Introduction

R718PA3 is a Class A device based on the LoRaWANTM protocol of Netvox and is compatible with the LoRaWAN protocol.
R718PA3 can be externally connected to an ozone sensor (RS485) to report the concentration of ozone collected by the device to the corresponding gateway. The device is compatible with the LoRaWAN protocol.
LoRa Wireless Technology:
LoRa is a wireless communication technology dedicated to long distance and low power consumption. Compared with other communication methods, LoRa spread spectrum modulation method greatly increases to expand the communication distance. Widely used in long-distance, low-data wireless communications. For example, automatic meter reading, building automation equipment, wireless security systems, industrial monitoring. Main features include small size, low power consumption, transmission distance, anti-interference ability and so on.
LoRaWAN:
LoRaWAN uses LoRa technology to define end-to-end standard specifications to ensure interoperability between devices and gateways from different manufacturers.

Appearance

netvox-R718PA3-Wireless-O3-Sensor-fig-1

Main Feature

  • Adopt SX1276 wireless communication module
  • 12V DC power supply
  • O3 detection
  • The base is attached with a magnet that can be attached to a ferrous object
  • Main body protection level: IP65 / IP67
  • Compatible with LoRaWANTM Class A
  • Frequency hopping spread spectrum
  • Configuring parameters and reading data via third-party software platforms, and set alarms via SMS text and email (optional)
  • Applicable to third-party platforms: Actility/ThingPark, TTN, MyDevices/Cayenne

Set Up Instruction

On/Off

Power on DC12V adapter

Turn on

| DC12V power supply, the green indicator flashing once means turn

on successfully.


Turn off (Restore to factory setting)

| Press and hold the function key for 5 seconds and the green indicator

flashes 20 times.

Power off| Remove DC12V adapter.




Note:

| 1.                 In the first 5 seconds after power on, the device will be in engineering test mode.

2.                 On/off interval is suggested to be about 10 seconds to avoid the

interference of capacitor inductance and other energy storage components.

Network Joining


Never joined the network

| Turn on the device to search the network to join. The green indicator stays on for 5 seconds: success

The green indicator remains off: fail

---|---


Had joined the network

(Not restore to the factory setting)

| Turn on the device to search the previous network to join. The green indicator stays on for 5 seconds: success

The green indicator remains off: fail


Fail to join the network

| Suggest to check the device verification information on the gateway

or consult your platform server provider.

Function Key


Press and hold for 5 seconds

| Restore to factory setting / Turn off

The green indicator flashes 20 times: success The green indicator remains off: fail

---|---


Press once

| The device is in the network: the green indicator flashes once and sends a report

The device is not in the network: the green indicator remains off

Data Report

  • The device will send a version package report immediately after powered on and it will send a report data with the voltage, the concentration of ozone after 20 seconds.
  • The device sends data according to the default configuration before any other configuring.

Default setting:

  • Maxime: Max Interval = 3min = 180s
  • Minime: The MinTime configuration is not available.
  • But the software has a restriction, MinTime must be configured a number greater than 0.

Note:

  1. The cycle of the device sending the data report is according to the default.
  2. R718PA3 reports the concentration of ozone.
  3. The device is powered by DC/AC adaptor; therefore, Battery displays 0x00.

Please refer Netvox LoRaWAN Application Command document and Netvox Lora Command Resolver
http://loraresolver.netvoxcloud.com:8888/page/index to resolve uplink data.

Example of ConfigureCmd

FPort:0x07

Bytes 1 1 Var (Fix =9 Bytes)
CmdID DeviceType NetvoxPayLoadData
  • CmdID– 1 byte
  • DeviceType– 1 byte – Device Type of Device
  • NetvoxPayLoadData– var bytes (Max=9bytes)

Description

|

Device

| Cmd ID| Device Type|

NetvoxPayLoadData

---|---|---|---|---
ConfigReport Req|

R718PA3

|

0x01

|

0x57

| MinTime (2bytes Unit: s)| MaxTime (2bytes Unit: s)| Reserved (5Bytes, Fixed 0x00)
ConfigReport Rsp|

0x81

| Status (0x00_success)| Reserved (8Bytes, Fixed 0x00)
ReadConfig

ReportReq

| 0x02| Reserved

(9Bytes, Fixed 0x00)

ReadConfig ReportRsp|

0x82

| MinTime (2bytes Unit: s)| MaxTime (2bytes Unit: s)| Reserved (5Bytes, Fixed 0x00)

  1. Configure device parameter MaxTime = 1min (The MinTime configuration is useless, but it needs to be set greater than 0 because of the software limitation.)
  2. Downlink: 0157000A003C0000000000 Device Return: 8157000000000000000000 (configuration is success) 8157010000000000000000 (configuration is failure)
  3. Read device configuration parameter
  4. Downlink: 0257000000000000000000 Device Return: 8257000A003C0000000000 (device current parameter)

Installation

  1. 1. The device has a built-in magnet (as the figure below). It can be attached to the surface of an iron object conveniently and quickly when it is installed. In order to make the device installation more secure, use screws (purchased) to fix the device to the wall or other surface (such as the installation diagram). The device is screwed by two screws in the middle (purchased by users).
    Note: Do not install the device in a metal shielded box or in an environment with other electrical equipment around it to avoid affecting the wireless transmission of the device.

  2. The device periodically reports the data, the concentration of ozone, according to Max Time. The default Max Time is 3min.
    Note: MaxTime can be modified by the downlink command, but it is not recommended to set the time too short

  3. The device can be used in scenarios such as:

  • Environmental protection
  • Disinfection detection
  • Chemical medicine
  • Real-time monitoring gas emission
  • Monitoring ozone emission during meat processingnetvox-R718PA3-Wireless-O3-Sensor-fig-3

Important Maintenance Instruction

Kindly pay attention to the following in order to achieve the best maintenance of the product:

  • Keep the equipment dry. Rain, moisture and various liquids or water may contain minerals that can corrode electronic circuits. In case the device is wet, please dry it completely.
  • Do not use or store in dusty or dirty areas. This way can damage its detachable parts and electronic components.
  • Do not store in excessive heat place. High temperatures can shorten the life of electronic devices, destroy batteries, and deform or melt some plastic parts.
  • Do not store in excessive cold place. Otherwise, when the temperature rises to normal temperature, moisture will form inside which will destroy the board.
  • Do not throw, knock or shake the device. Treating equipment roughly can destroy internal circuit boards and delicate structures.
  • Do not wash with strong chemicals, detergents or strong detergents.
  • Do not paint the device. Smudges can make debris block detachable parts up and affect normal operation.
  • Do not throw the battery into the fire to prevent the battery from exploding.
  • Damaged batteries may also explode.
  • All the above suggestions apply equally to your device, batteries and accessories. If any device is not operating properly.
  • Please take it to the nearest authorized service facility for repairing.

Copyright©Netvox Technology Co., Ltd.
This document contains proprietary technical information which is the property of NETVOX Technology. It shall be maintained in strict confidence and shall not be disclosed to other parties, in whole or in part, without written permission of NETVOX Technology. The specifications are subject to change without prior notice.

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals