SUNNY MCU-ST Series Emergency Light User Manual

September 17, 2024
Sunny

SUNNY MCU-ST Series Emergency Light

Specifications

  • Product: Self-Contained Emergency Light MCU-ST Series
  • Power Supply: 230VAC
  • Microcontroller: 8-bit
  • Remote Testing: Yes
  • Operating Temperature: Up to 50°C

FAQs

  • Q: How often should I charge the battery for maintenance?
    • A: The battery should be charged every 3 months to maintain operational life.
  • Q: Can the unit be used outdoors?
    • A: No, the unit should be installed indoors away from direct sunlight and humidity.
  • Q: How do I know if the unit is receiving power?
    • A: Check the AC LED indicator; a continuous orange light means it’s receiving a normal AC power supply.

PRODUCT FUNCTION

Status Indicators and Testing Buttons

  • LED AC. Indicates that the unit is receiving a power supply
  • LED Charge/Full Indicates that the unit’s battery is charging
  • LED Battery Indicates that the unit is receiving a power
  • LED Fail Indicate error status.
  • LED 5 sec/LDR Indicate the unit is performing a 5-seconds test and display light sensor operation status.
  • LED 30 mins Indicate the unit is performing a 30-minute test.
  • LED 60 mins Indicate the unit is performing a 60-minute test.
  • LED Auto Test Indicate automatic battery test status.
  • Switch Off Press to close device testing and shut down device systems
  • Switch Test Press to test the device’s availability (during normal circumstance and the unit is plugged in)
  • IR receiver Infrared signal receiver
  • LDR Light datector sensor

Remote Testing

Features

  1. Controlled by a highly intelligent 8-bit microcontroller.
  2. Set automatic test timer for every 1 month 15 minutes and 12 months 120 minutes, following the TIS 021004-22 standard, which helps prolong battery life and reduce workload for operators or users.
  3. A 5-second, 30-minute, or 60-minute self-test can be performed on the unit using the remote.
  4. The operation can be tested manually (Manual Test).
  5. It has a Light Detector (LDR) function to detect ambient light levels. When the light level is less than 5 Lux, the device will operate immediately during a power outage.
  6. It has a Low Voltage Sound indicator to alert before the system stops battery operation.
  7. Using high-quality LEDs with a lifetime of over 50,000 hours, providing bright and constant illimitation throughout its operation.
  8. The unit’s outer case is made from ABS UL94 V-O Flame Retardant plastic that is highly resistant to impact and corrosion.

Installation and Operation

  1. The unit can be installed on leveled ground or hung up.
  2. Install properly and securely to prevent accidents that could cause damage to the unit orother people and property.
  3. Plug the unit into a power socket with a 230VAC power supply.
  4. Notice the LED will show the status as follows.
    • The LED “AC” will turn on indicating that the unit is receiving power.
    • The LED “Battery” lighting up indicates the device is ready for use. In another 5 seconds, it will enter the battery charging state.
    • The LED “Charge/Full” blinking indicates the device is currently charging the battery.
    • The LED “Charge/Full” will be off when the battery is fully charged.
  5. To use the Light Detector function, press the Off+Test switch once on the device.
    • When using the Light Detector function, the device will check the light level in the event of a power outage. If the ambient light in that area is above 5 Lux, the emergency light will not provide backup illumination from the device in order to conserve the battery charge for when it is truly needed.
    • If the Light Detector function is not selected, the emergency light will function as a normal emergency light without considering ambient light. If there is a power outage, the device will immediately provide illumination.
  6. When the unit is operational, tests can be performed using the Test button on the unit or remotely using the remote with the following options.
    • Press the 5sec button to perform a 5 second test, after which the unit will return to normal operation.
    • Press the 30min button to perform a 30-minute test, after which the unit will return to normal operation.
    • Press the 60min button to perform a 60-minute test, after which the unit will return to normal operation.
    • To cancel the test command, press the ‘ ‘ button on the device or the ‘ ‘ button on the remote tester.
    • Note: When activating the self-test function whether through the remote or the button on the unit, the test button will have the same function.

Important Note on Using the Unit

  1. The emergency lighting unit should be installed indoors, out of direct sunlight and humidity. It should not be installed in an environment with temperatures higher than 50 degrees Celsius.
  2. The unit should be stored in temperatures under 25 Degree Celsius and the battery should be charged every 3 months to maintain its operational life.
  3. Please always read the manual carefully before operating the unit for the safest and most effective use of the product.

Indicators

Remote Testing

  •  Button for testing the device’s function for 5 seconds.
  •  Button for testing the device’s function for 30 mins.
  •  Button for testing the device’s function for 60 mins.
  •  Button for turning on auto battery test system
  •  Button for turning off auto battery test system
  •  Button for canceling the test

Dimension

Dimension (mm)

Initial Troubleshooting

Problem Cause What to do

– Power not getting to the unit after plugging in. The LED AC light does not turn on.| – The power socket might not have any power.

– The plug or socket is loose.

– The AC fuse is blown.

| – Check the 220-240VAC power supply.

– Check the plug and socket.

– Contact customer service.

– Emergency light does not turn on after the power goes out.| – The lamp is faulty

– The circuit’s wiring is loose.

– The DC fuse is blown

| – Contact customer service.

– Contact customer service.

– Contact customer service.

– Emergency light only turns on for a short time after the power goes out.| – The battery is not fully charged.

– The battery is past its operational lifetime or has deteriorated

| – Take the emergency light unit to charge until the “LED Charge” indicator turns off.

– Contact customer service to replace the battery

Warranty

Terms for Warranty and Service

  1. The Warranty will only be covered if the customer fills in the “warranty registration form” and mails the returned part back to the company within 7 days from the day of purchase. If this is not carried out the warranty will be considered void.
  2. The warranty only covers the unit’s internal parts. The conditions and durations for the warranty of each part are as specified and the duration of the warranty is calculated from the date of purchase.
  3. Please show your warranty card every time you contact our service center or the dealer you purchased the product from.
  4. Products that fall into the following category are considered not covered by the warranty.
    • The product was used in a way not specified in the manual.
    • The product was used with accessories not meet the required specifications specified in the manual.
    • The product seems to have been damaged from being dropped or from a strong impact, for example, the parts are loose, dented, scrapped, or misshapen.
    • The product has been repaired or modified by personnel not authorized by our company.
    • The Warranty Void sticker is torn or removed.
    • The product is damaged from careless use or incorrect maintenance, for example, the battery is swollen from overcharging, quick charging was used on the battery, the battery terminals have been short-circuited, the unit was used until the battery was completely discharged and not recharged immediately, the product was stored for long periods until the Battery Checker warning activates and still it is not plugged-in to charge or taking the battery to normal temperature conditions and not recharging it every 1 month.
    • The product was stored in an unsuitable environment, for example, a location with moisture or water vapor.
    • The product was supplied with a faulty AC power supply such as electrical overvoltage, electrical current surges, or lightning strikes entering the AC power line.
    • Damages from natural causes such as fire, being summered in fluids, humidity, chemicals, or force majeure. Damages from insects or animals.
    • Note: Please read the manual carefully before installation and operation to understand how to properly operate the unit.

CONTACT INFORMATION

  • For any further questions about your product please feel free to contact SUNNY’s customer service department.
  • Tel. (+66) 02-948-4450-2
  • E-mail: service@sunnyemergencylight.com.
  • IsOn Import-Export Co., Ltd.
  • 2915-2917 Ladprao Road, Klongjan,
  • Bangkapi, Bangkok 10240

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Sunny User Manuals

Related Manuals