ADTRAn GPON TA352 Exterior Wall Mount ONT Instruction Manual

June 6, 2024
ADTRAN

GPON TA352 Exterior Wall Mount ONT
Instruction Manual
Total Access
GPON TA352/TA374
Exterior Wall Mount ONT
May 2021 61287802F1C-13A

DESCRIPTION

This Quick Start provides instructions for the installation of the GPON TA352/TA374 Optical Network Termination (ONT) units (P/N: 1287802F1C, 1287803F1C). The GPON TA352 4th Gen ONT has two POTS ports and two Gigabit Ethernet ports; the GPON TA374 2nd Gen ONT has four POTS ports and four Gigabit Ethernet ports.
The ONTs are enclosed in a weather-hardened Network Interface Device (NID) which mounts to the exterior of a building. The figure below illustrates the TA374 ONT in the context of the NID with the access door of the NID removed.

 The ONT is a Class 1 Laser Product.

ONT Part Number
TA 352 4th Gen Exterior Wall Mount Outdoor ONT 1287802F1C
TA 374 2nd Gen Exterior Wall Mount Outdoor ONT 1287803F1C

INSTALLATION

This section explains NID installation and all cable routing.
After unpacking the ONT, inspect it for damage. If damage is noted, file a claim with the carrier and then contact ADTRAN. For more information, refer to the warranty.

WARNING!

  • Read all warnings and cautions before installing or servicing this equipment.
  • Refer to the national, state, and local electrical codes for the requirements for power, grounding, wiring, and installation methods.
  • The protective earth (PE) ground screw of this device must be properly tightened to the grounding post of the Network Interface Device (NID).
  • The PE terminal of the NID must be properly grounded utilizing a 6 AWG (13.3 mm²) ground wire.
  • This equipment must be serviced by authorized service personnel only. All repair procedures are detailed to allow sub-assembly repairs ONLY.
  • Authorized service personnel should not attempt component-level repairs or circuit modifications to the printed circuit board. Improper repairs can create a safety hazard.

CAUTION!
The buried fiber drop cable to the subscriber’s premise used in this application must be a UL Listed non-metallic armored cable containing no other electrically conductive materials.
Required Tools and Supplies
In addition to standard technician tools, the following tools are required for this installation:

  • Carpenter’s level
  • 3/32 inch screwdriver for connecting ONT power
  • 5/32 inch hex tamper proof bit
  • Two #10 screws (Max. Head Diameter 0.385″) and appropriate wall anchors for mounting the NID
  • RJ-11 and RJ-45 crimpers
  • A telephony/data communication test set
  • Assorted tie-wraps for securing cabling and wiring
  • Up to 4 RJ-45 and RJ-11 plugs
  • For fiber-optic connections, you must have the following tools:
  • PON power meter with wavelength filtering
  • Fiberscope or video scope
  • Fiber optics Fusion splicing tools
  • Fiber connector cleaning tool
  • SC/APC fiber connector

Included with the GPON TA352/TA374 packaging are 2/4 Two-screw Terminal Bridges (2 for the TA352 and 4 for the TA374), an SC/APC fiber jumper, and a 7-position power and alarm connector. For data, the connection to the ONT is through the RJ-45 Ethernet connectors. For POTS, the connection is made through the 2/4 Two-screw Terminal Bridges.

Installation Steps

To install the ONT, complete the following steps:

  • “Mount the NID Enclosure”
  • “Ground the NID”
  • “Install the ONT”
  • “Route the Fiber Connection”
  • “Connect Power/Alarm”
  • “Install a Local Power Source”
  • “Install the UPS”
  • “Connect Subscriber Services”
  • “Connect Ethernet to the ONT”

NID Port Identification
The NID has four input ports for service entry. Each port is equipped with a grommet to provide protection from the elements. Each port is identified in Figure 2.

Figure 2. NID Port Identification

Mount the NID Enclosure
WARNING!
This equipment must be connected to known, reliable earth ground at all times during installation and service. This product is intended for installation only in UL Listed
enclosure (QVGV) suitable for outdoor use  CORNING ® CABLE SYSTEMS Inc., Model FNI-NG1-U1010.
This equipment must be serviced by authorized service personnel only.
Complete the following steps to mount the enclosure:

  1. Choose a vertical surface near an approved ground, but away from downspouts, permanent water sprinklers, or other water sources. The subscriber should have easy access to testing.

  2. Refer to Figure 3 and use the top and bottom Mounting Holes as a template to mark fastener locations. Use a level to ensure the unit is level to prevent warping.
    Figure 3. Mounting Hole Location

  3. Pre-drill the marked locations and install fasteners or anchors appropriate to the mounting surface (each anchor rated to 15 lbs. minimum).

  4. Mount the NID to the side of the subscriber’s premise.

Ground the NID
Install the ground connection by completing the following steps (refer to
Figure 4 for ground cable routing):
CAUTION!
Do not use a knife to cut the opening in the rubber grommets. This can result in an excessively large hole and compromise the integrity of the unit and allow moisture into the unit.

  1. Refer to Figure 4 and insert the ground wire through the rubber grommet.

  2. Remove 1 inch of the insulation jacket from a 6 AWG minimum copper ground wire.
    Figure 4. Inserting the Ground Wire

  3. Loosen the set-screws on the ground bar.

  4. Insert the ground wire in the ground bar and tighten the set screw.

  5. Route the ground wire 12 inches below the finished grade by the shortest and most direct route to the AC power ground system to connect to the ground. Ensure the wire is free of any sharp bends.

  6. Attach the ground wire to the side of the subscriber’s premises with stainless steel half-moon clamps or tie-wrap the ground wire to the riser conduit of the Buried Fiber drop.

  7. Clean the Multi Grounded Neutral (MGN) connector with emery cloth to ensure a stable connection.

  8. Attach the ground wire from the NID to the MGN connector with the appropriate UL-approved ground clamp/fitting.

  9. Coat the connection with metal corrosion preventative.

  10. Attach a Warning Ground Tag to the grounding connection.

CAUTION!
Align the captive screw on the bottom of the ONT with the screw hole on the Ground Bar and tighten (refer to Figure 12) to ensure grounding for the ONT. This should be the last step before closing the NID.
Install the ONT
To install the ONT in the NID Housing, align the hinges on the ONT with the mounting points on the NID Housing and snap the two together (refer to Figure 5).
NOTE
Figure 5 shows the TA374 ONT which has 4 two-screw terminal bridges (POTS1 to POTS4, only 2 shown in Figure 12) and 4 Ethernet connections (ETH1 to ETH4). The TA352 has two POTS ports (POTS1, POTS2) and two Gigabit Ethernet ports (ETH 1, ETH 2).

Figure 5. ONT
Route the Fiber Connection
To route the fiber connection, complete one of the following options:

  • OptiTap® NID (P/N: 1187771G1)”
  • Fiber Splice SC/APC Bulkhead NID (P/N: 1187770G1)”

NOTE
Clean all optical surfaces before connecting cables.
OptiTap® NID (P/N: 1187771G1)
To install the fiber connection using the Optical Connector, refer to Figure 6, and complete the following steps.
CAUTION!
Ensure that the fiber cable entering the unit is UL Listed Optical Fiber Cable and contains no metallic members or other electrically conductive materials.=

Figure 6. Optical Connector

  1. Route the incoming fiber cable through the port identified in Figure2.
  2. Connect the optical connector.
  3. Connect a fiber jumper from the top of the optical connector to the bottom of the SC/APC connector located at the bottom edge of the ONT.
  4. Route the fiber jumper so that when the ONT is closed, the fiber is not pinched.

Fiber Splice SC/APC Bulkhead NID (P/N: 1187770G1)
To install the fiber connection using the bulkhead connector, complete the following steps:
1. Route the incoming fiber cable through the port identified in Figure7.
CAUTION!
If the fiber cable has a metallic trace wire, do not bring the trace wire inside the NID housing. It is recommended to cut off the trace wire at least 6 inches from the NID  housing and insulate it, or cut off the trace wire and buried it underground.

Figure 7. SC/APC Bulkhead Connector
2. Route the fiber in the fiber tray and terminate it at the bulkhead connector.
3. Connect a fiber jumper from the bulkhead connector to the SC/APC connector at the bottom of the ONT (refer to Figure 8).

Figure 8. Fiber jumper to the ONT
4. Route the fiber jumper so that when the ONT is closed, the fiber is not pinched.
WARNING!
Before making any power connections to this equipment, verify the power is off (fuse removed/breaker tripped). This equipment should only be operated from the type of certified/listed power supply supplied by the service provider with the equipment. The ONT is supplied with a 7-pin Power/Alarm Connector. Refer to the following steps and figures 9 to 11 to connect Power/Alarms to the ONT.
1. Remove the Power/Alarm Connector (shown in Figure 9) from the accessory bag.

Figure 9. Power/Alarm Connector
2. Route the Power/Alarm wire through the port as shown in Figure 10.

Figure 10. Power/Alarm Connection and Routing
3. Terminate the 2 power leads (Pins 6 and 7), and the five Uninterruptible Power Supply (UPS) leads by stripping away .125-inch of insulation from the wires and fastening them with the individual set screws (see the pinout table).
4. Connect the Power/Alarm connector to the bottom of the ONT (refeto Figure 9).
5. Tie wrap and route these wires as shown in Figure 11 to prevent the connector from coming loose when the ONT is closed. Figure 11. Power/Alarm Connector Installed
The following table provides a pinout of the Power/Alarm connector.

PIN Description
1 Low Battery
2 Battery Missing
3 Replace Battery
4 On Battery
5 Signal Return
6 12 V Return
7 +12 VDC

Install a Local Power Source

WARNING!
The ONT must be powered by a UL Listed Power Supply suitable for the application (rated 12 VDC, 1.25 A minimum) with an LPS output. Installation of the Local Power Source will be dictated by on-site conditions and local telephone company practices.
CAUTION!
To reduce the risk of fire, use a minimum no. 26 AWG telecommunications line cord.
Install the UPS
Installation of the Uninterruptible Power Source (UPS) will be dictated by on- site conditions and local telephone company practices. Refer to the installation material that is provided with the UPS.
CAUTION!
After the ground wire, fiber jumper, and power leads have been connected, close the ONT and secure it by tightening the inner security screw.
Ethernet, power, and POTS cables and attached equipment are intended for use within the same building with equipotential bonding and are not intended to be placed in separate buildings or structures. Failure to deploy as described could result in permanent damage from lightning or other electrical events and void the warranty.
If it is necessary to connect the Ethernet ports to remote outdoor equipment or between structures then add an appropriate protection device per the following: ADTRAN’s Ethernet Port protection Device (EPPD) (P/N  1700502G1) should be connected between the unit and the outside plant cable. Use of any Ethernet protector other than ADTRAN’s for this purpose will void the user’s warranty.
NOTE
Installation of this product must comply with the National Electric Code (NEC). Final acceptance of this Listed equipment installation will ultimately be up to the local Authority Having Jurisdiction (AHJ). The ONT is to be installed by qualified service personnel only.
Connect Subscriber Services
For both POTS and Ethernet connections, refer to Figure 12.
Connect POTS
To terminate the POTS lines, complete the following steps:
1. Route the subscriber POTS wires through the port (refer to Figure 12).
NOTE
Figure 12 shows the TA374 ONT which has 4 two-screw terminal bridges (POTS1 to POTS4, only 2 shown in Figure 12) and 4 Ethernet connections (ETH1 to ETH4). The TA352 has two POTS ports (POTS1, POTS2) and two Gigabit-Ethernet ports (ETH 1, ETH 2).

Figure 12. Two Post Bridge and Installation Connections
2. Trim each wire to length.
3. Connect the tip and ring wires to the terminal bridges.
4. Insert the RJ-11 connectors from the terminal bridges into the appropriate POTS Port.
Connect Ethernet to the ONT

  1. Route the Subscriber Ethernet cable(s) through the same cable entry as the POTS cables.
  2. Install RJ-45 connectors onto the Ethernet cable(s).
  3. Insert into the appropriate ETH 1–4 socket.
  4. Tie wrap both the POTS and Ethernet cables to the NID housing near the cable entry point.

LED STATUS
The LED table below provides the LED status for the ONT.

Label Status Indication
PWR Off
Green No power

No failure
GPON| Off
Green
Green Flashing| No power or not provisioned
Link stable
Linking in process
ETH 1–4
(YELLOW)| Yellow
Off| 100 Mbps speed
10 Mbps speed
ETH 1–4
(GREEN)| Green
Green Flashing
Off| Valid link detected
Link activity detected
No link established
POTS 1–4| Off
Green
Green Flashing| Administratively shut down
Off-hook
Ringing

REGISTRATION ID
There are two instances where the OLT will register the ONT:
■ Serial Number Activation (performed by the OLT when the ONT is “Discovered”)
■ Registration ID using a lineman’s handset (see below)

Set Registration ID Activation using Lineman’s Handset
To set the Registration ID using a DTMF Keypad on a standard lineman’s handset, complete the following steps:
NOTE
The ONT does not need to be connected to the OLT during the Registration ID process.
Only POTS port 1 can be used for Registration ID configuration.
1. Perform an initial power-up on a new ONT.
NOTE
At the start-up of the ONT, a 10-second Registration ID the configuration window is provided.
2. Wait for the indication that the Registration ID configuration is available.
The GPON LED will be flashing green on a 200-millisecond interval when Registration ID configuration is available.
3. Go off-hook and observe that dial tone is heard.
NOTE
Once a dial tone is heard by going off-hook during the Registration ID window, you have 10 seconds to enter the initial digits 00. Once 00 is entered, you have 300 seconds to complete the Registration ID process.
4. After a dial tone is heard, enter 001234XXXXXXXXXXXXXXXXXXXX, where XXXXXXXXXX is the Registration ID for this site.
NOTE
Only digits 0-9 are supported.
5. If entered correctly, a confirmation tone is played and the number is displayed on the phone’s caller-id display with the string “ACCEPTED”.
6. If programming is successful, the ONT plays a stutter dial tone and flashes the GPON LED green for approximately 10 seconds with a cadence of 300 milliseconds on/off before it continues its startup/ ranging process.
** NOTE
If a failure occurs, the ONT plays reorder tone and displays
Invalid on the caller-id display. If the pattern is entered incorrectly, the caller id displays Re-enter* if the
the first ID does not match the second.
Entering an invalid Registration ID, such as one with less than 10 digits or non-matching values, results in a reorder tone and you have the same 10-second window to restart step 3 to allow you to re-enter codes that were entered incorrectly.

SPECIFICATIONS

  • Electrical
    ■ Input Power Connection: UPS provided through 7-pin alarm connector
    ■ Voltage Range: 12 VDC nominal
    ♦ Minimum Voltage: 10 V
    ♦ Maximum Voltage: 16 V
    ■ Power Consumption: Less than 15 W

  • Optical
    ■ TX min power: 0.5 dBm
    ■ TX max power: 5.0 dBm
    ■ RSSI max sensitivity: –27.0 dBm
    ■ RX overload: –8.0 dBm
    ■ TX wavelength: 1310 nm typical
    ■ RX wavelength: 1490 nm typical

  • Physical
    ■ Height: 9.05 in. (23.0 cm)
    ■ Width: 8.66 in. (22.0 cm)
    ■ Depth: 1.38 in. (3.5 cm)
    ■ Weight: 3.5 lbs. (1.6 kg NID and ONT combined)

  • Environmental
    ■ Protected Equipment Environment (Outside)
    ♦ Operational Temperature Range: –40°C to +65°C ambient with mechanical enclosure
    ♦ Storage Temperature Range: –40°C to +85°C
    ♦ Relative Humidity: 95% (non-condensing)

MAINTENANCE

The ONT does not require routine hardware maintenance for normal operation. ADTRAN does not recommend that repairs be attempted in the field. Repair services may be obtained by returning the defective unit to ADTRAN. Refer to the warranty for further information. Field support for the software is provided through upgrade facilities.

SAFETY AND REGULATORY

Refer to the Safety and Regulatory Notice for this product (P/N: 61287802F1C-17) for detailed safety and regulatory information.
Documentation for ADTRAN Network Solutions products is available for viewing and download directly from the ADTRAN Support Community website.
Go to: https://supportforums.adtran.com/welcome
Registration is required.
ADTRAN offers training courses on our products, including customized training and courses taught at our facilities or at customer sites.
For inquiries, go to: http://adtran.com/training
The following online documents and resources provide additional information for this product:
ADTRAN Pluggable Optics Compatibility Matrix (online tool, go to: http://www.adtran.com/pluggableoptics)
GPON 352/374 Exterior Wall Mount ONT Compliance Notice
Warranty: ADTRAN will replace or repair this product within the warranty period if it does not meet its published specifications or fails while in service. Warranty information can be found online at www.adtran.com/warranty.
Trademarks: Brand names and product names included in this document are trademarks, registered trademarks, or trade names of their respective holders.
Copyright © 2021 ADTRAN, Inc. All Rights Reserved.

CAUTION!
SUBJECT TO ELECTROSTATIC DAMAGE OR DECREASE IN RELIABILITY HANDLING PRECAUTIONS REQUIRED
ADTRAN CUSTOMER CARE:
From within the U.S. 1.888.423.8726
From outside the U.S. +1 256.963.8716
PRICING AND AVAILABILITY 1.800.827.0807

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

ADTRAN User Manuals

Related Manuals