SEIFERT 6155305 BTU Thermoelectric Cooler
User manual
THIS instruction manual contains information and instructions to enable the user to work safely, correctly, and economically on the unit. Understanding and adhering to the manual can help one:
- Avoid any dangers.
- Reduce repair costs and stoppages.
- Extend and improve the reliability and working life of the unit.
PLEASE ENSURE TO USE THE RIGHT VERSION OF THE INSTRUCTION MANUAL SUITABLE
FOR YOUR UNIT.
Intended use
The unit is to be used exclusively for the dissipation of heat from control
cabinets and enclosures (stationary, not moving) in order to protect
temperature-sensitive components in an industrial environment. To meet the
conditions of use, all the information and instructions in the instruction
manual must be adhered to.
- General danger
- Indicates compulsory safety regulations which are not covered by a specific pictogram such as one of the following.
- High electric voltage
- Indicates electric shock danger.
- Important safety instruction
- Indicates instructions for safe maintenance and operation of the unit.
- Attention
- Indicates possible burns from hot components.
- Attention
- Indicates possible damage to the unit.
- Instruction
- Indicates possible danger to the environment.
Legal Regulations
Liability
The information, data and instructions contained in this instruction manual
are current at the time of going to press. We reserve the right to make
technical changes to the unit in the course of its development. Therefore, no
claims can be accepted for previously delivered units based on the
information, diagrams or descriptions contained in this manual. No liability
can be accepted for damage and production caused by:
- Disregarding the instruction manual
- Operating error
- Inappropriate work on or with the unit
- The use of non-specified spare parts and accessories
- Unauthorised modifications or changes to the unit by the user or his personnel
The supplier is only liable for errors and omissions as outlined in the guarantee conditions contained in the main contractual agreement. Claims for damages on any grounds are excluded.
Safety Instructions
Upon delivery the unit is already meeting current technical standards and can
therefore be safely taken into operation. Only authorised personnel is allowed
to work on the unit. Unauthorised personnel must be prohibited from working on
the unit. Operating personnel must inform their superiors immediately of any
malfunction of the unit.
Please note that before starting to work on or with the unit, a procedure must
be carried out inside the cabinet on which the unit is to be mounted.
Before commencing work inside the cabinet, the control cabinet manufacturer’s
instruction must be read with regards to:
- Safety instructions.
- Instructions on taking the cabinet out of operation.
- Instructions on the prevention of unauthorised cabinet reconnection.
The electric equipment meets the valid safety regulations. One can find dangerous voltages (above 50 V AC or above 100 V DC)
- Behind the control cabinet doors.
- On the power supply in the unit housing.
The unit has to be operated according to the type plate and the wiring diagram and must be protected externally from overloading and electrical faults via suitable protective devices.
-
Danger through incorrect work on the unit
The unit can only be installed and maintained by technically competent and qualified personnel, using only supplied material according to the supplied instructions. -
Danger from electrical voltage
Only specialized personnel are allowed to maintain and clean the unit. The person must ensure that for the duration of the maintenance and cleaning, the unit is disconnected from the electrical supply. -
Attention
Damage to the unit through the use of inappropriate cleaning materials. Please do not use aggressive cleaning material. -
Instruction
Damage to the environment through unauthorized disposal. All spare parts and associated materials must be disposed of according to environmental laws.
- Ambient fans
- Ambient heat sinks
- Thermoelectric elements
- Insulation
- Internal heat sink
- Internal fan
Technical Data
- Order Number 6155305
- Cooling Capacity L35L35 150 W
- Operating Temperature Range -20°C – +65°C
- Air Flow Volume (System / Unimpeded) Ambient air circuit: 120 / 260 m³/h
- Cabinet air circuit: 60 / 170 m³/h
- Mounting Wall mounted (with frame)
- Housing Material Stainless steel AISI 304 (V2A)
- Dimension A x B x C (D+E) 500 x 330 x 200 mm
- Weight 19 kg
- Cut Out Dimension 244 x 428 mm
- Voltage / Frequency 120 – 230 V ~ 50/60 Hz
- Current L35L35 1.4 A @ 120 V
- 0.7 A @ 230 V
- Starting Current 2.1 A @ 120 V
- 1.1 A @ 230 V
- Max. Current 1.5 A @ 120 V
- 0.8 A @ 230 V
- Nominal Power L35L35 170 W
- Max. Power 180 W
- Fuse 3 A (T) @ 120 V
- 2 A (T) @ 230 V
- Connection 8-Pole connector
- Ingress Protection IP 66, NEMA / UL Type 4X
- Approvals CE, cURus
Mounting
Always switch off the power supply before starting any work on the unit.
Installation
Ensure that flows of air leaving and entering the cooling unit, internal and
external, are not obstructed. Before drilling the enclosure, ensure the fixing
elements and couplings will not interfere with the equipment inside the
enclosure itself. When all mounting preparations are complete the actual
mounting operation can commence. Only use the enclosed material to mount the
unit on the cabinet.
Proceed as follows to mount the unit on the cabinet:
- Set the unit up on the cabinet.
- Ensure that the electrical connection is above the internal fan.
- Unit without duct: screw the M6 locknuts & washers into the M6 set screws in the unit.
- Unit with duct: screw the M6 screws & washers into the M6 threaded rivets in the unit. The resistance of the earth connection between the cabinet and cooling unit must be <0.1Ω.
Condensate management
Depending on the mounting situation the condensation management may need to be considered and possibly adjusted.
Mounting Principle
In order to maintain the TYPE 4X rating, the tightening torque for this unit should be 4.5 Nm and needs to follow the below sequence.
Cut Out Dimension
Dimension (H x W x D)
Electrical Connection
High electric voltage present. Installation, maintenance, cleaning and any
other work must be carried out by qualified personnel only. The personnel must
ensure that for the duration of this work the unit and the cabinet are
disconnected from the electrical supply and protected against
unauthorised/accidental reconnection.
Instruction: Check that the available voltage, frequency, and fuse rating
are the same as those stated on the unit data label.
Connection to the main electricity supply
The main connection is made via a cable. To connect the unit to the mains
supply proceed as follows:
- Disconnect the control cabinet from the mains.
- See the connection details on the circuit diagram.
- Note the connections on the three-pole terminal blocks from the following diagram.
Terminal 230 V ~ 50/60 Hz
- L Live
- PE Protective Earth
- N Neutral
Ensure that the correct polarity is maintained.
- The fans should have a clockwise rotation.
- Connect the unit to the mains.
- Take the control cabinet back into operation in the prescribed manner.
Power consumption and start-up current are stated on the data label and under technical data.
Controller
The display shows the temperature in the range of -50°C to +150°C (-58°F to +302°F). The temperature is displayed with a resolution of tenths between -19.9°C and +99.9°C (-3.8°F to +211.8°F). During programming, it shows the codes and values of the parameters. The display also shows icons according to occurring events.
Display icons
Icon Function Description
- Cooling relay active Flashes when the activation is delayed or inhibited by protection times, external disabling, or other procedures in progress
- Alarm relay active
- Heating relay active
- Ambient blower relay active
Alarm Flashes when alarms are active
Cooling mode Signal operation of the unit in cooling mode
TEST Test mode in progress Activated only by manual procedure
Programming
The operating parameters can be modified using the front keypad. Access differs
depending on the type of parameter. Access to configuration parameters is
protected by a password that prevents unwanted modifications or access by
unauthorized persons.
Setting cooling set point, St1:
- Press “SET” and the display should show St1 and then the pre-set value of St1. (default: +35°C / +95°F)
- Reach the desired value by using ▲ or ▼.
- Press “SET” again to save the new value of St1.
Setting temperature units (°C / °F), low-temperature alarm, and high- temperature alarm:
- Press the “PRG” button for 5 seconds to reach the modifiable parameter list.
- Use ▲ or ▼ to reach the desired parameter:
- C18 for temperature unit of measure
- °C = 0
- °F = 1
- P25 for low-temperature alarm threshold (default -10°C / +14°F)
- P26 for high-temperature alarm threshold (default +55°C / +131°F)
- Press “SET” on the desired parameter to display the current value.
- Use ▲ or ▼ to reach the desired value.
- Pressing “SET” temporarily saves the new value and returns to the parameters list.
- Repeat steps 2-5 to set other parameters.
- Press “PRG” for 5 seconds to permanently save the new values.
Set Point Parameter Default Range
- Cooling St1 35°C / 95°F 20°C – 50°C / 68°F -122°F
- Low Temperature Alarm P25 -10°C / 14°F -50°C – P26 / -58°F – P26
- High Temperature Alarm P26 55°C / 131°F P25 – 150°C / P25 – 302°F
Test function
Different test functions can be used depending on the combination of keys
pressed. Such tests run for the duration of 4 minutes.
- “SET+▲” tests cooling relays
- “SET+▼” tests alarm relays
Important Notes
- Whilst programming, if no button is pressed for 10 seconds, the display starts flashing, and after 1 minute returns to the main display without saving changes.
- To increase scrolling speed, press and hold the ▲ or ▼ button for at least 5 seconds.
- When pressing “PRG” for 3 seconds, the firmware revision code is displayed for 2 seconds.
- When cleaning the controller panel, do not use ethanol, hydrocarbons, ammonia or their by-products. Use neutral detergents and water.
The hysteresis is 5K, the minimum ON-time is 0s, the minimum OFF-time is 0s.
Wiring Diagram
Taking into Operation
- The power supply rating on the rating plate must comply with the mains supply
- Always disconnect the power supply before opening the unit.
Heat load to be dissipated from the enclosure should not exceed the specific
cooling output of the unit at any condition. While selecting a cooling unit
always cater for a safety margin of at least 15% extra cooling output. The
Peltier – elements should be controlled by a suitable thermostat. Models TG
6XXX with 100 – 230 V supply have already a controller integrated.
Trouble Shooting
In case of a fault please contact your nearest servicing office. A list of
service partners can be found on our website www.seifertsystems.com
Maintenance & Cleaning
- Always switch off power supply before starting any work on the unit. Only qualified personal may conduct any maintenance work on the cooling unit.
- All Peltier units are virtually maintenance-free and no filters which need to be cleaned or replaced. Check the ambient heat sinks from time to time. In case they are dirty proceed as following:
- Disconnect the enclosure from the mains.
- Clean the heat sink profile as required by blowing it out with compressed air.
- In cases of extreme pollution wet cleaning is required.
- The unit must be removed from the control cabinet for wet cleaning
Should a wet cleaning be necessary proceed as follows:
- Disconnect the whole plant from the mains.
- Remove the unit from the cabinet.
- Ensure that the seals are not damaged.
- Wash the heat sink with an environmentally safe cleaning fluid.
- Danger to the environment through unauthorized disposal.
Disposal
Dispose of cooling unit and used parts with due regard for the environment and
in accordance
with environmental laws and regulations.
Maintenance
Note: Only use original replacement parts when repairing the unit. This ensures that the unit functions perfectly and remains safe.
Fan replacement: The average working life of the fan is ca. 40,000 hours under normal conditions. Should a fan replacement be necessary proceed as follows:
- Disconnect the unit from the mains.
- Remove the unit cover.
- Remove the screws from the relevant fan.
- Mount a new fan.
Danger: to the unit through incorrect work.
Make sure that the cabinet fan or the ambient fan are not misplaced in the
unit as they are different. Ensure that the correct polarity is maintained. The
fans must rotate clockwise!
- Replace the 4 fan fixing screws.
- Close the unit and take it back into operation.
Transport & Storage
During transport and storage, the cooling unit must be kept in the position marked on the box and at a temperature between -40˚C and 70˚C and a relative humidity of max. 95% (at 25°C). In case of damaged packaging after transport or in-house handling, we recommend controlling the unit for any internal damages.
Parts supplied / Spare parts / Accessories
- 1 x Peltier Cooling unit
- 1 x Instruction manual
- 1 x CE Conformity Declaration
- 10 x Screws M5
- 10 x Washers
- 1 x IP66 RAL7035 Drain Plug (required to maintain IP66 rating)
- 1 x Female 8-Pole Connector
- 1 x Mounting Template
- 1 x Mounting Gasket Set
- Seifert Systems GmbH
- Albert-Einstein-Str. 3
- 42477 Radevormwald
- Germany
- Tel.+49 2195 68994-0
- info.de@seifertsystems.com
- Seifert Systems Ltd.
- HFO9/10
- Hal-Far Industrial Estate
- Birzebbuga, BBG 3000
- Malta
- Tel.+356 2220 7000
- info@seifertsystems.com
- Seifert Systems AG
- Wilerstrasse 16
- 4563 Gerlafingen
- Switzerland
- Tel.+41 32 675 35 51
- info.ch@seifertsystems.com
- Seifert Systems GmbH
- Bärnthal11
- 4901 Ottnang
- Austria
- Tel.+43 7676 20712 0
- info.at@seifertsystem.com
- Seifert Systems Ltd.
- Rep. Office
- 26100 Cremona
- Italy
- Tel.+39 349 259 4524
- info@seifertsystems.com
- Seifert Systems Inc.
- 75 Circuit Drive
- North Kingstown
- RI 02852
- USA
- Tel.+1401-294-6960
- info.us@seifertsystems.com
- Seifert Systems Pty Ltd.
- 105 Lewis Road
- Wantirna South
- 3152 Victoria
- Australia
- Tel.+61 3 98 01 19 06
- info@seifertsystems.com.au
Documents / Resources
|