor| See 4.5
ON| Water temperature sensor
3.4 Usb stick
Usb connectivity allows:
-
To update the software of the controller.
-
To record data for system monitoring (datalog).
For the software update, please refer to www.tece.com for getting the file, put the file on an usb stick. -
Insert the usb stick on the controller.
-
Switch off/on the controller.
-
During update,
-
Green led are power on from z1 to z6/z10
-
All led become red
-
Red led are power off from z6/z10 to z1
-
After update, you can remove the usb stick.
For trouble shooting, datalog is useful to record data on an ascii file stored on the usb dongle for trouble shooting. By pressing for 5 seconds, the master goes in features menu. The led of the first zone blinks either in red (datalog is enable) or in green (datalog is disable). You can enable or disable the datalog by clicking on . Long press on allow to leave the feature menu (otherwise there is a timeout of 10 s before automatically leaving the feature menu) One log file is created every 14 days. In the file, a record is made every 10 min.
Inputs/outputs
4.1 Power supply![TECE SH-CD6-230 Regelverteiler and Control Distributor
-
Power supply](https://manuals.plus/wp-content/uploads/2024/06/TECE-SH- CD6-230-Regelverteiler-and-Control-Distributor-Power-supply.jpg) 4.2 Heating/cooling (H &C) Input
Purpose: This input allows switching the regulation mode for the system: Heating or cooling.
Source of the signal:- A mechanical switch
- A Heat Pump
- A SH-SM paired on the SH-CU central unit as an ON/OFF device.
This solution allows getting a remote control of the H&C mode from the application. Format des Signals: Der Eingang kann potenzialfrei oder spannungsführend 230 V sein.
Mode | Free contact | Live contact |
---|---|---|
Heating | Opened | No signal |
Cooling | Closed | 230 Vac |
Only one device in the system should be able to select the H&C mode. Other possible H&C switch signal source (See 3.3)
-
Central unit (set manual H&C mode in the installer menu of the central) DIP4/DIP5 = OFF/OFF.
-
SH-HCM which embeds a H&C input DIP4/DIP5 = ON/OFF.
-
Digital thermostat configured as a Master H&C thermostat in manual or automatic mode (only one thermostat per installation) DIP4/DIP5 = OFF/ON.
If you have multiple connecting boxes SH-CD in the system, the H&C mode should be controlled by only one controller: -
Without central, the system considers the Connecting box set as Main SH-CD (please refer to 5.1.2) DIP4/DIP5 = ON/ON.
-
With central:
-
If the Connecting box controls the H&C mode, DIP4/DIP5 = ON/ON.
-
If the Central unit controls the H&C mode, DIP4/DIP5 = OFF/OFF.
DIP4 | DIP5 | Changeover signal H &C request by |
---|---|---|
OFF | OFF | Central unit (SH-CU) |
OFF | ON | Thermostat |
ON | OFF | Heat&cool module (SH-HCM) |
ON | ON | Connecting box (SH-CD) |
4.3 Pump Output
There are 2 outputs:
-
Live contact output (230 Vac)
-
Free contact output
These outputs can be used to trigger: -
A zone valve
-
A pump
-
A boiler or heat pump
The 2 outputs are triggered when there are a heating or cooling demand: -
In the controller if DIP switch 1 = OFF = local
-
In the system if DIP switch 1 = ON = global See 3.3
The delay between the heating or cooling demand and the pump activation is configurable: -
Pump starts 2 minutes after heating or cooling demand if DIP switch 3 = OFF
-
Pump starts 5 minutes after heating or cooling demand if DIP switch 3 = ON See 3.3
The purpose is to consider the latency of the actuator.
4.4 Contact for temperature limitation
This is a security input (Free contact).
Closed Contact | Opened Contact |
---|---|
No security detection | Overheating or overcooling detection |
The security input should be used on a controller with a pump.
When the contact is opened:
- The local pump output is stopped (even if DIP1=ON, i.e. global pump on the controller).
- The actuators are closed.
- The Pump/Drier LED is red blinking.
- The Heat and Cool LED is red blinking (in heating) or blue blinking (in cooling).
- If the controller is a sub controller, the heating or cooling demand is not sent to the main controller.
You can use a contact thermostat for thermal security. You can install 2
contact thermostats in serial to protect against both overheating and
overcooling (The security input is valid in both heating and cooling mode).
The product is delivered with a strap on the connector.
Please note that the pump of the SH-HCM is triggered when at least one pump of
the multiple SH-CD installed in the system is triggered.
4.5 Humidity detection input
The product has a humidity detection input.
2 possible types of signal according to DIP8 (See 3.3):
- A humidity contact sensor.
- Water temperature sensor (CTN 10 kΩ): Require SH-DTH thermostat.
4.5.1 Humidity contact sensor (dew-point control)
DIP8 = OFF
Format of the signal: The input is a free contact.
No Humidity | Humidity detected |
---|---|
Opened contact | Closed contact |
In cooling mode, when humidity is detected, the controller:
- Stops the pump signal.
- Closes all actuators.
- Sends the humidity alarm to all other SH-CD in the system.
- Requests the SH-HCM to enable the dehumidifier.
If the controller is a sub controller, the cooling demand is not sent to the
main controller.
4.5.2 Water temperature sensor
DIP8 = ON
There are 2 usages of the water temperature measurement.
Humidity detection
In cooling mode, for each zone, the controller computes the dew point based on
the ambient temperature and relative humidity sent by each thermostat
(Thermostat with relative humidity sensor is required).
When the water temperature reaches the dew point in one zone, the controller:
Safety approach DIP7 = OFF | Comfort approach DIP7 = ON |
---|---|
Close the actuator of the zone and stop the cooling demand of the zone. | Keep |
the actuator of the zone opened for one hour then close the actuator and stop the cooling demand in the zone if the humidity alarm is still triggered.
-
Enable remote dehumidifier of the zone.
-
Requests the heat&cool module SH-HCM to enable the global dehumidifier for at least 15 min and up the disappea- rance of the alarm if no remote dehumidifier is available in the zone.
If the controller is a sub controller, the cooling demand of the zone is not sent to the main controller.
Heating&Cooling mode detection
When DIP4 = ON and DIP5 = ON (H&C switch control = SH-CD) and DIP8 = ON the water temperature is used to automatically detect the H&C mode. -
If water temperature > 24°C, the system is in heating mode.
-
If water temperature < 20°C, the system is in cooling mode.
This feature is useful when the Heat Pump switches automatically in heating or cooling mode and has no output to inform the system. -
If the SH-HCM measures a water temperature:
-
The temperature is sent to the SH-CD which can be used if there is no water temperature sensor.
-
If H&C input = cool mode: The system switches in cooling mode regardless the water temperature.
4.6 NC/NO actuators
Connect one NC or NO actuator per connector.
- 230 V actuators for SH-CD-230
- 24 V actuators for SH-CD-24
The type of actuators is defined by DIP2.
It is necessary to use the same type for all actuators.
When there is a heating or cooling demand in one zone, the actuator is
triggered immediately.
When the heating or cooling demand is stopped, the actuator is closed
immediately except if this is the last actuator opened in the controller. In
that case, the delay before starting to close the actuator is dependent of
DIP3 (See 3.3):
- If DIP3 = OFF, the system waits 5 min before closing the last actuator
- If DIP3 = ON, the system waits 20 min before closing the last actuator
Justification: Many heat pumps have a built-in turn-off delay (to avoid
successive switch OFF/ON). In this case, the heat pump continues to run for x
minutes beyond the actual switch-off time. It is important to keep at least
one circuit open unless there is a buffer tank, hydraulic switch or bypass in
the installation.
4.7 External antenna
The controller embeds an internal antenna. If require, an external antenna can
be connected to improve the RF communication. It could be useful if the
controller is installed inside a metallic box. In that case, you need to
install the external antenna outside the metallic box.
Please respect the mounting to optimize sensitivity and avoid any dysfunction.
Antenna must be installed:
- outside the metallic box
- in vertical position
- and at least at 50 cm of metallic parts.
If you have several antenna (several controllers), they must be placed at minimum 80 cm of each other.
System configuration
5.1 System configuration without central unit
5.1.1. Standalone installation
Only one controller or multiple controllers without interconnection.
Device 1 | Device 2 | Remarks |
---|
By pressing for 5 seconds, the controller goes in RF pairing mode.
By using select zone 1 (LED blinks red), press to enter in Pairing with
thermostat mode. A green blinking LED is a position indicator. Move the green
blinking LED with to select the zone(s) to be paired. Select/deselect the zone
with . Selected zone is fix red but keeps blinking green (position indicator).
Already paired zone is fix green.| Thermostats:
Set product in RF pairing mode (refer to corresponding instruction manual).|
If RF pairing is done, the LEDs of the zones selected on the SH-CD must turn
off and the thermostats must exit the pairing mode.
To pair another thermostat, you need to enter/start the mode again.
Exit of the controller coupling mode: Long press on .
By pressing for 5 seconds, the controller goes in RF pairing menu.
By using select zone 3 (LED blinks red), press to enter in Pairing with a
slave device mode.
All LEDs are blinking green.| Set the device to RF coupling mode. Press the
button for 10 seconds.
For further information, refer to the manual of the respective device.| When
link is done SH-CD returns to coupling mode and SH-HCM returns to normal mode.
Exit of the controller coupling mode: Long press on
REMARK: only one heat-cool module SH-HCM per installation.
By pressing for 5 seconds, the controller goes in RF pairing menu.
By using select zone 3 (LED blinks red), press to enter in Pairing with a
slave device mode.
All LEDs are blinking green.| Set the SH-SM to RF coupling mode. Press the
button for 5 seconds
For further information, refer to the manual of the device.| When link is done
SH-SM exits coupling mode.
SH-CD returns to coupling mode. Exit of the controller coupling mode: Long
press on .
By pressing for 5 seconds, the controller goes in RF pairing menu.
By using select zone 3 (LED blinks red), press to enter in Pairing with a
slave device mode.
All LEDs are blinking green.| Set the SH-R to RF coupling mode. Press the
button for 3 seconds.
For further information, refer to the manual of the device.| When link is done
SH-R exits coupling mode.
SH-CD returns to coupling mode. Exit of the controller coupling mode: Long
press on .
5.1.2. Multiple controller’s installation
If there are multiple interconnected controllers in the installation, there
are 1 main-controller (Main SH-CD) and up to 3 sub-controllers (Sub SH-CD).
The main controller centralizes the information for the sub-controllers. If a
heat-cool module SH-HCM is used, it should be paired to the main-controller.
- The main controller propagates the Heat and Cool mode to the sub-controllers. This information could come from the SH-HCM or from a Master Digital thermostat according to the DIP4 and DIP5 (See 3.3)
- The main controller could handle the pump signal of the whole installation according to DIP1 (See 3.3)
Device 1: Main Controller | Device 2: Sub Controller | Remarks |
---|
First, all radio thermostats must be paired with the respective SH-CD
controller! See 5.1.1
By pressing for 5 seconds, the controller goes in RF pairing menu.
By using select zone 3 (LED blinks red), press to enter in Pairing with a
slave device mode.
All LEDs are blinking green.| By pressing for 5 seconds, the controller goes
in RF pairing menu.
By using select zone 2 (LED blinks red), press to enter in Pairing with a
master device mode.
All LEDs are blinking red.| When RF pairing is done, both SH-CD return to
pairing mode.
Exit of the controller pairing menu: Long press on .
5.2 System configuration with central unit
The central unit centralizes the communication between controllers.
Device 1: SH-CD | Device 2: SH-CU | Remarks |
---|
First, all radio thermostats must be paired with the respective SH-CD
controller! See 5.1.1
By pressing for 5 seconds, the controller goes in RF pairing menu. By using
select zone 2 (LED blinks red), press to enter in Pairing with a master
device mode.
All LEDs are blinking red.| Put the device into RF pairing mode. Select a
room (Room 1).
When pairing a SH-CD with SH-CUF, a room is generated for each wireless
thermostat. Therefore, the rooms must not be created in the central unit
beforehand.| When RF pairing is done, both SH-CD and SH-CU exit the pairing
mode.
Exit of the controller pairing menu: Long press on .
5.3 Control a dehumidifier per room.
There are 2 ways to detect humidity:
- At controller level using the humidity detection input (See 4.5).
- At the room level if the thermostat embeds a relative humidity sensor. When humidity is detected, there are 2 ways to trigger dehumidifier:
- A global dehumidifier is triggered by the SH-HCM if the feature is activated on SH-HCM.
- A dehumidifier is triggered on the room level where the humidity is detected.
For that case, you need to pair a SH-SM receiver on each zone of the controller to trigger a dehumidifier.
Device 1: SH-CD | Device 2: SH-SM | Remarks |
---|
By pressing for 5 seconds, the controller goes in RF pairing menu.
By using select zone 4 (LED blinks red), press to enter in dehumidifier
Pairing mode.
Choose the zones with .
Zones are defined by paired thermostat channels.
For example: TH1 = Z1, TH2 = Z2+Z3 and TH3 = Z4+Z5+Z6. Navigation proposes 3
zones to pair a dehumidifier on (Z1), (Z2+Z3) and (Z4+Z5+Z6).
Select/deselect the zone with . (You can select only one zone per
dehumidifier). Cursor blinks green.
Selected zone is blinking red and green Already paired zone is fix green.
(To remove a dehumidifier, select a zone in green, then press simultaneously
on and up to get the zone blinking in green)| Set the SH-SM to RF coupling
mode.
Press the button for 5 seconds. For further information, refer to the manual
of the device.| When link is done SH-SM exits coupling mode.
SH-CD returns to coupling mode.
Exit of the controller coupling mode: Long press on .
Other Features
6.1 Anti Grip Feature
The feature is enable using DIP6 (See 3.3). If the valves are not active
during a week, a complete exercise is triggered (actuator + pump outputs+
Heat/cool demand sent to the SH-HCM. 6.2 Reset
In case of dysfunction, it may be required to reset the product to factory
setting.
By pressing for 5 seconds, the master goes in Reset menu. LED of zone 1
starts red blinking, the remaining zone LED start green blinking.
Then by pressing simultaneously on , and up to getting all zone LED in red,
the controller reset is triggered and the product restarts. LEDS switch off.
6.3 Trouble shooting
Symptom | Trouble | Description | Trouble shooting |
---|---|---|---|
Red or blue blinking on Heat and Cool LED and Red blinking on Pump/ Drier LED | |||
Security detection | The contact of the security input is opened | If you not |
using a security thermostat, make sure, you have installed a strap on the
security thermostat input. Otherwise control the temperature of the pipe (too
hot in heating mode, too cold in cooling mode)
Red / Blue blinking on Heat and Cool LED| RF Issue| The controller has lost
the connection with a RF device other than a thermostat| Check distance
between devices. If the controller is installed within a metallic box, use an
external antenna located outside the metallic box.
A RF repeater may be required.
Fast Blue flashing on Pump/Drier LED| Humidity configuration problem| NTC
measurement on H&C input whereas the DIP8 = OFF.
ON/OFF input on H&C input whereas the DIP8 = ON| Check if NTC-sensor and DIP
switch setting
Red blinking on 1 zone| RF error with the thermostat| The controller has lost
the connection with the thermostat.| Check distance between the controller and
the thermostat.
A RF repeater may be required.
Red blinking on all zones| RF antenna error| The controller has lost all RF
connections (Thermostat and other devices)| External antenna may be required.
Technical characteristics
7.1 Technical data
| SH-CD6-24, SH-CD6-230, SH-CD10-24, SH-CD10-230
---|---
Electrical protection| Class II with functional earth
IP Protection| IP30
Shipping and storage temperature| -10 °C à 50 °C (14 °F à 122 °F)
Power supply| 230 V AC ± 10 % 50 Hz
Output maximum load (2 outputs)| Relay : 5 A
Actuators| 230 V /24 V NC/NO up to 2 W
Compatibility| SH-AT, SH-DT, SH-DTP, SH–HCM, SH-CU, SH-SM
7.2 Dimensions and weight
Directives
Designation | Description | Link |
---|---|---|
Low Voltage Directive (LVD) | The Low Voltage Directive (LVD) (2014/35/EU) |
ensures that electrical equipment within certain voltage limits provides a
high level of protection for European citizens, and benefits fully from the
Single Market.| 2014/35/UE
Electromagnetic Compatibility (EMC) Directive 2014/30/EU| The Electromagnetic
Compatibility (EMC) Directive 2014/30/EU ensures that electrical and
electronic equipment does not generate, or is not affected by, electromagnetic
disturbance.| 2014/30/UE
Restriction of the use of certain hazardous substances Directive (RoHS)
2011/65/ EU| Directive on the restriction of the use of certain hazardous
substances in electrical and electronic equipment.| 2011/65/EU
Waste Electrical & Electronic Equipment Directive (WEEE)| The WEEE Directive
(2012/19/EU) aims to reduce the amount of waste electrical and electronic
equipment that ends up in landfill.| 2012/19/EU
Ecodesign Commission Regulation| Ecodesign requirements for local space
heaters.| 2015/1188
Radio Equipment Directive (RED) 2014/53/EU| The Radio Equipment Directive
2014/53/EU (RED) establishes a regulatory framework for placing radio
equipment on the market.| 2014/53/EU
TECE GmbH
Germany
T + 49 25 72 / 9 28 – 0
info@tece.com
www.tece.com
FL230 091 00 a
References
- TECE - Close to you | TECE International
- Home | Watts Europe
- HOME
- stiftung-ear.de
- TECE - Close to you | TECE International