TRANE TEMP-SVX003-EN Rental Services Cooling Towers Instruction Manual

September 21, 2024
Trane

TEMP-SVX003-EN Rental Services Cooling Towers

“`html

Specifications

  • Product: Trane Rental Services Cooling Towers
  • Model: TEMP-SVX003A-EN
  • Usage: Heating, ventilating, and air-conditioning
    equipment

Product Information

The Trane Rental Services Cooling Towers are designed for
efficient cooling in various HVAC applications. It is essential to
follow the safety guidelines and warnings provided in the user
manual to ensure safe operation and maintenance of the
equipment.

Installation

Only qualified personnel should install the Trane Rental
Services Cooling Towers. Improper installation can result in
serious injury or death. Follow all installation instructions
carefully to ensure proper setup.

Operation

Prior to operating the cooling towers, read the manual
thoroughly to understand the operational procedures. Ensure that
all safety precautions are adhered to during operation to prevent
accidents.

Maintenance

Regular maintenance is crucial for the optimal performance of
the cooling towers. Follow the maintenance schedule outlined in the
user manual to keep the equipment in good working condition.

Product Usage Instructions

  1. Step 1: Installation

Install the cooling towers following the guidelines provided in
the manual. Make sure all connections are secure and the unit is
properly mounted.

  1. Step 2: Operation

Turn on the cooling towers according to the specified
procedures. Monitor the performance indicators to ensure smooth
operation.

  1. Step 3: Maintenance

Regularly inspect and clean the cooling towers as per the
maintenance schedule. Replace any worn-out parts promptly to
prevent breakdowns.

FAQ

Q: Who should install the Trane Rental Services Cooling

Towers?

A: Only qualified personnel should install and service the
equipment to ensure safety and proper functioning.

Q: What should I do if I encounter a potentially hazardous

situation while using the cooling towers?

A: If you encounter any hazardous situation, stop operation
immediately and refer to the safety guidelines in the manual.

“`

Installation, Operation, and Maintenance
Trane Rental Services
Cooling Towers

SAFETY WARNING
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air- conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment.

June 2024

TEMP-SVX003A-EN

Introduction

Read this manual thoroughly before operating or servicing this unit.
Warnings, Cautions, and Notices
Safety advisories appear throughout this manual as required. Your personal safety and the proper operation of this machine depend upon the strict observance of these precautions.

The three types of advisories are defined as follows:

WARNING

Indicates a potentially hazardous situation which, if not avoided, could

result in death or serious injury.

CAUTIONs

Indicates a potentially hazardous situation which, if not avoided, could

result in minor or moderate injury. It could

also be used to alert against unsafe

practices.

NOTICE

Indicates a situation that could result in equipment or property-damage only accidents.

Important Environmental Concerns
Scientific research has shown that certain man-made chemicals can affect the earth’s naturally occurring stratospheric ozone layer when released to the atmosphere. In particular, several of the identified chemicals that may affect the ozone layer are refrigerants that contain Chlorine, Fluorine and Carbon (CFCs) and those containing Hydrogen, Chlorine, Fluorine and Carbon (HCFCs). Not all refrigerants containing these compounds have the same potential impact to the environment. Trane advocates the responsible handling of all refrigerants.
Important Responsible Refrigerant Practices
Trane believes that responsible refrigerant practices are important to the environment, our customers, and the air conditioning industry. All technicians who handle refrigerants must be certified according to local rules. For the USA, the Federal Clean Air Act (Section 608) sets forth the requirements for handling, reclaiming, recovering and recycling of certain refrigerants and the equipment that is used in these service procedures. In addition, some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants. Know the applicable laws and follow them.

WARNING
Proper Field Wiring and Grounding Required!
Failure to follow code could result in death or serious injury. All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state/national electrical codes.
WARNING
Personal Protective Equipment (PPE) Required!
Failure to wear proper PPE for the job being undertaken could result in death or serious injury. Technicians, in order to protect themselves from potential electrical, mechanical, and chemical hazards, MUST follow precautions in this manual and on the tags, stickers, and labels, as well as the instructions below:
· Before installing/servicing this unit, technicians MUST put on all PPE required for the work being undertaken (Examples; cut resistant gloves/sleeves, butyl gloves, safety glasses, hard hat/bump cap, fall protection, electrical PPE and arc flash clothing). ALWAYS refer to appropriate Safety Data Sheets (SDS) and OSHA guidelines for proper PPE.
· When working with or around hazardous chemicals, ALWAYS refer to the appropriate SDS and OSHA/GHS (Global Harmonized System of Classification and Labeling of Chemicals) guidelines for information on allowable personal exposure levels, proper respiratory protection and handling instructions.
· If there is a risk of energized electrical contact, arc, or flash, technicians MUST put on all PPE in accordance with OSHA, NFPA 70E, or other country-specific requirements for arc flash protection, PRIOR to servicing the unit. NEVER PERFORM ANY SWITCHING, DISCONNECTING, OR VOLTAGE TESTING WITHOUT PROPER ELECTRICAL PPE AND ARC FLASH CLOTHING. ENSURE ELECTRICAL METERS AND EQUIPMENT ARE PROPERLY RATED FOR INTENDED VOLTAGE.

©2024 Trane

TEMP-SVX003A-EN

WARNING Follow EHS Policies!
Failure to follow instructions below could result in death or serious injury.
· All Trane personnel must follow the company’s Environmental, Health and Safety (EHS) policies when performing work such as hot work, electrical, fall protection, lockout/tagout, refrigerant handling, etc. Where local regulations are more stringent than these policies, those regulations supersede these policies.
· Non-Trane personnel should always follow local regulations.
Copyright
This document and the information in it are the property of Trane, and may not be used or reproduced in whole or in part without written permission. Trane reserves the right to revise this publication at any time, and to make changes to its content without obligation to notify any person of such revision or change.
Trademarks
All trademarks referenced in this document are the trademarks of their respective owners.
Revision History
· Document renamed to align with numbering standards.
· Minor updates in General Information and Unit Dimensions and Weights.

Introduction

TEMP-SVX003A-EN

3

Table of Contents
General Information . . . . . . . . . . . . . . . . . . . . . . . 5 Cooling Towers Overview . . . . . . . . . . . . . . . . 5
Unit Dimensions and Weight . . . . . . . . . . . . . . . 7 Lifting, Mounting, and Transportation . . . . . . . 7
270 Tons . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 500 Tons . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 1000 Tons . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Rigging Guidelines . . . . . . . . . . . . . . . . . . . . 8 270 Tons . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 500 Tons . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 1000 Tons . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Dimensional Drawings . . . . . . . . . . . . . . . . . . 10 270 Tons . . . . . . . . . . . . . . . . . . . . . . . . . . 10 500 Tons . . . . . . . . . . . . . . . . . . . . . . . . . . 11 1000 Tons . . . . . . . . . . . . . . . . . . . . . . . . . 12
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . 13 270 Tons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 500 Tons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 1000 Tons . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Cooling Tower Piping Kit and Water Connections
16 270 Tons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Style Towers . . . . . . . . . . . . . . . . . . . . . . . 16 500 Tons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Piping Kit Assembly . . . . . . . . . . . . . . . . . . 17 1000 Tons . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Piping Kit Assembly . . . . . . . . . . . . . . . . . . 19
Start-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 270 Ton Tower (CSCT0270F0) . . . . . . . . . . 22 500 Ton Tower (CSCT0500F1) . . . . . . . . . . 23 1000 Ton Tower (RSCT1000F2) . . . . . . . . . 25
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 Water Treatment Recommendations . . . . . . 27 Control of Biological Contamination . . . . . . . 27 Air Contamination . . . . . . . . . . . . . . . . . . . . . 27
Cooling Tower . . . . . . . . . . . . . . . . . . . . . . . . . . 29 270 Tons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
4

Dimensional Drawings . . . . . . . . . . . . . . . . .30 500 Tons . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . .31 Dimensional Drawings . . . . . . . . . . . . . . . . .32 1000 Tons . . . . . . . . . . . . . . . . . . . . . . . . . . . .33 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . .33 Dimensional Drawings . . . . . . . . . . . . . . . . .34
TEMP-SVX003A-EN

General Information

WARNING
Live Electrical Components!
Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury. When it is necessary to work with live electrical components, have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks.

WARNING
Proper Field Wiring and Grounding Required!
Failure to follow code could result in death or serious injury. All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state/national electrical codes.

Cooling towers in the rental fleet include as in below Table 1.
Towers are nominally rated for flow and tonnage at the industrial standard Cooling Technology Institute (CTI) conditions with entering water temperature (EWT) of 95°F, leaving water temperature (LWT) of 85°F, entering wet bulb temperature (EWB) of 78°F and three gallons per minute per ton. For other flows and temperature conditions, contact Trane Rental Services.
The ambient operating temperature for the towers is 35ºF to 140ºF. All are equipped with basin heaters to provide low temperature protection when properly installed. For ambient temperatures below 40ºF, the basin heaters must be used.
Pumps, flexible water hose, transformers, and other accessories are available upon request.

Cooling Towers Overview

Note: All information contained in this document is for reference only. CSCT0270F0XX – 270-ton nominal cooling tower (810 GPM) CSCT0500F1XX – 500-ton nominal cooling tower (1500 GPM) RSCT1000F2XX – 1000-ton nominal cooling tower (3000 GPM) Note: Where XX represents the unique inventory number.
Table 1. Cooling tower general data

Manufacturer Inlet Water Connection Qty/Size/Type Outlet Water Connection Qty/Size/Type Make-Up Water Connection Qty/Size/Type Overflow Connection Qty/Size/Type Drain Connection Qty/Size/Type Nominal Flow Rate Number of Cells Number of Fans/Cell Drive Type Capacity Control Max Make-Up Water Valve Pressure Make-up Water Control

CSCT0270F0 Baltimore Air Coil® (1) 6 in. Victaulic (1) 6 in. Victaulic
(1) 2 in. MPT (1) 3 in. FPT (1) 2 in. FPT
810 GPM 1 1
Belt Fan Cycling 20-50 PSI Mechanical Float Valve

Nominal Tons CSCT0500F1
Evapco® (2) 6 in. Victaulic (2) 10 in. Victaulic
(2) 2 in. MPT (2) 3 in. FPT (2) 3 in. FPT 1500 GPM
2 1 Belt Fan Cycling 20-50 PSI Mechanical Float Valve

RSCT1000F2 Reymsa®
(2) 8 in. Victaulic (2) 10 in. Victaulic
(2) 1.5 in. FPT (2) 2 in. FPT (2) 2 in. FPT 3000 GPM
2 8 Direct Variable Speed Fans 20-50 PSI Mechanical Float Valve

TEMP-SVX003A-EN

5

General Information
Table 1. Cooling tower general data (continued)

CSCT0270F0

Construction Type

All Metal

Operating Principle

Forced Draft, Counterflow

Fill Material

PVC

Max Fill Operating Temperature(a)

130°F

(a) Higher Operating Temperatures will cause permanent damage to fill.

Nominal Tons CSCT0500F1
All Metal Induced Draft, Counterflow
PVC 130°F

RSCT1000F2 Fiberglass
Induced Draft, Counterflow PVC 130°F

6

TEMP-SVX003A-EN

Unit Dimensions and Weights

Lifting, Mounting, and Transportation

270 Tons
· Modified for easy installation. · Designed to comply with transportation height requirements for industrial, flatbed trailers. · Equipped with forklift pocket and crane lifting eyes.

Table 2. Weights and dimensions – CSCT0270

Model Nominal Tons Length Width Height Shipping Weight (lbs) Operational Weight (lbs) Level Requirements (end to end)

CSCT0270F0 270 20 ft. 8 ft.
9 ft. 1 in. 6,500 10,700 1/8 in.

500 Tons

· Modified to meet transportation dimensional requirements. · Drop-deck trailer configuration required to comply with transportation height requirements. · Towers are mounted on dedicated 48-ft. dropdeck trailers. · The cooling tower can be removed from the trailer. Refer to the rigging guidelines section of this manual. All 500-ton towers
are equipped with forklift pockets.

Table 3. Weights and dimensions – CSCT0500

Model Nominal Tons Length Width Height Shipping Weight (lbs) Operational Weight (lbs) Level Requirements (end to end)
(a) Includes weight and dimension of trailer.

CSCT0500F1(a) 500 48 ft.
8 ft. 6 in. 13 ft. 6 in.
24,960 32,580 1/8 in.

1000 Tons

· Modified to meet transportation dimensional requirements. · Drop-deck trailer configuration required to comply with transportation height requirements. · Towers are mounted on dedicated 48-ft. drop-deck trailers. · Towers are permanently mounted to trailer and should not be removed.

Table 4. Weights and dimensions – RSCT1000

Nominal Tons Length Width

Model

RSCT1000F2(a) 1000
48 ft. 4 in. 8 ft. 6 in.

TEMP-SVX003A-EN

7

Unit Dimensions and Weights

Table 4. Weights and dimensions – RSCT1000 (continued)

Model Height Shipping Weight (lbs) Operational Weight (lbs) Level Requirements (end to end)
(a) Includes weight and dimension of trailer.

RSCT1000F2(a) 13 ft. 6 in. 27,600 52,280 1/8 in.

Rigging Guidelines

WARNING Heavy Objects!
Failure to follow instructions below could result in unit dropping which could result in death or serious injury, and equipment or property-only damage.
Ensure that all the lifting equipment used is properly rated for the weight of the unit being lifted. Each of the cables (chains or slings), hooks, and shackles used to lift the unit must be capable of supporting the entire weight of the unit. Lifting cables (chains or slings) may not be of the same length. Adjust as necessary for even unit lift.
· Drain, clean basin, and disconnect any piping and wiring before returning unit to trailer. · When tower is reloaded in the original position, reconnect turnbuckles (if equipped) and tighten to secure to trailer.
270 Tons
· If tower is removed from trailer, the foundation on which the tower will be operating from must support the operating weight of the tower.
· If tower remains on the trailer, operating weight will impact the landing gear and tires. Cribbing or weight distribution plates may be required.
· When tower is removed from trailer, mark the exact location of tower on trailer. Tower should be replaced in the same location with outlet water connections on the same side of the trailer. The trailer must be returned in the same condition in which it was delivered.
· Lifting eyes are located on each side of the bottom of the towers.
500 Tons
· If tower is removed from trailer, the foundation on which the tower will be operating from must support the operating weight of the tower.
· If tower remains on the trailer, operating weight will impact the landing gear and tires. Cribbing or weight distribution plates may be required.
· When tower is removed from trailer, mark the exact location of tower on trailer. Tower should be replaced in the same location with outlet water connections on the same side of the trailer. The trailer must be returned in the same condition in which it was delivered.
· Lifting plates are located on each side of the top of the towers. Fork pockets are located in the base of the tower. · The dual outlet towers should be positioned with 10-inch outlet connections on passenger side of trailer.

8

TEMP-SVX003A-EN

Figure 1. Tower rigging connections

Unit Dimensions and Weights

1000 Tons
Important: Cooling tower is permanently trailer mounted.

TEMP-SVX003A-EN

9

TEMP-SVX003A-EN

Note: Drawing does not show exact location of inlet piping.
10

8 ft.-9 1/4 in.

3 ft.-10 5/8 in.

11 ft.-11 5/8 in.

7 ft.-2 5/16 in. 6 in.

6 in. WATER OUTLET 6 1/8 in.
3 ft.-11 1/4 in. 8 ft.-1 in.

6 in. WATER INLET

ACCESS DOOR 2 in. MPT MAKE-UP 3 in. MPT OVERFLOW

8 ft.-6 5/8 in. 9 ft.-8 5/8 in. 10 ft.-4 7/8 in. 20 ft.

2 in. MPT DRAIN

2 5/8 in.

5 ft.-10 5/8 in. 9 ft. 1 in.

FAN MOTOR

Unit Dimensions and Weights
Dimensional Drawings
270 Tons
Figure 2. CSCT0270F0

500 Tons
Figure 3. CSCT0500F1

TEMP-SVX003A-EN

NOTES:

1. (M)- FAN MOTOR LOCATION

2. MPT DENOTES PIPE THREAD

FPT DENOTES PIPE THREAD

BFW DENOTES BEVELED FOR WELDING

3. MAKE-UP WATER PRESSURE-20 psi MIN, 50 psi MAX

7′-10″ M

M

FACE 2

M ACCESS

ACCESS

DOOR

DOOR

53

WIRE RACK

CONTROL PANEL

2 10′-6″
73

94 FACE 2

1 3/8

INLET REINFORCEMENT
19 3/4

24′-2″ FACE 1
PLAN VIEW
HIGH PICK POINT

19 3/4

M

CORNER REINFORCEMENT
80 1/2 (2) 10 BFW/GVD OUTLETS

71 7/8

23 1/8 15 8 3/8
3 1/2

4 3/4

9 52 5/8

(2) 6 BFW/GVD
INLET

M 71 7/8

(2) 2 MPT MAKE-UP
(2) 3 FPT OVERFLOW (2) 3 FPT DRAIN (PLUGGED)
TIE DOWN BRACKET

(2) LIFTING SLOTS FOR FORK LIFT
24′-2″ FACE 1

9 52 5/8

4 3/4

Unit Dimensions and Weights

11

Unit Dimensions and Weights
1000 Tons
Figure 4. RSCT1000F2

12

PIPING SUPPORT

CUT A-A

11921

PIPING SUPPORT VICTAULIC

3241

9921
M1 RIGHT SIDE VIEW

ACCESS DOOR

M1

102

ACCESS DOOR

277

ACCESS DOOR

CUT B-B

CONTROL PANEL

PIPING SUPPORT

CONTROL PANEL SUPPORT
VICTAULIC

CBOANSTIRNOHLEPAATNEERL11921
VICTAULIC

3241

UNICON CONTROL PANEL

2121

9921

VICTAULIC

M2 RIGHT SIDE VIEW

ACCESS DOOR

M2

ACCESS DOOR

BASIN HEATER CONTROL PANE
UNICON CONTR PANEL

ACCESS DOOR

13 576

ACCESS DOOR

PLAN VIEW

CUT A-A

PRESSURE GAGE

277

ACCESS DOOR

CONTROL PANEL
9

PRESSURE GAGE

CUT B-B

CONTROL PANEL

11921

ACCESS DOOR

PIPING SUPPORT

ACCESS DOOR

ACCESS DOOR

PIPING SUPPORT

TRUCK BED (BY OTHERS)

TRUCK BED TIE DOWN

274

CUT A-A
16 576
SIDE VIEW

166

TRUCK BED TIE DOWN

2121

TRUCK BED TIE DOWN
108

CUT B-B
12

TEMP-SVX003A-EN

Electrical Data
270 Tons
Table 5. Electrical data – CSCT0270
Model Disconnect Type Wire Connection Type MCA MOP Fan Motor Qty – Size – Type Fan Motor Qty – RLA Basin Heater Qty – Size Basin Heater FLA Vibration Switch SCCR
Note: All towers are 460V, 3-phase, 60 Hz.
Figure 5. CT motor control panel end

CSCT0270F0* Circuit Breaker – 150 Amp Series 16 Cam-Type Only
75.8 A 150 A (1) 40 HP – TEFC (1) 52.0 A (1) 9 kW (1) 10.8 A Yes 5kAIC

TEMP-SVX003A-EN

13

Electrical Data
500 Tons
Table 6. Electrical data – CSCT0500
Model Disconnect Type Wire Connection Type MCA MOP Fan Motor Qty – Size – Type Fan Motor Qty – RLA Basin Heater Qty – Size Basin Heater FLA Vibration Switch SCCR
Note: All towers are 460V, 3-phase, 60 Hz.

Figure 6. CT control panel end

CSCT0500F1* Non-Fused Switch – 100 Amp
Series 16 Cam-Type Only 76.5 A 100 A
(2) 25 HP – TEFC (2) 34.0 A (2) 6 kW (2) 7.2 A Yes 5kAIC

14

TEMP-SVX003A-EN

1000 Tons
Table 7. Electrical data – RSCT1000
Model Disconnect Type Wire Connection Type MCA MOP Fan Motor Qty – Size – Type Fan Motor Qty – RLA Basin Heater Qty – Size Basin Heater FLA Vibration Switch SCCR
Note: All towers are 460V, 3-phase, 60 Hz.
Figure 7. 1000-ton CT control panel end

RSCT1000F2* Circuit Breaker – 300 Amp Series 16 Cam-Type Only
180.0 A 300 A (16) 5 HP – EC (16) 4.7 A (4) 8 kW (4) 9.63 A
No 65kAIC

Electrical Data

TEMP-SVX003A-EN

15

Cooling Tower Piping Kit and Water Connections

Note: TRS Orange Hose is not suction rated and cannot be used on the suction side of the cooling tower.
TRS provides piping kits to reduce the number of final connections at the tower to one inlet and one outlet connection per tower including suction rated hose on return side of tower. Water connection piping kits including parts, quantities, and installation order are listed below.
WARNING
Heavy Object!
Failure to follow instructions below could result in unit dropping which could result in death or serious injury, and equipment or property-only damage. Ensure that all the lifting equipment used is properly rated for the weight of the unit being lifted. Each of the cables (chains or slings), hooks, and shackles used to lift the unit must be capable of supporting the entire weight of the unit. Lifting cables (chains or slings) may not be of the same length. Adjust as necessary for even unit lift.
Figure 8. Cooling tower piping kit connection

· Trane supplied suction hose is greater than 150 pounds per section.
· Trane trailer mounted hose trays are greater than 1000 pounds per tray.
· Refer to CHS-SVX01*-EN for additional information on Victaulic Couplings
270 Tons

Table 8. Piping kit contents – CSCT0270F0

Qty

Description

3

DN150-6 – 6 in.107N QuickVic Coupling

2

6 in. x 5 ft. Suction Hose

Style Towers
· One (1) 6-in. inlet · One (1) 6-in. outlet grooved water connections

6 in. x 10 ft. Suction Hose

16

TEMP-SVX003A-EN

Cooling Tower Piping Kit and Water Connections

500 Tons

Table 9. Total piping kit contents – CSCT0500F1

Qty

Description

2

6 in. x 68 3/4 in. Sch. 80 PVC Pipe

2

6 in. x 48 in. Sch. 80 PVC Pipe

1

6 in. x 28 in. Sch. 80 PVC Pipe

1

6 in. x 9 1/4 in. Sch. 80 PVC Pipe

3

8 in. x 10 ft. Suction Hose

3

DN150-6 – 6 in. No 11 90° Elbow

3

DN250-150 – 10 in. x 6 in. No 50. Concentric Reducer

2

DN150-6 ­ 6 in. Series 761 Vic 300 MasterSeal Butterfly Valve with Gear Operator

13

DN150-6 – 6 in. 107N QuickVic Coupling

1

DN200-8 8 in. No. 20 Tee

2

DN200-8 – 8 in. No 11 45° Elbow

8

DN200-8 – 8 in. 107N QuickVic Coupling

3

DN250-200 – 10 in. x 8 in. No 50. Concentric Reducer

1

DN250-10 10 in. No. 20 Tee

5

DN250-10 – 10 in. 107N QuickVic Coupling

CSCT0500F1 style towers have inlet/outlet piping kits to tie 6-inch inlet and 10-inch outlet grooved water connections together. See Figure 9, p. 18.
Piping Kit Assembly
Do not tighten couplings until piping is fully assembled. Follow all Victaulic assembly instructions including, torque specifications for couplings and lubricant for all gaskets. For more information, refer to CHS-SVX01*-EN.
Tower Supply Side Instructions

Table 10. Supply side piping kit contents – CSCT0500F1

Qty

Description

2

6 in. x 68 3/4 in. Sch. 80 PVC Pipe

2

6 in. x 48 in. Sch. 80 PVC Pipe

1

6 in. x 28 in. Sch. 80 PVC Pipe

1

6 in. x 9 1/4 in. Sch. 80 PVC Pipe

3

DN150-6 – 6 in. No 11 90° Elbow

3

DN250-150 – 10 in. x 6 in. No 50. Concentric Reducer

2

DN150-6 ­ 6 in. Series 761 Vic 300 MasterSeal Butterfly Valve with Gear Operator

13

DN150-6 – 6 in. 107N QuickVic Coupling

1

DN250-10 10 in. No. 20 Tee

3

DN250-10 – 10 in. 107N QuickVic Coupling

1. At each tower inlet, attach DN150 ­ 6 inch 90° Elbow facing directly down using DN150 ­ 6 inch Victaulic Coupling.
2. Attach 6 inch x 68 ¾ inch Sch. 80 PVC Pipe to each supply elbow using DN150 ­ 6 inch Victaulic Coupling.
3. Attach DN150 ­ 6 inch Series 761 Butterfly Valve to each PVC Pipe using DN150 ­ 6 inch Victaulic Coupling.
4. Attach 6 inch x 9 ¼ inch Sch. 80 PVC Pipe to tower rear supply butterfly valve using DN150 ­ 6 inch Victaulic Coupling.
5. Support DN150 ­ 6 inch, 90° Elbow and attach to tower rear PVC Pipe facing the front of the tower, parallel with the trailer using DN150 ­ 6 inch Victaulic Coupling.
6. Attach DN250-150 – 10 inch x 6 inch No 50. Concentric Reducer to tower front butterfly valve using DN150 ­ 6 inch Victaulic Coupling.
7. Support DN250-10 10 inch No. 20 Tee and attach to 10 inch x 6 inch Concentric Reducer at the front tower supply connection using DN250 ­ 10 inch Victaulic Coupling.
Note: The top of the tee should connect with the tower front supply. See Figure 9, p. 18.
8. Attach DN250-150 ­ 10 inch x 6 inch No 50. Concentric Reducer to both sides of 10 inch Tee with DN250 ­ 10 inch Victaulic Couplings.
9. Support piping and connect both supply connections together using two 6 inch x 48 inch and one 6 inch x 28 inch Sch. 80 PVC Pipe from front to rear supply tower connections.
10. Tighten couplings.
Tower Return Side Instructions

Table 11. Return side piping kit contents – CSCT0500F1

Qty

Description

3

8 in. x 10 ft. Suction Hose

1

DN200-8 8 in. No. 20 Tee

2

DN200-8 – 8 in. No 11 45° Elbow

8

DN200-8 – 8 in. 107N QuickVic Coupling

3

DN250-200 – 10 in. x 8 in. No 50. Concentric Reducer

2

DN250-10 – 10 in. 107N QuickVic Coupling

1. At each tower outlet, attach DN250-200 ­ 10 inch x 8 inch No 50. Concentric Reducer using DN250 ­ 10 inch Victaulic Couplings.
2. At each tower outlet, attach one end of 8 inch x 10 foot Suction Hose using DN200 ­ 8 inch Victaulic Couplings. Hose weight may be greater than 150 pounds.

CAUTION
Heavy Object!
Lifting this object manually may cause minor to moderate injury. Follow local standards or requirements for lifting heavy objects.

TEMP-SVX003A-EN

17

Cooling Tower Piping Kit and Water Connections

3. Route each hose away from the tower outlets and towards each other in the middle of the trailer. See Figure 10, p. 18
4. At the opposite end of each 8 inch x 10 foot Suction Hose(s), attach DN200-8 – 8 inch No 11 45° Elbow using DN200 ­ 8 inch Victaulic Couplings.
5. Bring both 8 inch ­ 45° Elbows into DN200-8 8 inch No. 20 Tee and attach using DN200 ­ 8 inch Victaulic Couplings.
Figure 9. Cooling tower piping kit connection(s)

6. For the remaining connection on 8 inch Tee, attach 8 inch x 10 foot Suction Hose using DN200 ­ 8 inch Victaulic Couplings.
7. At the end of the 8 inch x 10 foot Suction Hose, attach DN250-200 – 10 inch x 8 inch No 50. Concentric Reducer using DN200 ­ 8 inch Victaulic Coupling.
8. Tighten couplings.

6 in. x 68 in. PVC

6 in. x 68 in. PVC

10 in. Tee w/10 in. x 6 in. Reducers
Blue Lines Represents (3) 8 in. x 10 ft. Suction Hoses
Figure 10. Cooling tower – assembled piping kit

8 in. Tee w/8 in. 45°s on either side from tower

18

TEMP-SVX003A-EN

Cooling Tower Piping Kit and Water Connections

1000 Tons

Table 12. Total spool kit contents – RSCT1000F2

Qty

Description

30

DN200-8 – 8 in. 107N QuickVic Coupling

2

8 in. Dia x 12 in. Long Sch. 80 PVC Pipe(s)

3

8 in. Dia x ~88.5 in. Long Sch. 80 PVC Pipe(s)

1

8 in. Dia x 21 in. Long Sch. 80 PVC Pipe(s)

1

8 in. Dia x 24 in. Long Sch. 80 PVC Pipe(s)

1

8 in. Dia x ~36.5 in. Long Sch. 80 PVC Pipe(s)

1

8 in. Dia x ~45.5 in. Long Sch. 80 PVC Pipe(s)

10

DN250-10 – 10 in.107N QuickVic Coupling

7

DN200-8 – 8 in. No 10 90° Elbow

2

DN200-8 – 8 in. No 11 45° Elbow

2

DN250-10 10 in. No. 20 Tee

2

DN200-8 – 8 in. No. 60 Cap

2

DN250-10 -10 in. No. 60 Cap

6

DN250-200 – 10 in. x 8 in. No 50. Concentric Reducer

2

DN200-8 – Series 761 Vic 300 MasterSeal Butterfly Valve with Lever Operator

4

8 in. x 8 ft.Suction Hose

1

10 in. x 8 ft. Suction Hose

RSCT1000F2 style towers have inlet/outlet piping kits to tie two 8 inch inlet and 10 inch outlet grooved water connections together. See Figure 11, p. 21.
Piping Kit Assembly
Do not tighten couplings until piping is fully assembled.
Follow all Victaulic assembly instructions including, torque specifications for couplings and lubricant for all gaskets. For more information refer to Trane Rental Services Temporary Cooling – Flexible Water Hose Installation, Operation, and Maintenance (CHS-SVX01*-EN).

CAUTION Heavy Object!
Lifting this object manually may cause minor to moderate injury. Follow local standards or requirements for lifting heavy objects.
Trailer mounted hose trays must be removed via mechanical lift due to weight greater than 1000 pounds.

Tower Supply Side Piping Assembly Instructions:

Table 13. Supply side spool kit contents – RSCT1000F2

Qty

Description

14

DN200-8 – 8 in. 107N QuickVic Coupling

3

8 in. Dia x ~88.5 in. Long Sch. 80 PVC Pipe(s)

1

8 in. Dia x ~36.5 in. Long Sch. 80 PVC Pipe(s)

1

8 in. Dia x ~45.5 in. Long Sch. 80 PVC Pipe(s)

2

DN250-10 – 10 in. 107N QuickVic Coupling

3

DN200-8 – 8 in. No 10 90° Elbow

1

DN250-10 10 in. No. 20 Tee

2

DN200-8 – 8 in. No. 60 Cap

2

DN250-200 – 10 in. x 8 in. No 50. Concentric Reducer

2

DN200-8 – Series 761 Vic 300 MasterSeal Butterfly Valve with Lever Operator

Note: Tower piping kit designed such that only one side (driver or passenger) of tower will be used.
1. Starting at the tower connection side that won’t be used, attach DN200-8 ­ 8 inch No. 60 Caps using DN200 ­ 8 inch Victaulic Couplings.
2. At each tower inlet, attach DN200-8 ­ 8 inch Series 761 Butterfly Valve using DN200 ­ 8 inch Victaulic Couplings.
Note: If connecting to passenger side of tower, Module 2 (front module) butterfly valve will need to be rotated 90° clockwise from the upright position in order to not interfere with electrical connections.
3. Attach DN200-8 ­ 8 inch No. 10, 90° Elbow to each butterfly valve using DN200 ­ 8 inch Victaulic Couplings. Elbows should face the ground and be perpendicular to tower supply piping.
4. Attach approximately 45.5 inch x 8 inch Sch. 80 PVC Pipe to module 2 (front module) elbow and approximately 36.5 inch x 8 inch Sch. 80 PVC Pipe to Module 1 (rear tower) using DN200 ­ 8 inch Victaulic Couplings.
5. Support DN200-8 ­ 8 inch No. 10, 90° Elbow and attach to Module 2 (front module) PVC Pipe facing towards the rear of the trailer, parallel with the trailer using DN200 ­ 8 inch Victaulic Coupling.
6. Attach two DN250-200 ­ 10 inch x 8 inch No 50. Concentric Reducer(s) to DN250-10 10 inch No. 20 Tee with one reducer on the top and one reducer on one side of the Tee DN250 ­ 10 inch Victaulic Coupling(s).
7. Support DN250-10 10 inch No. 20 Tee with reducers attach to Module 1; 8 inch Sch. 80 PVC Supply Piping using DN200 ­ 8 inch Victaulic Coupling.
Note: Orient the Tee with the branch line facing up and connecting to Module 1(rear module). See Figure 12, p. 21.
8. While properly supporting piping, connect both supply connections together using (3) 8 inch x 88.5 inch Sch. 80 PVC Pipe(s) from front to rear supply tower connections.

TEMP-SVX003A-EN

19

Cooling Tower Piping Kit and Water Connections

9. Final assembly should resemble Figure 12, p. 21. 10. Tighten couplings.
Tower Return Side Piping Assembly Instructions

Table 14. Return side spool kit contents – RSCT1000F2

Qty

Description

16

DN200-8 – 8 in. 107N QuickVic Coupling

2

8 in. Dia x ~88.5 in. Long Sch. 80 PVC Pipe(s)

1

8 in. Dia x ~36.5 in. Long Sch. 80 PVC Pipe(s)

1

8 in. Dia x ~45.5 in. Long Sch. 80 PVC Pipe(s)

8

DN250-10 – 10 in. 107N QuickVic Coupling

4

DN200-8 – 8 in. No 10 90° Elbow

2

DN200-8 – 8 in. No 11 45° Elbow

1

DN250-10 10 in. No. 20 Tee

2

DN250-10 -10 in. No. 60 Cap

4

DN250-200 – 10 in. x 8 in. No 50. Concentric Reducer

4

8 in. x 8 ft. Suction Hose

1

10 in. x 8 ft. Suction Hose

1. At tower connection side that won’t be used, attach DN250-10 ­ 10 inch No. 60 Caps using DN250 ­ 10 inch Victaulic Couplings.
2. At each tower outlet, attach DN250-200 ­ 10 inch x 8 inch No 50. Concentric Reducer using DN250 ­ 10 inch Victaulic Couplings.
3. At each tower outlet, attach 8 inch x 12 inch Sch. 80 PVC Pipe(s) using DN200 ­ 8 inch Victaulic Couplings.
4. To relieve undue stress on cooling tower basin connections, support each 8 inch x 12 inch Sch. 80 PVC Pipes with pipe jack stands underneath the front of the trailer in the spare tire carrier area.
5. Attach DN200-8 ­ 8 inch No. 10, 90° Elbow(s) to each 8 inch Sch. 80 PVC Pipe using DN200 ­ 8 inch Victaulic Couplings. Elbows should face the ground and be perpendicular to tower return piping.
6. Attach approximately 24 inch x 8 inch Sch. 80 PVC pipe to Module 2 (front module) elbow and approximately 21 inch x 8 inch Sch. 80 PVC to Module 1 (rear module) elbow using DN200 ­ 8 inch Victaulic Couplings.
7. Support DN200-8 ­ 8 inch No. 10, 90° Elbow(s) and attach to each 8 inch Sch. 80 PVC Pipe installed in previous step using DN200 ­ 8 inch Victaulic Couplings. Orient elbows to face away from trailer and towards each other. See Figure 13, p. 21.
8. Attach two pieces (8 inch x 8 foot suction hose) to each installed elbow and bring the opposite end of the hoses together in the middle per Figure 11, p. 21.
9. Place DN250-10 10 inch No. 20 Tee in between each outlet connection of tower and close to the hoses routed in previous step.

10. Assemble DN250-200 – 10 inch x 8 inch No 50. Concentric Reducer(s) on either side of the pass through on the tee.
11. Attach DN200-8 – 8 inch No 11 45° Elbow(s) to each reducer.
12. Fasten with DN200 ­ 8 inch Victaulic Couplings.
Note: 45° Elbow orientation should be set pointing towards each hose.
13. Attach each outlet hose to the 45° Elbow/Tee assembly using DN200 ­ 8 inch Victaulic Couplings.
14. At top of tee, attach 10 inch x 8 foot suction hose using DN250 ­ 10 inch Victaulic Coupling and route to pump inlet.
15. Tighten couplings.

20

TEMP-SVX003A-EN

Figure 11. Cooling tower piping kit assembly

Cooling Tower Piping Kit and Water Connections

Figure 12. Assembled supply side drop piping

Figure 13. Assembled suction side drop down

TEMP-SVX003A-EN

21

Start-Up

270 Ton Tower (CSCT0270F0)
1. Confirm 460V three phase power is connected via Series 16 Type Cams and the phase rotation is correct.
2. Confirm tower is level, refer to Table 2, p. 7 for level requirements.
3. Flush the cold water basin (with strainer screens in place) to remove sediment or dirt that may have settled during transportation.
4. Install water piping, remove basin access, adjust make up water valve to correct level.
Notes:
· Basin outlet connections must be fully submerged for tower to operate properly.
· A bleed line and valve should be installed on pump discharge piping. Route line to appropriate drain.
· Tower drain plug has been removed to avoid water pooling inside the tower basin. Drain plug is located inside the starter cabinet. Reinstall drain plug prior to starting tower if port is not to be used.
5. Fill the loop and confirm (while water is flowing through the system), the water in the basin stays above tower basin connections.
Note: Refer to Table 1, p. 5 for make-up water operating pressures.
If operation ambient temperatures below 45°F while cooling tower is on site, basin heater switch (located on starter panel) should be in “AUTO” position.
If ambient temperatures above 45°F while cooling tower is on site, basin heater switch should be placed in the “OFF” position.
Heater must be fully submersed below water to operate properly.
Figure 14. Cooling tower basin heater switch

8. To start the cooling tower, flip disconnect to the “ON” position.
Important: Prior to starting fan(s), water must be flowing through the system.
This tower is equipped with an HOA Switch located on the starter panel. Turn the switch to “HAND” mode to run the fan 24/7. Turn the switch to “AUTO” mode to run the fan until the basin water setpoint has been reached. Figure 15. Cooling tower fan switch
If running the tower in auto, select a supply water setpoint via the temperature control mounted directly to the tower next to the 6 inch water connections. The cooling tower fan will cycle on/off as the basin water temperature exceeds or meets the dial setpoint. Figure 16. Cooling tower temperature control

6. Confirm 460V three phase power is connected via Series 16 Type Cams and phase rotation is correct.
7. Confirm all access openings, safety screens and covers are in place and secure.
22

9. Confirm proper rotation of fan and allow sufficient time for unit to reach steady state prior to leaving unit to operate autonomously.
TEMP-SVX003A-EN

500 Ton Tower (CSCT0500F1)
1. Confirm tower is level, refer to Table 3, p. 7 for level requirements. Note: This tower has two cells. Each cell can operate at individual setpoints if required.
2. If tower cells are to be run in parallel with each other and both cells are feeding the same process, confirm weir plate between tower basins is removed. If tower cells are to be run on independent water circuits, confirm weir plate has been installed between cells.
3. Flush the cold water basin (with strainer screens in place) to remove sediment or dirt that may have settled during transportation.
4. Install water piping, remove tower louvers, adjust make up water valve(s) to correct level
Notes: · Basin outlet connections must be fully submerged for
tower to operate properly. · A bleed line and valve should be installed on pump
discharge piping. Route line to appropriate drain. · Tower drain plug has been removed to avoid water pooling
inside the tower basin. Drain plugs are located inside the starter cabinet. Reinstall drain plug prior to starting tower if ports are not to be used. 5. Fill the loop and confirm (while water is flowing through the system), the water in the basin stays above tower basin connections. Note: Refer to Table 1, p. 5 for make-up water operating
pressures. If operation ambient temperatures below 45°F while cooling tower is on site, basin heater switches (located on starter panel) should be in “AUTO” position. If ambient temperatures above 45°F while cooling tower is on site, basin heater switch should be placed in the “OFF” position. Heater must be fully submersed below water to operate properly. Figure 17. Cooling tower basin heater switches
6. Confirm 460V three phase power is connected via Series 16 Type Cams and phase rotation is correct.
TEMP-SVX003A-EN

Start-Up
7. Confirm all access openings, safety screens and covers are in place and secure.
8. To start the cooling tower, turn disconnect to the “ON” position.
Important: Prior to starting fan(s), water must be flowing through the system.
This tower is equipped with individual HOA Switches for each tower module on the starter panel. Turn the switch to “HAND” mode to run the fan 24/7. Turn the switch to “AUTO” mode to run the fan until the basin water setpoint has been reached. Figure 18. Cooling tower fan switch
WARNING Live Electrical Components!
Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury. When it is necessary to work with live electrical components, have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks.
If running the tower in auto, use the Honeywell T775 Controller to select a supply water setpoint via the Honeywell Controller mounted on the inside of the starter panel. The cooling tower fan(s) will cycle on/off as the basin water temperature exceeds or meets the T775 Controller setpoint. Please refer to Figure 20, p. 24 for programming setpoint. To access the cooling setpoint, press Menu
Program Relay 1 SETPOINT Up or Down Arrows to change SETPOINT Press right arrow () to
accept the setpoint Temperature.
23

Start-Up
Note: Relay 1 changes setpoint for cell 1 of cooling tower and Relay 2 changes setpoint for cell 2 of cooling tower.

Figure 19. Cooling tower temperature control

Figure 20. Setpoint navigation

9. Confirm proper rotation of fan and allow sufficient time for unit to reach steady state prior to leaving unit to operate autonomously.

24

TEMP-SVX003A-EN

1000 Ton Tower (RSCT1000F2)
1. Confirm tower is level, refer to Table 4, p. 7 for level requirements.
Note: This tower has 2 cells and the ability to operate each cell at individual setpoints if required.
2. If tower cells are to be run in parallel with each other and both cells are feeding the same process, confirm equalization valve between tower basins is open. If tower cells are to be run on independent water circuits, equalization valve between tower basins is closed.
3. Flush the cold water basin (with strainer screens in place) to remove sediment or dirt that may have settled during transportation.
4. Install water piping, remove tower louvers, adjust make up water valve(s) to correct level.
Notes:
· Basin outlet connections must be fully submerged for tower to operate properly.
· A bleed line and valve should be installed on pump discharge piping. Route line to appropriate drain.
· Tower drain plug has been removed to avoid water pooling inside the tower basin. Drain plugs are located inside the starter control cabinet. Reinstall drain plugs prior to starting tower if ports are not to be used.
5. Fill the loop and confirm (while water is flowing through the system), the water in the basin stays above tower basin connections.
Note: Refer to Table 1, p. 5 for make-up water operating pressures.
If operation ambient temperatures below 45°F while cooling tower is on site, basin heater breakers (located inside of the starter panel) should be in “ON” position. If ambient temperatures are going to be above 45°F while cooling tower is on site, basin heater breakers should be placed in the “OFF” position.
Figure 21. Cooling tower basin heater breakers

Start-Up
6. Confirm 460V three phase power is connected via Series 16 Type Cams and phase rotation is correct.
7. Confirm all access openings, safety screens and covers are in place and secure.
8. To start the cooling tower, turn disconnect (Represented as letter I in Figure 22, p. 25) to the “ON” position.
Important: Prior to starting fan(s), water must be flowing through the system.
This tower is equipped with individual Start and Stop Buttons for each tower module on the starter panel. Selection of M1(J1) and M2(J2) “Start” button(s) will enable the temperature controller assigned to the respective module to control the fans. Figure 22. Cooling tower starter panel door layout
The control module(s) are in a separate cabinet that is mounted on the end of the cooling tower, next to the starter cabinet at eye level. Figure 23. Cooling tower control module

TEMP-SVX003A-EN

9. Once the control module(s) are powered up, see one of the two screens in Figure 24, p. 26. To toggle between the
“Info” screen and the “Main Menu” screen, press +
simultaneously on the control module.
25

Start-Up
Figure 24. Cooling tower control module startup screens
10. The tower control module(s) control each tower individually, so the setpoint will need to be changed on both control module(s) in order to maintain setpoint.
11. To change the setpoint, navigate to the “Main Menu” Setting SETPOINT 1 from this menu, press the “P” Key and the “SETPOINT 1” value is begin to flash. Using the + keys, adjust the setpoint to the desired value and press the “P” key to save. Note: If prompted for a passcode use 0010 to enter the setting screen.
12. To exit to main menu, press + keys. The tower fans will modulate accordingly to reject the heat load and maintain cold water temperature.
13. Confirm proper rotation of fan(s) and allow sufficient time for unit to reach steady state prior to leaving unit to operate autonomously. For additional information, refer Reymsa Cooling Tower IOM that ships with machine or contact Trane Rental services for copy.

26

TEMP-SVX003A-EN

Maintenance

· Confirm proper chemical water treatment and bleed all of the air out of the system. See the water treatment recommendations below.
· Before beginning any maintenance, be certain that the power is turned off and the tower is properly locked and tagged out.
· Inspect the basin strainer and clean weekly or as often as necessary to keep it clean.
· Check the float and float valve periodically to make sure the water level is correct in the basin. The water level can be checked during operation by opening the removable louver section at the valve while the pump is running and the fans are off.
· Inspect the air louvers periodically to remove any paper, leaves, or other debris that may be blocking airflow into the unit.
Water Treatment Recommendations
To avoid build-up of residuals in the water distribution system, water must be bled off from the system in an amount equal to the rate of evaporation. In addition, water quality should be checked to confirm that the chemistry is balanced and that the water system is free from biological contamination. It is recommended the system has a bleed line installed on the discharge side of the system pump and should include a metering connection and valve. The metering connection should be used to determine the bleed water volume. The valve is used to regulate the flow. As a guideline, the bleed line and valve should be large enough to allow bleed off of an amount of water equal to 3 US gpm for each 100 tons cooling or use the formula Bleed (gpm) = Flow (gpm) x Range (F) / 1,000. Confirm with the water treatment specialist the required bleed off for the system. In some cases, the make-up water will be so high in mineral content that a normal bleed-off will not prevent scaling. Water treatment will be required and qualified water treatment company familiar with the local water conditions should be consulted. Any water treatment system used in the unit must be compatible with the unit’s materials of construction. If a chemical water treatment system is used, the chemicals selected must be accurately metered and concentrations properly controlled. See Table 15 for recommended levels.
TEMP-SVX003A-EN

Table 15. Water chemistry guidelines

Parameter pH Hardness as CaCO3 Alkalinity as CaCO3 Chlorides as Cl TDS (Total Dissolved Solids) Silica – SiO4 Sulfates – SO4 Phosphates – PO2

Range 6.5 to 8.0 50 to 300 ppm 50 to 300 ppm 125 ppm max 1500 ppm max 180 ppm max 250 ppm max 15 ppm max

· Soft water systems should be avoided. · The use of acid should be avoided. · CAUTION – Never batch load chemicals into unit. · Always regulate chemical feed.

Control of Biological Contamination

Water quality should be checked regularly for biological contamination. If biological contamination is detected, a more aggressive water treatment and mechanical cleaning program is required. The water treatment program should be performed in conjunction with a qualified water treatment company. It is important that all internal surfaces be clean of accumulated dirt and sludge.
To minimize the risk of biological contamination prior to startup or after an extended shut down, it is recommended that the entire system (cooling tower, system piping, heat exchanger, etc.) be properly cleaned. Clean all debris such as leaves and dirt from the basin. Completely fill the basin to the overflow level with water. Initiate a biocide water treatment or shock treatment program prior to operating the unit. It is preferable that all such procedures be conducted and supervised by the water treatment specialist.

CAUTION
Personal Protective Equipment (PPE) Required!
Failure to follow all safety instructions below could result in minor to moderate injury. ALWAYS wear Personal Protective Equipment (PPE) including goggles or face shield, chemical resistant gloves, boots, apron or suit as required. If it becomes necessary to use cleaning agent, refer to the manufacturer’s Materials Safety Data Sheet and follow all recommended safe handling practices.
Air Contamination
If the unit is located in an industrial area where there are chemical fumes or particulate matter in the air the impurities

27

Maintenance
will be washed out in the recirculated water and may cause scaling or corrosion. It is important not to locate the unit next to a smokestack because the unit will draw in these fumes and severely corrosive conditions may result. Bleed-off will help the situation, but if there is any sign of corrosion or scaling, a qualified water treatment company should be contacted.

28

TEMP-SVX003A-EN

Cooling Tower

270 Tons

Table 16. General – CSCT0270F0

Labels Nominal Cooling Tons

Value 270(a)

Number of Electrical Circuits

1

Number of Cells

1

Number of Fans/Cell

1

(a) Nominal cooling tower tons are determined at 3 GPM/ton, 85/95 across tower at 78°F wet bulb temperature.

Table 17. Electrical data ­ non-fused disconnect

Labels Voltage Frequency Wire Connection Type SCCR Minimum Circuit Ampacity (MCA) Maximum Overcurrent Protection (MOP) Basin Heater Qty/FLA Fan Motor Qty/FLA

Value 460V 3-phase 60 Hz Series 16 Cam-Type Connection Only 5000 A 75.8 A
150 A
(1) 10.8 A (1) 52.0 A

Table 18. Mechanical data

Labels

Value

Inlet Connection Qty/Size/Type

(1) 6 in. Victaulic

Outlet Connection Qty/Size/Type (1) 6 in. Victaulic

Make-up Connection Qty/Size/Type (1) 2 in. MPT

Drain Connection Qty/Size/Type

(1) 2 in. FPT

Overflow Connection Qty/Size/Type (1) 3 in. FPT

Drive Type

Belt Drive

Maximum Inlet Water Temp

130°F

Installed Clearances

4 ft. (sides), 6 ft. (ends)

Features
· Minimal setup required for quick installation/start-up · Forced draft counterflow · Complete controls package included · Galvanized steel construction · Capable of being lifted and transported by forklift · One (1) 9kW basin heaters

Table 19. Dimensions and weights

Labels

Value

Length

20 ft.

Width

8 ft.

Height

9 ft. 1 in.

Shipping Weight

6,500 lbs

Operating Weight

10,700 lbs

Fork Pocket Center to Center Distance 3.75 in. x 9.75 in.

Fork Pocket Dimensions

63 in.

Note: Lifting device: Forklift or crane

Note: Sound Data ­ Available Upon Request

TEMP-SVX003A-EN

29

Cooling Tower

Table 20. Cooling tower capacity (GPM)

Water Temperature

Wet Bulb Temperature (°F)

In (°F)

Out (°F)

66

68

70

72

75

78

80

95

85

1348

1274

1196

1113

975

816

694

103

85

1017

968

915

858

763

653

567

105

85

973

927

877

824

735

631

549

120

90

1007

972

936

897

832

760

706

130

90

910

880

848

813

756

692

644

Dimensional Drawings

Figure 25. Unit drawing

5 ft.-10 5/8 in. 9 ft. 1 in.

FAN MOTOR

8 ft.-1 in.

6 in. WATER INLET 6 in. WATER OUTLET

ACCESS DOOR 2 in. MPT MAKE-UP 3 in. MPT OVERFLOW
20 ft.

2 in. MPT DRAIN

30

TEMP-SVX003A-EN

500 Tons

Cooling Tower

Table 21. General – CSCT0500F1

Labels

Value

Nominal Cooling Tons

500(a)

Number of Electrical Circuits

1

Number of Cells

2

Number of Fans/Cell

2

(a) Nominal cooling tower tons are determined at 3 GPM/Ton, 85/95 across tower at 78°F wet bulb temperature.

Table 22. Electrical data ­ non-fused disconnect

Labels Voltage Frequency Wire Connection Type SCCR Minimum Circuit Ampacity (MCA) Maximum Overcurrent Protection (MOP) Basin Heater Qty/FLA Fan Motor Qty/FLA

Value 460V 3-phase 60 Hz Series 16 Cam-Type Connection Only 5kAIC 76.5 A
100 A
(2) 7.2 A (2) 34.0 A

Note: This drawing is a representation only and actual delivered product may vary.

Table 24. Dimensions and weights

Labels Length Width Height Shipping Weight w/ Trailer Operating Weight w/ Trailer Trailer Weight
Note: Lifting device: Forklift or crane

Value 48 ft. 8 ft. 6 in. 13 ft. 6 in. 24,960 lbs 32,580 lbs ~15,000 lbs

Note: Sound data ­ Available upon request.

Table 23. Mechanical data

Labels Inlet Connection Qty/Size/Type Outlet Connection Qty/Size/Type Make-up Connection Qty/Size/Type Drain Connection Qty/Size/Type Overflow Connection Qty/Size/Type Drive Type Maximum Inlet Water Temp Installed Clearances

Value (2) 6 in. Victaulic (2) 10 in. Victaulic (2) 2 in. MPT (2) 3 in. FPT (2) 3 in. FPT Belt Drive 130°F 12 ft. (sides), 4 ft. (ends)

Features
· Minimal setup required for quick installation/start-up · Series 16 cam-type connections · Complete controls package included · Galvanized steel construction · Two (2) 6kW basin heaters · Thermostatic staging of fans with manual bypass · Weir gate for independent cell operation

TEMP-SVX003A-EN

31

Cooling Tower

Table 25. Cooling tower capacity (GPM)

Water Temperature

In (°F)

Out (°F)

95

85

103

85

105

85

120

90

130

90

66 2605 1862 1756 1747 1575

68 2453 1772 1667 1705 1535

Dimensional Drawings

Figure 26. Unit drawing

Wet Bulb Temperature (°F)

70

72

75

2320

2154

1848

1675

1537

1326

1571

1458

1246

1653

1592

1471

1475

1407

1292

78 1500 1086 1027 1305 1134

80 1212 895 840 1192 1028

7 ft.-10 in. M

M

24 ft.-2 in.

ACCESS DOOR

M

ACCESS DOOR

CONTROL PANEL

19 3/4 M

10 ft.-6 in.

80 1/2 (2)10 BFW/GVD OUTLETS

71 7/8

(2) BFW/GVD
INLET

HIGH PICK POINT

19 3/4

M 71 7/8

(2) 2 MPT MAKE-UP
(2) 3 FPT OVERFLOW
(3) 3 FPT DRAIN (PLUGGED)

94

1 3/8

23 1/8 15 8 3/8 3 1/2

4 3/4

9 52 5/8

(2) LIFTING FOR FORK LIFT
24 ft.-2 in.

9 52 5/8

32

TEMP-SVX003A-EN

1000 Tons

Cooling Tower

Table 26. General – RSCT1000F2

Labels Nominal Cooling Tons

Value 1000(a)

Number of Electrical Circuits

1

Number of Cells

2

Number of Fans/Cell

8

(a) Nominal cooling tower tons are determined at 3 GPM/ton, 85/95 across tower at 78°F wet bulb temperature.

Table 27. Electrical data ­ circuit breaker style disconnect (300 Amp)

Labels Voltage Frequency Wire Connection Type SCCR Minimum Circuit Ampacity (MCA) Maximum Overcurrent Protection (MOP) Basin Heater Qty/FLA Fan Motor Qty/FLA

Value 460V 3-phase 60 Hz Series 16 Cam-Type Connection Only 65,000 A 180 A
300 A
(4) 9.63 A Each (16) 4.7 A Each

Table 28. Mechanical data

Labels Inlet Connection Qty/Size/Type Outlet Connection Qty/Size/Type Make-up Connection Qty/Size/Type Drain Connection Qty/Size/Type Overflow Connection Qty/Size/Type Drive Type Maximum Inlet Water Temp

Value (2) 8 in. Victaulic (2) 10 in. Victaulic (2) 1½ in. FPT (2) 2 in. FPT (2) 2 in. FPT Direct Drive EC Fan 130°F

Features
· Minimal setup required for quick installation/start-up · Induced draft counterflow · Complete controls package included · EC fan motors for capacity modulation · Reinforced fiberglass construction with permanently
bonded UV protection · Seamless cold water basin · Water connections on both sides of tower · Two (2) 8 kW basin heaters · Cells can run independently of each other or together · Mechanical float make up water valve

Table 29. Dimensions and weights

Labels

Value

Length

48 ft. 4 in.

Width

8 ft. 6 in.

Height

13 ft. 6 in.

Shipping Weight w/ Trailer

30,000 lbs

Operating Weight w/ Trailer

54,600 lbs

Trailer Weight

10,100 lbs

Note: Lifting device: None ­ not removable from trailer

Table 30. Installed clearances(a)

Labels

Value

Front/Back

6 ft.

Sides

5 ft.

(a) Clearances assume three walls surround tower with one open end. See IOM for additional clearances while operating multiple towers in close proximity of each other.

Table 31. Sound data
Labels Free-Field S.P.L at 5 ft. Free-Field S.P.L at 30 ft. Free-Field S.P.L at 50 ft.

Value 75.9 dBA 60.3 dBA 55.9 dBA

TEMP-SVX003A-EN

33

Cooling Tower

Table 32. Cooling tower capacity (GPM)

Water Temperature

In (°F)

Out (°F)

95

85

103

85

105

85

120

90

130

90

66 3679 3735 3884 3341

68 3483 348. 3699 3229

Dimensional Drawings

Figure 27. Unit drawing

Wet Bulb Temperature (°F)

70

72

75

4599

4237

3650

3274

3052

2687

3302

3110

2904

3566

3426

3276

3110

2982

2771

78 3000 2273 2566 3031 2553

80 2481 1955 2180 2756 2354

34

TEMP-SVX003A-EN

Notes

TEMP-SVX003A-EN

35

Trane – by Trane Technologies (NYSE: TT), a global climate innovator – creates comfortable, energy efficient indoor environments for commercial and residential applications. For more information, please visit trane.com or tranetechnologies.com.
Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice. We are committed to using environmentally conscious print practices.

TEMP-SVX003A-EN 16 Jun 2024
Supersedes CHS-SVN08G-EN (Sep 2023)

©2024 Trane

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Trane User Manuals

Related Manuals