ANLY AVR172 AVR 3-Phase Voltage Relay User Manual
- September 13, 2024
- ANLY
Table of Contents
ANLY AVR172 AVR 3-Phase Voltage Relay
AVR
3-PHASE(SINGLE PHASE)
VOLTAGE RELAY User’s Manual
RESTRICTIONS ON USE
When using this product in applications that require particular safety or when
using this product in important facilities, please pay attention to the safety
of the overall system and equipment. Install fail-safe mechanisms, perform
redundancy checks and periodic inspections and adopt other appropriate safety
measures when it is necessary.
SAFETY PRECAUTION
This manual uses the following symbols to ensure safe operation of this product.
-
WARNING
Warnings are indicated when mishandling this product might result in death or serious injury to user. -
CAUTION
Cautions are indicated when mishandling this product might result in minor injury to the user, or only physical damage to the timer.
WARNING
- Note this incorrect wiring of this product can damage it and lead to other hazards. Make sure the product has been correctly wired before turning the power ON.
- Before wiring, or removing / mounting the product, be sure to turn the power OFF. Failure to do so might cause electric shock.
- Do not touch electrically charged parts such as the power terminals. Doing so might cause electric shock.
- Do not disassemble the product. Doing so might cause electric shock or faulty operation.
CAUTION
- Use the product within the operating ranges recommended in the specification (temperature, humidity, voltage, shock, mounting direction, atmosphere and etc.). Failure to do so might cause fire or faulty operation.
- Make sure the product is firmly connected to the socket. Failure to do so might cause electric shock or fire.
SPECIFICATIONS
SPECIFICATIONS
Operating voltage| AC(V): 220, 240, 380, 415, 440
Allowable setting voltage range| ±5%~±20% of rated operating voltage
Rated frequency| 50 / 60 Hz
Rest time| AVR165: MAX 3sec fixed / AVR172: 0~10sec adjustable
Contact rating| 250VAC 5A (Resistive load)
Power consumption| Approx. 3VA
Life| Mechanical : 5,000,000 times / Electrical : 100,000 times
Ambient temperature| -10 ~ +50 °C (without condensation & freezing)
Ambient humidity| MAX 85% RH (without condensation)
Altitude| MAX 2000m
Weight| Approx. 170g
NAMES AND FUNCTIONS OF FACEPLATE
SETTING PROCEDURE
-
1. Over voltage setting Reset delay setting
Set the desired value for over voltage. This function can be turn off by turning the knob to off position.
Set the desired value for reset delay time. -
Under voltage setting4. Tripping delay setting
Set the desired value for under voltage. This function can be turn off by turning the knob to off position. Set the desired value for tripping delay time.
INDICATIONS
-
STATUS
-
Normal :
When the voltage is within the set over and under level, balance, phase sequence, and all phase are present, then the red LED starts lighting. -
Over :
If the voltage rises above the adjusted over level then the red LED starts blinking once
and go out three times. -
Under :
If the voltage drops below the adjusted under level then the red LED starts blinking twice and go out twice.
-
-
POWER
A green LED indicates the presence of the power supply voltage.-
Unbalance :
If the voltage is unbalance then the red LED starts blinking three times and go out once. -
Phase reverse :
If the phase reverse then the red LED starts to keep blinking . -
Phase loss :
If the phase loss then the red LED starts to go out.
-
CONNECTION
TIMING CHART
DIMENSION(mm)
ANLY ELECTRONICS CO., LTD.
http://www.anly.com.tw
Printed in Taiwan