IDEAL IS 0055-1 10 Awg Lever Wire Connector Instructions

September 19, 2024
IDEAL

10 AWG LEVER WIRE CONNECTOR
INSTRUCTIONS – MODELS  L32, L33, L35

IS 0055-1 10 Awg Lever Wire Connector

CAUTON : LISTED FOR USE WITH Cu-Cu AND Cu-CC. DO NOT USE WITH ALUMINUM WIRE. For use in dry locations only. Consult IDEAL for a complete table of UL Listed Certified combinations. To be sold only with installation instructions.
Installation Instructions:

  1. Wiring must comply with all applicable electrical codes.
  2. Turn OFF power before removing or installing connectors.
  3. Cleanly strip wires 1/2″ (13 mm).
  4. Open lever of desired port.
  5. Insert conductor into open port making sure the conductor is fully inserted into the back of the connector. Use only one conductor per port.
  6. While holding wire in port, close and secure the lever.
  7. Verify conductor is fully inserted to the back of the connector.
  8. Connector is reusable. If reusing connector, cut and re-strip conductors.
  9. To remove a wire, open lever and remove wire.

Wire Ranges

Solid Copper : 22-10 AWG (0.5-6mm2r)
Solid Copper-Clad Aluminum : 12-10 AWG
Stranded Copper : 22-10 AWG
For use on insulation types TFN, TFFN, THHN, XHHW, T90 nylon or equivalent.
Temperature Rating : 105°C max. (221°F)
Voltage Rating: 600V maximum in building wiring, 1000V maximum in fixtures and signs.

WARNING
Improper use or installation of this product may cause fire, electrocution, serious personal injury or death. Shut off power to the circuit or remove fuse before using this product. Use
only connectors properly sized to the wiring being used. Consult local building codes for installation requirements.
WARNING
Cancer and Reproductive Harm
Warranty:www.idealind.com

IDEAL INDUSTRIES, INC.
1375 Park Avenue  Sycamore, IL 60178 | U.S.A.
IS 0055-1