HERSCHEL Vulcan Fan Purge Timer Instruction Manual
- June 3, 2024
- HERSCHEL
Table of Contents
Vulcan Fan Purge Timer
Instruction Manual
Vulcan Fan Purge Timer
ELECTRICAL
EQUIPMENT:
Waste electrical products should not be disposed of with household waste.
Please recycle where facilities exist.
IMPORTANT NOTICE TO PURCHASER:
Before utilizing the product, user should determine the suitability of the
product for its intended use. HERSCHEL INFRARED LTD expressly disclaims the
implied warranties and conditions of merchantability and fitness for a
particular purpose. In no case shall HERSCHEL INFRARED LTD be liable under any
legal theory, including but not limited to contract or strict liability, for
any direct, indirect special, incidental or consequential damages resulting
from product use.
Original instructions covering Fan Purge Timer models produced 072021 onwards.
IMPORTANT SAFETY PRECAUTIONS
READ THESE INSTRUCTIONS CAREFULLY AND RETAIN FOR FUTURE REFERENCE.
Failure to observe these instructions will invalidate the warranty.
WARNING
TO REDUCE THE RISK OF ELECTRIC SHOCK OR INJURY:
- This appliance must be disconnected from its power source during installation activities and when replacing.
- Do not use if Line voltage exceeds 245V.
- The Fan Purge Timer must be mounted on a non-flammable surface.
- Installation must only be carried out by qualified electricians.
- No user-serviceable parts inside. Please contact Herschel or your Representative should any repairs be necessary.
SAVE THESE INSTRUCTIONS.
DESCRIPTION:
Herschel Infrared’s Fan Purge Timer is designed for use with the Vulcan
Industrial heater. It can be used in Single or 3-phase Vulcan installations.
The Fan Purge timer sits downstream of the circuit controller (Contactor,
Thermostat, PIR or PLC Control) and will switch on the Vulcan’s fans when
current is detected on any of the phases powering the heater. When set up
following these instructions, the Fan Purge Timer will leave the fans running
for between 2-3 minutes after current to the heater has been switched off.
The Fan Purge Timer does not carry any of the heater’s electrical load, so
typically only 1 unit is required for each 3-phase circuit. Maximum current on
the fan circuit is 5 amps which should be more than adequate to power all the
fans on the heaters on a given circuit. (Each fan consumes only 20 Watts so 5
amps implies up to 14 x 912kW
units or 28 x 5kW units).
INSTALLATION:
Fix the Fan Purge Timer to a wall by drilling 2 holes 70mm apart; insert
rawlplugs and use 2 pan-headed screws through the fixing centres in the back
of the box to secure the box to the wall.
ELECTRICAL CONNECTION:
Remove the 3 blanking covers at the bottom of the plastic box and Insert the 3
cable glands supplied with the Fan Purge Timer into the 3 holes.
Connect a permanent 240V electrical supply to the terminals on the far left
marked “240V IN FAN”) and take out the Live & Neutral Fan Output (Marked “Fan
O/P”) to power the fans.
Connect Line 1, 2, 3, Neutral and Earth from the 3-phase circuit to the
terminals on the far right (Marked “Sense”). For Single Phase installations,
connect the Live lead to the L1 terminal.
CONNECTION DIAGRAM 4 WIRE 3 PHASE HEATER LOADS AND NEUTRAL 240V AC FANS
OPERATION
IMPORTANT! Before First use, use a small screwdriver to set the Purge
Timer to 50% (approximately 2½ minutes). (Turn so the slot in the timer points
straight up.) The Green “POWER” LED will be lit when electrical supply to the
unit is present (and should therefore always be on).
The Red “STATUS” LED will light continuously when current is detected on any
of L1, L2 or L3 and the Cooling fans will run.
When current is no longer detected on any of L1, L2 or L3, the unit will go
into Purge mode. The Vulcan lamps will be OFF but Fans will continue to run
for 2 minutes. The Red “STATUS” LED will flash during Purge mode.
When the Red “STATUS” Led is off, this indicates both the heaters and the fans
are OFF.
TEST AND VERIFY THE ABOVE IMMEDIATELY FOLLOWING INSTALLATION. DO NOT ALLOW
VULCAN LAMPS TO OPERATE WITHOUT THE FANS RUNNING.
MAINTENANCE AND REPAIR:
DO NOT attempt to repair any electrical functions on this unit. Doing so will
void your warranty. Please contact Herschel or your Representative if a unit
fails.
DISPOSAL:
The Fan Purge Timer is an electrical product and at the end of its working
life it should be disposed of in accordance with local regulations.
WARRANTY:
Register your product here: https://www.herschel-infrared.co.uk/customer-
service/warranty-registration/ Within two years from date of purchase Herschel
will repair or replace the Fan Purge Timer where the fault is due to defects
in materials or workmanship. In the event of a warranty claim please consult
your local dealer and return the heater together with proof of purchase.
A prerequisite for validity of the warranty is use at the specified supply
voltage of the heater and use in accordance with the conditions specified in
this manual. Any further warranty or claims are excluded.
The warranty covers the repair or replacement of the defective product only
and Herschel shall have no liability for installation costs or consequential
loses however incurred.
Removing the serial number will void the warranty. The warranty will also be
void if the heater has been tampered with or opened in any way.
The product label must be left on the unit where it will remain visible after
installation if necessary. Herschel Infrared Ltd cannot accept responsibility
for damage, loss or injury caused by ingress of water or moisture, accidental
damage, mishandling, external impact, adjustment by unauthorised personnel or
failure to follow the correct maintenance and safety precautions as stated in
the manual. Refer to Herschel Infrared Ltd’s warranty policy for full details.