Danfoss PVG 100 Electrical Actuating Module Installation Guide

September 13, 2024
Danfoss

Danfoss PVG 100 Electrical Actuating Module

Installation Guide

Electrical Actuating Module

PVE series 4 for PVG 32 and PVG 100

Oil flow direction for standard assembled group@

For Technical Information, see Danfoss.com

Mounting PVE

Instruction covers

  • Protect LVDT-pin if present
  • Ensure O-rings are in place
  • Ensure gasket when using AMP and DIN/Hirschmann connector
  • Do not over torque

warning
PVEA is not for use on PVG 100

All PVE variants. PVEO and PVEO-R are without LVDT

Version ON/OFF

  • Ground pins are internally connected.

  • Pin 3 is not connected on
    Hirschmann/DIN version of PVEO.

  • UDC2 supplies electronics for feedback signal on PVEO-DI.

Connection PVEO with direction indication (DI)

Connector 1 A U DC B U DC Gnd Gnd
AMP (grey) p 1 p 2 p 3 p 4
Connector 2 DI-B DI- A Gnd U DC 2
--- --- --- --- ---
AMP (black) p 1 p 2 p 3 p 4

Connection PVEO standard

Connector A B
AMP/Hirschmann/DIN pin 1 pin 2
Deutsch pin 1 pin 4
Function A (pin 1) B (pin 2)
--- --- ---
Neutral 0 0
Q: P ® A UDC 0
Q: P ® B 0 UDC

Control all PVEO

Connector A B

AMP

Hirschmann/DIN

| pin 1| pin 2
Deutsch| pin 1| pin 4

DI general not

  • On DI versions two UDC connections (UDC and UDC2) are necessary.
    UDC will supply the electronics and

  • UDC2 will supply the solenoid valves  two ground pins are internally connected.
    With advantages two separate power supplies can be used, see also Technical information for PVE series 4.

Proportional Version

Standard PVE
Connection PVEA/PVEH/PVEM/PVES/PVEU – also with  oat B four pin

Connector U S U DC Gnd Error
AMP pin 1 pin 2 pin 3 pin 4
Hirschmann/ DIN pin 2 pin 1 gnd pin 3
Deutsch pin 1 pin 4 pin 3 pin 2
  • On PVEM the error pin is not used and not connected (pin 3 Hirschmann/DIN).
  • Ground pins are internally connected.

Control (US) for standard mounted PVEA/ PVEH/ PVEM/ PVES

Function Voltage relative PWM
Neutral 0,5 • UDC 50%
Q: P ® A 0,5 ® 0,25 • UDC 50% ® 25%
Q: P ® B 0,5 ® 0,75 • UDC 50% ® 75%
Function Voltage relative PWM
--- --- ---
Neutral 0,5 • UDC 50%
Q: P ® A 0,5 ® 0,34 • UDC 50% ® 34%
Q: P ® B 0,5 ® 0,65 • UDC 50% ® 65%
Float 0,75 • UDC 75%

Standard PVE with DI
Connection PVE with direction indication (DI)

Connector 1 U S U DC 1 Gnd Error
AMP (grey) p 1 p 2 p 3 p 4
Deutsch p 1 p 4 p 3 p 2
Connector 2 DI-B DI- A Gnd U DC 2
--- --- --- --- ---
AMP (black) p 1 p 2 p 3 p 4
Deutsch p 4 p 3 p 2 p 1

Control (US) for standard mounted PVEA–DI/ PVEH–DI

Function U S PWM
Neutral 0,5 • UDC 50%
Q: P ® A 0,5 ® 0,25 • UDC 50% ® 25%
Q: P ® B 0,5 ® 0,75 • UDC 50% ® 75%
  • Ground pins are internally connected.
  • UDC2 only supplies electronics for feedback signal and error pin on PVEA-DI / PVEH-DI. Two separate power sources can be used.

Standard PVE with SP
Connection PVE with Spool Position (SP)

Connector U S Error SP Gnd U DC
Deutsch p 1 p 2 p 4 p 5 p 6

Control (US) for standard mounted PVES-SP

Function U S PWM
Neutral 0,5 • UDC 50%
Q: P ® A 0,5 ® 0,25 • UDC 50% ® 25%
Q: P ® B 0,5 ® 0,75 • UDC 50% ® 75%

PVE with separate
Float pin Connection PVEH with float A six pin

Connector| U S (control)| U DC (power)| Float| Ground| Error
---|---|---|---|---|---
AMP| pin 1| pin 2| pin 5| pin 3| pin 4
Deutsch| pin 1| pin 6| pin 3| pin 5| pin 2

PWM controlled PVE – PVEP Connection PVEP

Connector| PWM A| Error| PWM B| Gnd| U DC
---|---|---|---|---|---
Deutsch| p 1| p 2| p 3| p 5| p 6
Function| PWM A| PWM B
---|---|---
Neutral| < 10%| < 10%
Q: P ® A| 10% ® 80%| < 10%
Q: P ® B| < 10%| 10% ® 80%

Safety and Monitoring

Fault monitoring overview

__

Type

| __

Fault monitoring

| __

Delay before error out

| __

Error mode

| Error output status| Fault output on PVE 1)| __

LED light

| Memory (reset needed)
---|---|---|---|---|---|---|---
PVEO PVEM| No fault monitoring| –| –| –| –| –| –
__

__

PVEA PVEH PVEP PVES PVEU

| __

Active

| __

500 ms

(PVEA: 750 ms)

| No fault| Low| < 2 V| Green| –
Input signal faults| __

High

| __

__

~UDC

| Flashing red| __

Yes

Transducer (LVDT)| Constant red
Close loop fault
__

Passive

| __

250 ms

(PVEA: 750 ms)

| No fault| Low| < 2 V| Green| –
Input signal faults| __

High

| __

__

~UDC

| Flashing red| __

No

Transducer (LVDT)| Constant red
Close loop fault
PVE

Float six pin

| __

Active

| 500 ms| Float not active| __

High

| __

__

~UDC

| __

Constant red

| __

Yes

750 ms| Float still active

  1. Measured between fault output pin and ground.

Spool Position Feedback (-SP

The –SP functionality is a 0,5V to 4,5V inverted feedback with 2,5V as neutral value.

Direction Indication Feedback (-DI)

As shown in the figure, both “DI-A” and “DI-B” signals are “High” when the spool is in neutral position. When the spool is moving in the A direction, the “DI-A” signal goes “Low” and the “DI-B” signal stays “High”. The reverse is true when the spool is moved in the B direction.
Direction Indication Feedback (-DI)

Both direction indication signals go low when the error indicator goes high.

Values for both Direction Indicators, pin A and pin B

Transition to low from high 0.8 ± 0.1 mm [0.031 in]
Transition to high from low 0.4 ± 0.1 mm [0.015 in]
Transition to low both pins error pin goes high
Maximum load of “DI-A” , “DI-B” 50 mA
Voltage U DC high by load 20 mA > UDC –1.5 V
Voltage U DC high by load 50 mA > UDC –2.0 V
Voltage low < 0.2 V

Technical data

The following technical data are from typical test results. For the hydraulic system a mineral based hydraulic oil with a viscosity of 21 mm2/s [102 SUS] and a temperature of 50°C [122°F] were used.

Supply voltage U DC rated 12 V DC 24 V DC
range 11 V to 15 V 22 V to 30 V
max. ripple 5%
Current consumption at rated voltage 0.65 A @ 12 V 0.33 A @ 24 V
Signal voltage (PVEM) neutral 0.5 x UDC
A-port « B-port 0.25 • UDC to 0.75 • UDC
Signal current at rated voltage (PVEM) 0.25 mA 0.50 mA
Input impedance in relation to 0.5 • U DC 12 KW
Power consumption 8 W

PVEA, PVEH, PVEP, PVES, PVEU

Supply voltage U DC rated / range 11 V to 32 V
max. ripple 5%

Current consumption

at rated voltage              PVEH/PVEP/PVES/PVEU (PVEA)

| 0.57 (0.28) A @ 12 V| 0.3 (0.15) A @ 24 V
__

__

__

Signal voltage

| PVEA/PVEH/PVES – neutral| 0.5 x UDC
PVEA/PVEH/PVES – A-port « B-port| 0.25 • UDC to 0.75 • UDC
PVEU – neutral| 5V
PVEU – A-port « B-port| 2.5V to 7.5V
PVEP – neutral| A< 10%, B < 10%
PVEP – A-port| 10%<A<80%, B< 10%
PVEP – B-port| A< 10%, 10%<B<80%
Signal currentat rated voltage| 0.25 mA to 0.70 mA
Input impedance in relation to 0.5 • U DC| 12 KW
Input capacitor| 100 hF
Power consumption        PVEH/PVEP/PVES/PVEU (PVEA)| 7 (3.5) W

Oil viscosity

__

__

Oil viscosity

| range| 12 – 75 mm2/s [65 – 347 SUS]
---|---|---
min.| 4 mm2/s [39 SUS]
max.| 460 mm2/s [2128 SUS]

Note: Max. start up viscosity 2500 mm2/s

NB: In particularly exposed applications, protection by screen is recommended.

Bleeding
If the group is installed vertically, it is recommended to bleed it at the adjusting screws (Pos.A)
Note: Because of the hydraulic build-up of PVEA, it may be necessary to bleed the PVEK.

Protection
All PVE modules comply with protection class IP65 in accordance with IEC 529. However, in particularly exposed applications protection in the form of screening is recommended.

Warning

All marks and brands of valves – inclusive proportional valves – can fail and cause serious damage. It is therefore important to analyse all aspects of the application.
Because the proportional valves are used in many different operation conditions and applications, the manufacturer of the application is alone responsible for making the final selection of the products – and assuring that all performance, safety and warning requirements of the application are met.
The process of choosing the control system – and safety level – could e.g. be governed by EN 954-1 (Safety related parts of control system). See also Technical information for PVE series 4.

Accessories

Connector code numbers

Part number| Name|
---|---|---
157B4992| AMP CONNECTING KIT (GREY)| 4 pin with housing, contact and wire sealing
157B4993| AMP CONNECTING KIT (BLACK)| 4 pin with housing, contact and wire sealing
984L3165| EL-PLUG, ON-OFF black| Hirschmann DIN connector set*

Set of seals code numbers

Part number Name Actuator
157B4997 Set of seals PVE for PVG 32/ PVG 100
155G8519 Set of seals PVE for PVG 120
11061235 Set of seals PVHC for PVG 32/ PVG 100

Cables code numbers

Feature Wire colors Length Code number
Connector pin 1 pin 2 pin 3

pin 6
Deutsch| 4 pin| white| blue| yellow| red| —| —| 4 m| 11007498
6 pin| white| blue| yellow| red| black| green| 4 m| 11007513
AMP| 4 pin| white| blue| yellow| red| —| —| 4 m| 157B4994
6 pin| white| red| black| yellow| green| blue| 5 m| 157B4974
AMP/black coding| 4 pin| white| blue| yellow| red| —| —| 4 m| 157B4995

520L0619 • Rev EB • Mar 2014