COPELAND AE8-1275 R10 Sentronic and Sentronic Plus Electronic Oil Pressure Control Owner’s Manual
- September 15, 2024
- Copeland
Table of Contents
- AE8-1275 R10 Sentronic and Sentronic Plus Electronic Oil Pressure Control
- Product Information
- Specifications
- Product Usage Instructions
- Safety
- Responsibilities, Qualifications, and Training
- Terminal Venting and Other Pressurized System Hazards
- Flammable Refrigerant Hazards
- Electrical Hazards
- Q: How should I check if a Sentronic is installed correctly in
AE8-1275 R10 Sentronic and Sentronic Plus Electronic Oil Pressure Control
Product Information
Specifications
- Model: Sentronic and Sentronic+
- Control Type: Electronic Oil Pressure Control
- Bulletin Number: AE8-1275 R10
- Release Date: May 2024
Product Usage Instructions
Safety
It is crucial to be aware of the hazards and precautions
outlined in the user manual. Ensure that all individuals involved
in the design, manufacture, installation, and servicing of the
system are informed about safety measures.
Responsibilities, Qualifications, and Training
Proper qualifications and training are essential for those
handling the Sentronic and Sentronic+ Electronic Oil Pressure
Control. Only qualified personnel should be responsible for the
installation and maintenance of the system.
Terminal Venting and Other Pressurized System Hazards
Be cautious of pressurized oil, refrigerant, and debris that may
spray out in case of a compressor’s electrical terminal pin seal
loss. This can lead to serious injuries or property damage. Visit
copeland.com/terminal-venting for detailed information.
Flammable Refrigerant Hazards
Prevent flammable refrigerant release as it can create an
explosive concentration near the system, potentially leading to
fire or explosion. Refer to copeland.com/flammable-refrigerants for
safety guidelines.
Electrical Hazards
Prior to any work on the system, ensure it is de-energized, and
capacitors have been discharged to avoid the risk of electric
shock.
FAQ
Q: How should I check if a Sentronic is installed correctly in
a system?
A: Refer to the user manual for detailed instructions on how to
verify proper installation of the Sentronic in your system.
MAY 2024
BULLETIN AE8-1275 R10
Application Engineering
Sentronic and Sentronic+ Electronic Oil Pressure Control
BULLETIN NO:
Contents
AE8-1275 R10
Safety
Important Safety Information
2
Responsibilities, Qualifications and Training
2
Terminal Venting and Other Pressurized System
Hazards
2
Flammable Refrigerant Hazards
3
Electrical Hazards
3
Hot Surface and Fire Hazards
3
Lifting Hazards
3
POE Oil Hazards
3
Precautions
3
Signal Word Definitions
5
Introduction
Basic Control Operation
6
Installing Sentronic
7
Field Installation Checks
8
Start-Up Quick Checks
8
Sentronic Specifications
8
Electrical Connection Instructions
10
Electrical Bench Checkout Procedure
13
Start-Up Quick Checks
15
Interchangeability of Sentronic and Sentronic+
Modules and Sensors
15
Connecting the Sentronic+ Module to an Older
Sentronic Sensor
15
Connecting the old Sentronic Module to a Newer
Sentronic+ Sensor
16
Sentronic+ Terminal Strip
16
How to Check a Sentronic Installed in a System 17
MAY 2024
BULLETIN AE8-1275 R10
Safety
Important Safety Information
Those involved in the design, manufacture, and installation of a system,
system purchasers, and service personnel may need to be aware of hazards and
precautions discussed in this section and throughout this document. OEMs
integrating the compressor into a system should ensure that their own
employees follow this bulletin and provide any necessary safety information to
those involved in manufacturing, installing, purchasing, and servicing the
system.
Responsibilities, Qualifications and Training
· OEMs are responsible for system design, selection of appropriate components,
integration of this component into the system, and testing the system. OEMs
must ensure that staff involved in these activities are competent and
qualified.
· OEMs are also responsible for ensuring that all product, service, and
cautionary labels remain visible or are appropriately added in a conspicuous
location on the system to ensure they are clear to any personnel involved in
the installation, commissioning, troubleshooting or maintenance of this
equipment.
· Only qualified and authorized HVAC or refrigeration personnel are permitted
to install, commission, troubleshoot and maintain this equipment. Electrical
connections must be made by qualified electrical personnel.
· Observe all applicable standards and codes for installing, servicing, and
maintaining electrical and refrigeration equipment.
Terminal Venting and Other Pressurized System Hazards
If a compressor’s electrical terminal pin loses its seal, pressurized oil,
refrigerant, and debris may spray out. This is called “terminal venting”.
The ejected debris, oil, and refrigerant can injure people or damage property.
The oil and refrigerant spray can be ignited by electrical arcing at the
terminal or any nearby ignition source, producing flames that may project a
significant distance from the compressor. The distance depends on the pressure
and the amount of refrigerant and oil mixture in the system. The flames can
cause serious or fatal burns and ignite nearby materials.
Each compressor has a terminal cover or molded plug that covers electrical
connections. The cover or plug helps to protect against electric shock and the
risks of terminal venting. If terminal venting occurs, the cover or plug helps
contain the spray of refrigerant and oil and reduces the risk of ignition. If
ignition occurs, the plug or cover helps contain the flames. However, neither
the terminal cover nor the molded plug can completely eliminate the risk of
venting, ignition, or electric shock.
See copeland.com/terminal-venting for more details about terminal venting.
Additionally, a compressor’s refrigerant lines keep refrigerant and oil under
pressure. When removing or recharging refrigerant from this component during
service, this can pose a pressurized fluid hazard.
© 2024 Copeland
2
www.copeland.com
MAY 2024
BULLETIN AE8-1275 R10
Flammable Refrigerant Hazards
If flammable refrigerant is released from a system, an explosive concentration
can be present in the air near the system. If there is an ignition source
nearby, a release of flammable refrigerant can result in a fire or explosion.
While systems using flammable refrigerant are designed to mitigate the risk of
ignition if the refrigerant is released, fire and explosion can still occur.
See copeland.com/flammable-refrigerants for more information on flammable
refrigerant safety.
Electrical Hazards
Until a system is de-energized, and capacitors have been discharged, the
system presents a risk of electric shock.
Hot Surface and Fire Hazards
While the system is energized, and for some time after it is deenergized, the
compressor may be hot. Touching the compressor before it has cooled can result
in severe burns. When brazing system components during service, the flames can
cause severe burns and ignite nearby combustible materials.
Lifting Hazards
Certain system components may be very heavy. Improperly lifting system
components or the compressor can result in serious personal injury. Use proper
lifting techniques when moving.
POE Oil Hazards
This equipment contains polyol ester (POE) oils. Certain polymers (e.g.,
PVC/CPVC and polycarbonate) can be harmed if they come into contact with POE
oils. If POE oil contacts bare skin, it may cause an allergic skin reaction.
Precautions
· Always wear personal protective equipment (gloves, eye protection, etc.). ·
Keep a fire extinguisher at the jobsite at all times. · Keep clear of the
compressor when power is applied.
– IMMEDIATELY GET AWAY if you hear unusual sounds in the compressor. They can
indicate that terminal pin ejection may be imminent. This may sound like
electrical arcing (sizzling, sputtering or popping). However, terminal venting
may still occur even if you do not hear any unusual sounds.
© 2024 Copeland
3
www.copeland.com
MAY 2024
BULLETIN AE8-1275 R10
· Never reset a breaker or replace a blown fuse without performing appropriate
electrical testing
– A tripped breaker or blown fuse may indicate an electrical fault in the
compressor. Energizing a compressor with an electrical fault can cause
terminal venting. Perform checks to rule out an electrical fault.
· Disconnect power and use lock-out/tag-out procedures before servicing.
– Before removing the terminal cover or molded plug, check that ALL electrical
power is disconnected from the unit. Make sure that all power legs are open.
(Note: The system may have more than one power supply.)
– Discharge capacitors for a minimum of two minutes
– Always use control of hazardous energy (lock-out/tag-out) procedures to
ensure that power is not reconnected while the unit is being serviced.
· Allow time for the compressor to cool before servicing.
– Ensure that materials and wiring do not touch high temperature areas of the
compressor.
· Keep all non-essential personnel away from the compressor during service.
· For A3 refrigerants (R290) remove refrigerant from both the high and low
sides of the compressor. Use a recovery machine and cylinder designed for
flammable refrigerants. Do not use standard recovery machines because they
contain sources of ignition such as switches, high- and low-pressure controls
and relays. Only vent the R290 refrigerant into the atmosphere if the system
is in a well-ventilated area.
· Never use a torch to remove the compressor. Only tubing cutters should be
used for both A2L and A3 refrigerants.
· Use an appropriate lifting device to install or remove the compressor.
· Never install a system and leave it unattended when it has no charge, a
holding charge, or with the service valves closed without electrically locking
out the system.
· Always wear appropriate safety glasses and gloves when brazing or unbrazing
system components.
· Charge the system with only approved refrigerants and refrigeration oils.
· Keep POE oils away from certain polymers (e.g., PVC/CPVC and polycarbonate)
and any other surface or material that might be harmed by POE oils. Proper
protective equipment (gloves, eye protection, etc.) must be used when handling
POE lubricant. Handle POE oil with care. Refer to the Safety Data Sheet (SDS)
for further details.
· Before energizing the system:
1. Securely fasten the protective terminal cover or molded plug to the
compressor, and
2. Check that the compressor is properly grounded per the applicable system
and compressor requirements.
© 2024 Copeland
4
www.copeland.com
MAY 2024
BULLETIN AE8-1275 R10
Signal Word Definitions
The signal word explained below are used throughout the document to indicate
safety messages.
DANGER indicates a hazardous situation which, if not avoided, will result in
death or serious injury.
WARNING indicates a hazardous situation which, if not avoided, could result in
death or serious injury.
CAUTION, used with the safety alert symbol, indicates a hazardous situation
which, if not avoided, could result in minor or moderate injury.
© 2024 Copeland
5
www.copeland.com
MAY 2024
BULLETIN AE8-1275 R10
Introduction
The current Copeland® Sentronic® electronic oil pressure safety control (see
Figure 1) replaces two older Sentronics; the four terminal, triac output
style, and the five terminal, relay output style (see Figure 2). The current
Sentronic has all the features of previous Sentronic, with valuable additions.
All Sentronics utilize a pressure sensor and an electronic control module to
precisely measure oil pump differential pressure. The main advantage of
Sentronic is the elimination of the traditional capillary tubes, bellows, and
pressure connections that mechanical pressure switches require to measure
differential oil pressure. These require careful handling and are known to be
a source of leaks in refrigeration systems.
A second advantage of Sentronic is in the use of a precise electronic clock
for the two-minute time out circuit. Traditional mechanical controls use
resistance heaters to provide the time to trip in the event of low oil
pressure. 208volt systems, low ambient temperatures or brown-out type
conditions cause the heater output to be reduced, thus increasing the time out
period from two minutes to three or four minutes when low oil pressure
conditions exist. With the electronic clock, the time out will always be the
same.
As a result of the elimination of the capillary tube measuring system and a
more precise timing circuit, Sentronic will improve the overall reliability of
the refrigeration system.
Any Copeland® compressor with the new oil pump design (see AE4-1166) can
utilize Sentronic. Any Sentronic can replace existing capillary tube controls
in the field.
As in the past, all new and replacement Copelametic® compressors equipped with
oil pumps require the use of an Copeland approved oil pressure safety switch.
Failure to use an approved oil pressure safety switch will be considered as
misuse of the compressor and can adversely affect warranty replacement of the
compressor should a lubrication connected failure occur.
To meet Copeland specifications, an oil pressure safety switch must meet many
requirements. These include
maintaining its pressure setting and time delay calibration within close
limits over the widest variation in operating conditions to be expected and
must successfully pass a life test with a minimum of 200,000 cycles. Controls
must be of the non-adjustable, manual reset type with a 120 second nominal
time delay at rated voltage, have a cut-out pressure setting of 7 to 9 PSID
(Pounds per Square Inch Differential, the difference between crankcase
pressure and oil-pump outlet pressure) and a cut-in (timer delay off) pressure
of 12-14 PSID.
Basic Control Operation
The Sentronic Sensor
The same oil pressure sensor is used for all Sentronics. It mounts directly
into the oil pump. The Sentronic sensor measures oil pump differential
pressure. It has an internal contact that opens on low oil pressure and
signals the Sentronic electronic control module to begin time out. The same
contact closes when proper oil pressure is present and stops the module time
out.
Should oil pressure fall below 7-9 PSID for a period of two minutes, the
Sentronic module will open the control circuit, using its Normally Closed
(N.C.) contact, and shut the compressor off.
Approximate oil pressure can be measured in the field. Oil pumps are furnished
with a Schrader valve mounted on the oil pump discharge port. To measure oil
pressure, subtract crankcase pressure from discharge oil pressure.
Tripping of the oil pressure safety switch is a warning that the system has
been without proper lubrication for too long a time. Repeated trips of the oil
pressure safety control are a clear indication that something in the system
requires immediate remedial action. On a well-designed system there should be
no trips of the oil pressure safety control, and repeated trips should never
be accepted as a normal part of the system operation.
Caution: An electronic timer may be placed in series with the compressor
contactor to force a delay before each start and prevent possible short
cycling. The timer must be located so it also prevents the Sentronic from
energizing during the timing period. SOME INEXPENSIVE TIMERS
© 2024 Copeland
6
www.copeland.com
MAY 2024
BULLETIN AE8-1275 R10
MAY “LEAK” ENOUGH POWER, WHILE “TIMING OUT”, TO ENERGIZE THE SENTRONIC EVEN
THOUGH THERE MAY NOT BE ENOUGH “LEAKAGE” TO CLOSE THE COMPRESSOR CONTACTOR.
THIS CAN CAUSE A PREMATURE SENTRONIC TRIP. If there is doubt, the circuit
should be checked before placing it in operation.
The Sentronic Module
The Sentronic has in addition to the (N.C.) contact, used for compressor
shutdown, a Normally Open (N.O.) contact that can be used in an alarm circuit
(See Diagram 4A).
The Single Pole Double Throw (S.P.D.T.) contact of Sentronic can be
electrically isolated from the control circuit power supply and used to
control a circuit with a different voltage (See Diagram 6).
Sentronic has a timing circuit that actually compares the amount of time with
good oil pressure to that with insufficient oil pressure and has a memory that
will shut the compressor down after a period of more than two minutes if the
compressor has a “history” of oil pressure fluctuations with more unacceptable
than acceptable pressures.
Sentronic also has a memory that retains the compressor oil pressure “history”
for up to one minute in the event of a power loss.
Sentronic uses a permanent magnet integral with the reset button to reset its
output control relay in the event of a trip. When the reset button is
depressed, it magnetically pulls the Sentronic relay’s armature to its
original, reset position. Sentronic needs no voltage present to reset.
Installing Sentronic
To Install the Sensor, Figure 1:
1. Remove the plug fitting from the oil pump housing. Discard the copper
washer from under the head of the plug fitting.
2. Install a new O ring into the groove on the sensor. Use refrigeration oil
to pre-lube the O ring before installation. Use care not to cut the O ring.
3. Install a new copper washer under the hex flange of the sensor. Do not
reuse the copper washer removed with the plug fitting. Screw the sensor into
the pump body. Torque the sensor to 60-65 Ft./lb.
To Install the Module, Figure 1:
4. When using the bracket above the oil pump use two 10-32 pan head slotted
screws with washers. The maximum screw length is .265 plus bracket thickness.
Longer screws could damage the circuit board.
5. Plug the cable from the module into the end of the sensor. Care should be
taken not to wrap the cable around a current carrying conductor.
Hi-Potting: Excessive hi-potting can cause damage to the Sentronic module.
Copeland hi-pots the module as part of final processing. If hi-potting is
required, we recommend it to be limited to single time.
Electrostatic Painting: Static electricity discharges from electrostatic
painting can damage the Sentronic module. We recommend that the module not be
mounted until such painting is completed.
Remote Mounting the Sentronic Module
All OEM Copeland® compressors with oil pumps shipped after September 1986, have a plug fitting in the oil pump for mounting the sensor. The oil pump is designed to accept either the Sentronic sensor or a capillary tube for the traditional mechanical oil pressure control.
The Sentronic sensor sends a low voltage signal to the Sentronic module. When the Sentronic module is mounted on the compressor the sensor will normally experience no disturbance from nearby electrical sources. The radiating power sources that can cause problems are almost always in grounded metallic enclosures. However, if the Module is located remotely from the compressor, and the sensor leads are extended, and/or routed along with other wiring, provisions must be made to prevent interference with the
© 2024 Copeland
7
www.copeland.com
MAY 2024
BULLETIN AE8-1275 R10
sensor signal which can cause nuisance trips or even Start-Up Quick Checks
damage to the module itself. Observe these precautions:
1. Sensor leads must be replaced with a shielded cable. The shield should
extend from the Sentronic module to the female sensor connector and should be
grounded only at the module end.
2. The Sentronic module has a good grounding source when mounted to the
compressor. When it is remote mounted, it must have sufficient grounding area
to minimize the effects of high-level electrical transients and secondary
lightning effects. A metal enclosure with minimum mounting surface area of 75
sq. in. is required.
Checking The Sensor
Unplug the sensor and start the compressor. Simultaneously measure the oil
pump differential pressure. Monitor the two terminals at the back of the
sensor with an ohmmeter or continuity measuring set. If the differential
pressure is below the range of 7 to 9 PSID, the sensor circuit should be open
(no continuity, infinite resistance). If the pressure is above 12-14 PSID, the
sensor circuit should be closed.
Checking the Installed Sentronic Module*
3. Copeland makes available an optional 10′ shielded Shut off the compressor. Unplug the sensor. Verify the
cable designed especially for the Sentronic. The cable module is powered by reading control voltage between the
is grounded per instruction 1.
208-230/240 (or 115/120) terminal and the L (or 2 if separate control is used) terminal.
Field Installation Checks
Before installing Sentronic, determine if the existing oil pump is equipped
with the plug fitting for mounting the sensor. If not, order the Sentronic Oil
Pump Kit.
All Sentronics can be used to replace conventional capillary tube style oil
pressure controls in the field.
Start the compressor with the sensor unplugged. Recheck to make sure the
module voltage is still present. After 120 seconds ±15 seconds, the L-M
contact should open and shut off the compressor.
With the module off on oil pressure, wait 2 minutes and press the reset
button. Module power is required to reset the 4 and 5 terminal Sentronics. The
contactor should close and start the compressor.
Earlier four and five terminal Sentronics (see Fig. 2) were electrically reset oil pressure switches. They were wired to have power to reset! The current Sentronic requires no power to reset and may be directly mechanically and electrically interchanged with any mechanical oil pressure switch.
*NOTE: More complete step-by-step procedures for bench and system Sentronic checks are included on pages 7 and 8 of this bulletin.
Sentronic Specifications
If the Sentronic module is to be remote mounted from the compressor and/or its
sensor leads are to be routed along with other voltage lines, the Sentronic
Remote Mount Instructions must be followed.
Wiring differences exist from one system manufacturer’s unit to another. If
wiring modifications are unclear, consult a certified electrician. No wiring
modifications are required for compressors using solid state motor protectors.
Cut-Out Cut-In Time Delay Max Control
7-9 PSID 12-14 PSID 120 Seconds ±15 Seconds 720 VA; 120/240V
© 2024 Copeland
8
www.copeland.com
MAY 2024
BULLETIN AE8-1275 R10
Figure 1
© 2024 Copeland
Figure 2 9
www.copeland.com
MAY 2024
BULLETIN AE8-1275 R10
Electrical Connection Instructions
CAUTION!! Damage to the Sentronic module will result if the “M” terminal of
the Sentronic is connected to ground or directly to line voltage!
When changing components or making any kind of electrical alterations to any
installation, existing or new, all ground connections must be specifically
checked to make sure they are secure. If there is any doubt about component or
system grounding, the local electrical inspector should be consulted.
While the compressor is running, if the compressor net oil pressure falls
below the cut-out setting of the sensor while operating and does not re-
establish sufficient pressure within an acceptable time, the time delay
circuit will open the L-M contacts, stopping compressor operation. Once the
oil pressure switch has tripped, it must be manually reset to restore the
system to operation.
IMPORTANT: If a power interruption occurs after an oil pressure safety trip,
wait two minutes before resetting after power is restored.
Control With Alarm
The electrical connection diagrams included in this bulletin are intended to represent the most common Sentronic application control circuits. The system manufacturer should be consulted when more complex circuits are encountered.
Diagrams 4A (new Sentronic) and 4B (previous Sentronic) use an added alarm circuit. To contrast the 4 and 5 terminal Sentronics with the new Sentronic. The new Sentronic does not require an extra relay or auxiliary contact for an alarm circuit.
Standard Control Circuits
Both Diagrams 3A (new Sentronic) and 3B (previous Sentronic) show typical
wiring connections and the similarity of Sentronic and Sentronic oil pressure
switches used on three-phase motor compressors.
Sentronics are energized when they are connected to a voltage source. In both
diagrams 3A and 3B, if the compressor controlling and overload devices are
closed, the compressor starts and at the same time, a circuit is made from one
side of the power two incoming lines to the “L” terminal. The “L” terminal is
one side of the “L”-“M”, N.C. contact of the Sentronic module. The “M” side of
the N.C. contact is usually connected to the compressor contactor coil. The
circuit for the electronic module power is completed by the connection of the
230/ 240 (or 115/120) volt terminal to the other side of the incoming power
line.
The Current Sensing Relay Used With Compressor Inherent Motor Protectors:
Compressors equipped with internal inherent protection and oil pressure safety
controls, will trip the oil pressure safety control if the internal inherent
protector should open due to motor overheating or a temporary motor overload.
After an overload trip of a compressor with an inherent protector the control
circuit will still be closed, and the Sentronic energized, although the
compressor motor is not operating. The two-minute timing circuit will activate
due to a lack of oil pressure, and after the 120 second time delay, the oil
pressure safety switch will trip. Even though the compressor motor cools
sufficiently for the internal inherent protector to automatically reset, the
compressor cannot start until the oil pressure safety control is manually
reset.
The electronic two-minute timing circuit operates whenever voltage is applied to a Sentronic, and it has not tripped. The timing will be interrupted when oil pressure rises above 12-14 PSID and closes the Sentronic sensor. Should oil pressure not build up sufficiently for 120 seconds, the electronic delay will time out, open its L-M contact, break the control circuit, and de- energize the compressor contactor to stop compressor operation.
This is normally not a problem, since the compressor, if properly applied, will seldom if ever trip on the internal inherent protector. If it should happen to do so, the fact that a protector trip has occurred, indicates that the system operation should be reviewed. However, on frozen food or other critical applications where a product loss may occur, if a compressor shutdown should occur during the night, or over the weekend when the equipment in unattended, it
© 2024 Copeland
10
www.copeland.com
MAY 2024
BULLETIN AE8-1275 R10
may be desirable to prevent a possible nuisance trip by means of a current
sensing relay.
The Penn R10A (Johnson Controls) current sensing relay has been developed for
this purpose. It is mounted on the load side of the contactor, senses by
induction the full operating current of one phase of the motor, closes on a
rise in current above 14 amps, and opens if the load current falls below 4
amps.
The use of the current sensing relay allows the compressor to cycle on the
internal inherent protector without affecting the operation of the oil
pressure safety control.
Both Diagrams 5A and 5B use a current relay (C.S.). When the current relay is
not energized by motor current, its Normally Open (N.O.) contact opens the
circuit that powers the Sentronic to avoid a nuisance trip.
Diagram 5B shows the circuit used with the older model Sentronic. An external
control relay, “R”, is required to maintain power to the module in the event
of an oil pressure safety trip since the module requires power to reset. When
the module is tripped on low oil pressure, relay “R” is not energized, and the
relay “R” Normally Closed (N.C.) contact provides a voltage path to the
module.
The circuit of Diagram 5A uses the new Sentronic. The current relay operates
in the same manner as in Diagram 5B, but the oil pressure switch requires no
power to reset, so it needs no external relay to provide a reset power path.
NOTE: On some 550-volt motor-compressors, it may be necessary to loop the
current carrying wire so that it passes through the current sensing relay
twice in order to increase the metered amperage to close the relay contacts.
Diagram 3A
Diagram 3B
© 2024 Copeland
11
www.copeland.com
MAY 2024
BULLETIN AE8-1275 R10
Diagram 4A
Diagram 4B
Diagram 5A
Diagram 5B
© 2024 Copeland
12
www.copeland.com
MAY 2024
BULLETIN AE8-1275 R10
Electrical Bench Checkout Procedure
This instruction sheet describes how the Sentronic may be easily bench-checked using only a voltmeter and a 120VAC electrical extension cord.
CAUTION! Damage to the Sentronic module may result if the “M” terminal of the Sentronic is connected to ground or directly to a voltage line!
This test is conducted with 120VAC. A shock will result if the Sentronic terminals are touched when the Sentronic module is energized.
Diagram 6
Use care whenever working with any voltage! Make sure your electrical outlet is grounded, the electrical extension cord used has a ground wire, and the ground wire is connected to the grounding screw of the Sentronic.
Using a Separate Control Voltage with the New Sentronic:
Apply 120VAC power to the Sentronic module terminals marked “120” and “L”. The Sentronic should
Diagram 6 shows how the current Sentronic might be used
have a jumper in place between terminals “M” and “2”.
with a voltage on its S.P.D.T. contact that is different from the voltage that supplies its power. Any A.C. voltage up to and including 240V might be used.
2. Wait two minutes, then push the Sentronic reset button to reset the module and start the timing circuit.
To use the Sentronic contact (S.P.D.T.) for a separate voltage, remove the jumper between terminals “2” and “M”. In this diagram, the separate control voltage is supplied by “LL1” and “LL2”. The separate voltage powers the compressor contactor (CC), by means of a Remote Relay. When the Remote Relay is energized, requesting the compressor to run, its contact, (RR), closes to deliver “LL1” voltage to the operating and limit contacts. If the contacts in the operating and limit circuit are closed, “LL1” voltage energizes the compressors contactor coil (CC). When the compressor contactor closes, it provides the power, through a control circuit transformer (XFMR), to energize the Sentronic. If the Sentronic trips, it contact (“L” to “M”) in the “LL1-LL2” control circuit opens to deenergize the compressor contactor and stop the compressor. The Sentronic contact (“L” to “A”) closes to energize an Alarm Relay (AR).
3. With a voltmeter, measure line voltage (120VAC) between the “M” terminal
and the “120” terminal. It should be the same as the electrical outlet voltage
about 120VAC.
4. Since there is no connection made to the pressure sensor, the module sees
this as a no-oil pressure condition. After two minutes (plus or minus 15
seconds – dependent on 50 or 60 cycle frequency) the Sentronic internal timer
will “time-out”. The module will trip; the circuit between “L” and “M” will
open, and it will no longer pass current to the load.
5. With the voltmeter connected to terminals “M” and “120”, the voltage
should now read zero volts because the circuit between “L” and “M” has been
opened through the action of the electronic circuit.
6. Reset the Sentronic, then remove voltage from terminals “120” and “L”.
With a small piece of wire, jumper the female sensor connections at the end of
© 2024 Copeland
13
www.copeland.com
MAY 2024
BULLETIN AE8-1275 R10
the black sensor cord attached to the module. Reapply power to terminals “120” and “L” and wait two minutes. The module should not “time-out” after two minutes because jumpering the sensor connections makes the timing circuit “see” good oil pressure. The jumper imitates the action of a small pressure switch located in the sensor. This switch opens on low oil pressure and closes on good oil pressure.
remains the same, comparing low vs. sufficient oil pressure time.
Electrical Noise Suppression
The Sentronic+ has added an electronic noise suppression feature that no
longer requires the use of shielded cables.
7. Measure between the “120” terminal and the “M” terminal with the
voltmeter. The meter should read full line voltage showing that the circuit
has not opened.
8. To check if the module will operate on 208/240 volts as well as on 120
volts, change the scale of the voltmeter (if necessary), to read up to 250VAC.
Without removing power, measure the voltage between the “M” terminal and the
“240” terminal. You should read nearly twice the voltage as that read between
the “M” terminal and the 120″ terminal. This is because Sentronic has a small
control transformer connected so that it can accept either 120V or 208/240V.
It’s self-transforming action actually enables it to step up its own voltage.
By making this voltage check, the transformer is being checked.
9. If the module successfully passes the above test sequence it is fully
functional. If the module fails any of the above steps, it is faulty and
should be replaced.
LED Diagnostics
Additional diagnostic capabilities have been added to provide instant status
of oil control.
· LED GREEN Compressor has sufficient oil pressure.
· LED RED Compressor has experienced insufficient oil pressure for longer than
two minutes Compressor is off on oil control.
· RED/GREEN FLASHING Compressor is experiencing erratic oil pressure
indicating a possible system issue.
Sentronic+ Specifications
Cut-out
7-9 PSID
Cut-in
12-14 PSID
Time Delay
120 Seconds+/-15 Seconds
Max Control
500 VA; 120/240V
Sensor Torque 60-65 Ft./lb.
The Sentronic+ oil pressure safety control replaces the current Sentronic. The Sentronic+ is a direct replacement for mechanical devices and the current Sentronic. The Sentronic+ control offers the following features:
Wiring
The Sentronic+ wiring remains the same. There are several wiring schemes
depending on control circuit components. They are shown on pages 11 to 13.
Cap Tube Elimination
Diagram (3A) – Standard control circuit
Sentronic+ continues to add system reliability by removing the traditional cap
tube oil pressure controls that are prone to refrigerant leaks.
Precise Timing
Identical to the current Sentronic the Sentronic+ uses a precise timing
circuit that is not susceptible to low voltage or brown out conditions. The
memory in the timing circuit
Diagram (4A) – Standard control with added alarm circuit
Diagram (5A) – Standard control with alarm and current sensing relay circuit
Diagram (6) – Standard control with alarm, current sensing relay and separate
control voltage
© 2024 Copeland
14
www.copeland.com
MAY 2024
BULLETIN AE8-1275 R10
Start-Up Quick Checks
Checking the Sensor
Unplug the sensor and start the compressor. The Sentronic module LED should be red. Simultaneously measure the oil pump pressure vs. crankcase pressure. Monitor the two terminals at the back of the sensor with an ohmmeter. If the differential pressure is below the range of 7 to 9 PSID, the sensor circuit should be open. If the pressure is above 12 to 14 PSID, the sensor circuit should be closed.
Connecting the Sentronic+ Module to an Older Sentronic Sensor
Checking the Installed Sentronic+
Removing the cable from the old Sentronic module:
Module Shut off the compressor. Unplug the sensor. Verify the module is
powered by reading control voltage between the 240V (or 115V) terminal and the
L (or 2 if separate control is used) terminal.
Start the compressor with the sensor unplugged. Recheck to make sure the
module voltage is still present. After 120 seconds +/- 15 seconds, the L-M
contact should open and shut off the compressor.
· Disconnect power to the old module · Disconnect the cable from the sensor ·
Remove the cover from the old module · Remove the two cable quick connections
from the
circuit board · Using pliers, squeeze the strain relief slots and
pull to remove the cable from the module · Remove the old module from the
compressor
Removing the cable from the new Sentronic+ module:
Interchangeability of Sentronic and Sentronic+ Modules and Sensors
The new Sentronic+ oil pressure control uses both a new module and a new
sensor. The sensors and module can be made compatible with older generation
components if the following steps are taken:
To use a Sentronic+ module with an older Sentronic sensor, the original
Sentronic sensor cable must be wired to the new Sentronic+ module.
· Remove the cover from the Sentronic+ module · Pull the 2-cable quick
connects from the circuit
board (these are labeled “Org” and “Red”) · Remove the wires from the strain
relief (note the
routing of the wires for future reference) and lift the wires out · Remove the
wire cable from the module by twisting the conduit counterclockwise and gently
pulling
Connecting the old cable to the Sentronic+ module:
To use an older Sentronic module with a Sentronic+ sensor, the new Sentronic+
cable must be wired to the Sentronic module.
There is an older generation Sentronic module which is fully compatible with
the new Sentronic+ sensor. It is supplied with the new (Sentronic+) cable
which is gray for identification purposes, see illustration.
· Trim approximately 2″ of cable sheathing from the module end of the old
cable, taking care not to nick the wire insulation
· Feed the wires into the module through the hole in the bottom of the case
· Leaving enough lead length to reach the quick connects, push the wires into
the strain relief.
· Connect the 2 quick-connects to the “ORG” and “RED” spades. (Note: the
connections may be
© 2024 Copeland
15
www.copeland.com
MAY 2024
BULLETIN AE8-1275 R10
interchanged; there is no polarity on these wires). Refer to the figure below.
· Install the module to the compressor and make wiring and sensor connections
per the general instructions.
Connecting the old Sentronic Module to a Newer Sentronic+ Sensor
Removing the cable from the new Sentronic+ module:
· Disconnect power to the module Disconnect the cable from the sensor
· Remove the cover from the Sentronic+ module · Pull the 2 cable quick
connects from the circuit
board (these are labeled “Org” and “Red”) · Remove the wires from the strain
relief by lifting
the wires out · Remove the wire cable from the module by
twisting the conduit counterclockwise and gently pulling · Removing the cable
from the old Sentronic module: · Remove the cover from the old module · Remove
the two cable quick connections from the circuit board · Using pliers, squeeze
the strain relief slots and pull to remove the cable from the module
· Retain the strain relief from the cable for use on the Sentronic+ cable
· Connecting the new cable to the old Sentronic module:
· Position the strain relief on the new cable at the termination of the
conduit
· Feed the wires into the module through the hole in the bottom of the case
· Push the strain relief into position to lock it · Connect the two quick
connects to the circuit
board. There is no polarity on the leads. · Install the module on the
compressor and make
wiring and sensor connections per the general instructions
Sentronic+ Terminal Strip
· The Sentronic+ module terminal strip is designed to accept a bare wire end
instead of a spade terminal
· If a Sentronic+ module is being retrofitted to a system with spade
connections, the spade may be clipped off and ¼” of the wire end stripped. Or,
one leg of the spade may be clipped off for insertion into the terminal strip
© 2024 Copeland
16
www.copeland.com
MAY 2024 How to Check a Sentronic Installed in a System
BULLETIN AE8-1275 R10
© 2024 Copeland
17
www.copeland.com
MAY 2024
BULLETIN AE8-1275 R10
Revision Tracking R10 The document format has been updated to the new Copeland format. All occurrences of “Emerson” have been removed. A note regarding A3 and R290 venting has been updated.
© 2024 Copeland
18
www.copeland.com
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>