Satel SPP-110 Conventional Fire Alarm Sounder Instruction Manual

September 28, 2024
Satel

SPP-110 Conventional Fire Alarm Sounder

“`html

Specifications:

  • Product: Conventional fire alarm sounder SPP-110 EN
  • Firmware version: 1.00
  • Manufacturer: SATEL
  • Designed for use with SATEL fire alarm control panels
    (conventional: CSP-104, CSP-108, CSP-204, CSP-208; addressable:
    ACSP-402)

Product Usage Instructions:

1. Installation:

  1. Disconnect power before making any electrical connections.

  2. The sounder is designed for installation indoors, in spaces
    with normal air humidity.

  3. Turn the cover counter-clockwise and remove it.

  4. Drill the holes for screws in the enclosure base. Use the
    provided screws to fasten the base to the wall.

  5. Drill a hole for cables in the enclosure base.

  6. Place the enclosure base against the wall and mark the mounting
    hole locations.

  7. Drill holes for wall plugs (screw anchors) in the wall.

  8. Run the cables inside the enclosure base.

  9. Secure the enclosure base to the wall using wall plugs and
    screws.

  10. Use DIP switches to configure the sounder settings (refer to
    Configuring the sounder settings).

  11. Connect the zone circuit wires to the sounder. If it’s at the
    end of a line, attach a 10k resistor to its terminals.

  12. Replace the cover and lock it with a screw.

2. Configuring the sounder settings:

Use the DIP switches on the electronics board to configure the
sounder settings. Follow the instructions provided in the user
manual to select the desired tone and supply voltage.

FAQ:

Q: Can I use the SPP-110 sounder outdoors?

A: No, the sounder is designed for indoor use only in spaces
with normal air humidity.

Q: How do I know which tone to select for acoustic

signaling?

A: Refer to Table 1 in the user manual that provides a list of
tones and their corresponding switch settings on the electronics
board.

“`

Conventional fire alarm sounder
SPP-110 EN
Firmware version 1.00
spp-110_en 04/24 SATEL sp. z o.o. · ul. Budowlanych 66 · 80-298 Gdask · POLAND tel. +48 58 320 94 00
www.satel.pl

IMPORTANT
The device should be installed by qualified personnel. Prior to installation, please read carefully this manual in order to avoid mistakes that can lead to malfunction or even damage to the equipment. Disconnect power before making any electrical connections. Changes, modifications or repairs not authorized by the manufacturer shall void your rights under the warranty.
The following symbols may be used in this manual: – note, – caution.

The SPP-110 sounder is used for acoustic alarm signaling. The sounder is designed to work with the SATEL fire alarm control panels (conventional: CSP-104, CSP-108, CSP-204, CSP-208; addressable: ACSP-402).
1. Features
· Acoustic signaling by means of piezoelectric transducer. · 32 selectable tones. · Selectable volume level.
2. Installation
Disconnect power before making any electrical connections. The sounder is designed for installation indoors, in spaces with normal air humidity. 1. Turn the cover counter-clockwise and remove it (Fig. 1). 2. Drill the holes for screws in the enclosure base. Use the countersunk screws (Fig. 2)
or the non-countersunk screws (Fig. 3) to fasten the enclosure base to the wall. 3. Drill the hole for cables in the enclosure base (Fig. 4).

2

SPP-110

SATEL

4. Place the enclosure base against the wall and mark the location of mounting holes.
5. Drill the holes for wall plugs (screw anchors) in the wall.
6. Run the cables inside the enclosure base.
7. Use wall plugs and screws to secure the enclosure base to the wall. Select wall plugs specifically intended for the mounting surface (different for concrete or brick wall, different for plaster wall, etc.).
8. Use the DIP switches to configure the sounder settings (see: “Configuring the sounder settings” p. 3).
9. Connect the zone circuit wires to the sounder (Fig. 5). If the sounder is connected to the zone circuit at the end of line, screw a 10 k resistor to its terminals. You can connect the cable shields to the E terminals (using a shielded cable is not required).

SATEL

SPP-110

3

10. Replace the cover and turn it clockwise (Fig. 6). 11. Lock the cover with a screw (Fig. 7).

2.1 Configuring the sounder settings
Use the DIP switches on the electronics board (Fig. 8) to configure the sounder settings.

2.1.1 Selecting the tone
To select the tone, use the switches 1-5, marked as S1-S5 on the electronics board. The tones and their corresponding switch settings are described in Table 1 (where: switch in ON position = 1; switch in OFF position = 0).

N DIP switch

o

12345

1 00000

2 10000

3 01000

4 11000

Acoustic signaling

Frequency Hz

Description

800 & 970

2 Hz (250 ms ­ 250 ms)

800-970

7 Hz (7/s)

800-970

1 Hz (1/s)

2850

Continuous

4

N DIP switch

o

12345

5 00100

6 10100

7 01100

8 11100

9 00010

10 10010

11 01010

12 11010

13 00110

14 10110

15 01110

16 11110

17 00001

18 10001

19 01001

20 11001

21 00101

22 10101

23 01101

24 11101

25 00011

26 10011

27 01011

28 11011

29 00111

30 10111

31 01111

32 11111

Tone / supply voltage
1 / 18 VDC 1 / 28 VDC 2 / 18 VDC 2 / 28 VDC 3 / 18 VDC 3 / 28 VDC 4 / 18 VDC 4 / 28 VDC 5 / 18 VDC 5 / 28 VDC 6 / 18 VDC 6 / 28 VDC 7 / 18 VDC

SPP-110

SATEL

Acoustic signaling

Frequency Hz

Description

2400-2850

7 Hz

2400-2850

1 Hz

500-1200

3 s sound, 0.5 s silence, repeated

1200-500

1 Hz

2400-2850

2 Hz (250 ms ­ 250 ms)

970

0.5 Hz (1 s)

800 & 970

1 Hz (500 ms ­ 500 ms)

2850

0.5 Hz (1 s)

970

0.8 Hz (250 ms / 1 s)

970

Continuous

554 & 440

100 ms ­ 400 ms

660

3.3 Hz (150 ms)

660

0.28 Hz (1.8 s)

660

0.05 Hz (13 s / 6.5 Hz)

660

Continuous

554 & 440

0.5 Hz (1 s)

660

1 Hz (500 ms ­ 500 ms)

2850

4 Hz (150 ms ­ 100 ms)

800-970

50 Hz

2400-2850

50 Hz

970

3 x 500 ms sound, 1.5 s silence, repeated

800-970

3 x 500 ms sound, 1.5 s silence, repeated

970 & 800

3 x 500 ms sound, 1.5 s silence, repeated

2400

Continuous

990 & 650

2 Hz (250 ms ­ 250 ms) (Symphoni Tones)

510 & 610

2 Hz (250 ms ­ 250 ms) (Squashni Micro Tones)

300-1200

1 Hz

510 & 610

1 Hz (500 ms ­ 500 ms)

Table 1.

Angle-dependent [°] minimum sound level [dBA]

15°

45°

75°

105°

135°

165°

74.3

85.7

89.9

89.4

84.2

77.0

77.0

87.2

91.4

90.9

85.8

80.0

78.0

85.7

89.1

88.8

83.5

78.0

79.6

87.5

90.7

90.4

85.4

79.9

78.9

86.1

90.0

89.7

83.9

78.2

80.9

87.8

91.3

91.0

85.8

80.3

71.0

81.0

83.5

82.0

79.7

69.6

71.3

81.4

84.04

82.6

79.7

69.7

75.3

83.4

85.6

85.0

81.1

75.0

75.2

83.4

85.5

85.0

81.0

74.5

76.6

84.7

86.7

86.4

82.6

75.1

76.4

84.6

86.4

86.1

82.6

75.1

79.8

87.2

91.8

91.5

85.8

81.5

SATEL
Tone / supply voltage
7 / 28 VDC 8 / 18 VDC 8 / 28 VDC 9 / 18 VDC 9 / 28 VDC 10 / 18 VDC 10 / 28 VDC 11 / 18 VDC 11 / 28 VDC 12 / 18 VDC 12 / 28 VDC 13 / 18 VDC 13 / 28 VDC 14 / 18 VDC 14 / 28 VDC 15 / 18 VDC 15 / 28 VDC 16 / 18 VDC 16 / 28 VDC 17 / 18 VDC 17 / 28 VDC 18 / 18 VDC 18 / 28 VDC 19 / 18 VDC 19 / 28 VDC 20 / 18 VDC 20 / 28 VDC 21 / 18 VDC 21 / 28 VDC 22 / 18 VDC 22 / 28 VDC 23 / 18 VDC 23 / 28 VDC 24 / 18 VDC 24 / 28 VDC 25 / 18 VDC 25 / 28 VDC 26 / 18 VDC 26 / 28 VDC 27 / 18 VDC 27 / 28 VDC 28 / 18 VDC 28 / 28 VDC 29 / 18 VDC 29 / 28 VDC

SPP-110

5

Angle-dependent [°] minimum sound level [dBA]

15°

45°

75°

105°

135°

165°

80.9

88.6

92.8

92.6

87.3

82.9

78.6

86.5

90.5

90.3

84.6

80.7

80.2

88.3

92.1

91.8

86.5

82.6

77.0

81.0

86.9

86.1

80.2

75.8

77.0

81.3

87.0

86.2

80.1

75.7

73.2

86.3

90.6

90.3

84.9

76.6

74.2

87.2

91.6

91.3

85.9

77.6

74.6

86.5

90.7

90.3

85.0

77.2

77.3

87.8

91.9

91.5

86.5

80.2

73.4

84.1

86.9

88.4

85.9

73.8

77.5

87.8

90.5

91.9

89.4

76.6

72.7

85.7

90.0

89.7

84.1

75.9

73.9

86.7

91.1

90.9

85.3

77.2

73.1

86.2

90.5

90.2

84.8

76.5

73.4

86.2

90.8

90.3

84.8

76.5

75.9

83.6

86.9

86.4

80.1

77.6

77.5

84.8

88.4

87.9

81.0

79.3

75.9

84.9

87.4

87.0

81.7

74.8

77.4

86.3

89.0

88.6

83.0

76.3

76.8

86.0

88.5

88.2

83.0

75.8

78.6

87.4

90.2

89.7

84.3

77.4

77.2

86.1

88.6

88.2

82.9

76.0

78.7

87.4

90.3

89.9

84.3

77.5

77.0

85.9

88.4

88.2

83.0

75.8

78.7

87.4

90.2

89.8

84.3

77.4

76.0

84.1

87.4

87.0

80.2

77.9

77.5

85.4

88.6

88.3

81.5

79.5

76.9

85.9

88.4

88.1

82.7

75.7

78.5

87.3

90.0

89.5

84.1

77.2

74.0

84.0

86.0

85.6

82.8

73.0

74.8

84.6

86.5

85.6

83.4

73.5

77.4

85.4

88.5

88.0

83.1

77.5

79.4

87.3

90.4

90.0

85.0

79.5

75.6

83.3

85.4

84.9

80.6

74.4

75.4

83.4

85.6

84.7

80.3

74.4

73.3

86.5

90.8

90.5

85.1

76.6

74.6

87.6

91.9

91.5

86.1

77.6

78.0

85.8

89.7

89.3

83.4

77.6

80.0

87.1

91.2

90.7

84.8

79.2

74.7

86.0

90.3

90.0

84.4

77.3

77.4

87.5

91.5

91.3

86.1

80.0

75.4

79.6

85.6

87.0

80.9

76.3

75.5

79.7

85.8

87.1

80.9

76.3

78.9

88.2

91.1

90.7

85.2

77.6

79.9

89.2

91.9

91.7

86.0

78.4

6

SPP-110

SATEL

Tone / supply voltage
30 / 18 VDC 30 / 28 VDC 31 / 18 VDC 31 / 28 VDC 32 / 18 VDC 32 / 28 VDC

Angle-dependent [°] minimum sound level [dBA]

15°

45°

75°

105°

135°

165°

76.4

84.9

87.6

87.3

81.8

76.1

77.9

86.3

89.0

88.8

83.1

77.7

77.8

86.0

89.8

89.5

83.9

79.4

78.4

86.6

90.4

90.1

84.6

80.1

76.4

85.1

87.6

87.4

81.9

76.2

77.9

86.5

89.2

89.0

83.0

77.8

Table 2.

2.1.2 Volume setting
Use the switch 6 (marked as V on the electronics board) to change the volume of the following tones: 4, 5, 6, 9, 12, 14, 22 and 28. The switch in ON position ­ maximum volume (recommended). The switch in OFF position ­ lower volume. For other tones, it is recommended to set the switch to OFF position.

3. Maintenance
The fire alarm system elements require regular maintenance. The periodic checks of the SPP-110 sounder should be carried out at least every 6 months. In spaces where working conditions are difficult (e.g. dust, aggressive environment that may cause corrosion, etc.), the periodic checks should be carried out more often. As part of maintenance, start a test in the control panel and make sure the acoustic signaling is working. Please go to the fire alarm control panel manuals to find out how to start the test.
4. Specifications
Supply voltage …………………………………………………………………………………………. 18…28 VDC Alarm current consumption ………………………………………………………………………………….15 mA Operating temperature range…………………………………………………………………….-10°C…+55°C Maximum humidity ………………………………………………………………………………………………..95% Protection rating ………………………………………………………………………………………………… IP21C Operating environment type………………………………………………………………………………………. A

SATEL

SPP-110

7

Dimensions ……………………………………………………………………………………..108 x 108 x 87 mm Weight………………………………………………………………………………………………………………. 225 g

8

SPP-110

SATEL

The SPP-110 fire alarm sounder conforms to the essential requirements of the EU Regulations and Directives:
CPR 305/2011 Regulation of the European Parliament and of the Council of 9 March 2011 laying down harmonized conditions for the marketing of construction products and repealing the Council Directive 89/106/EEC on construction products;
EMC 2014/30/UE Electromagnetic Compatibility Directive;
LVD 2014/35/EU Low Voltage Directive.
The CNBOP-PIB Certification Body in Józefów issued the Certificate of Constancy of Performance 1438-CPR-0880 for the construction product SPP-110 fire alarm sounder, confirming its compliance with the requirements of EN 54-3:2003+A1:2002+A2:2006.
The Certificate and the Declaration of Performance can be downloaded from the www.satel.pl website.
The SPP-110 fire alarm sounder has been granted the Certificate of Admittance No 4833/2023 by the CNBOP-PIB in Józefów. The Certificate of Admittance can be downloaded from the www.satel.pl website.

23
SATEL Sp. z o.o. · ul. Budowlanych 66 · 80-298 Gdask · POLAND 1438
1438-CPR-0880 DOP/CPR/0880 EN 54 3:2003+A1:2002+A2:2006
Fire safety. SPP-110 fire alarm sounder (type A).
Declaration of Performance DOP/CPR/0880 Application ­ fire safety. Technical specifications ­ please refer to this manual.

References

Read User Manual Online (PDF format)