Carrier 30RC 020-060 Variable Speed Fan Control Installation Guide
- September 14, 2024
- Carrier
Table of Contents
Carrier 30RC 020-060 Variable Speed Fan Control Installation Guide
30RC 020-060,
38RCS 025-050,
38RCD 025-060
Greenspeed® Variable Speed Fan Control
Installation Instructions
Part No: 30RC70004901, 30RC70005001, 30RC70005101, 30RC70005301, 30RC70005401, 30RC70005501, 30RC70005701, 30RC70005801, 30RC70005901
CONTENTS
Page
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . 1 GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Inspect Shipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Step 1 — Install Wind Baffle Accessory Kit . . . . . . . 6 Step 2 — Mount the VFD . . . . . . . . . . . . . . . . . . . . . . 6 • 20-30 TON UNITS
- 35-60 TON UNITS
Step 3 — Control Panel Wiring . . . . . . . . . . . . . . . . . 7 Step 4 — Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
SAFETY CONSIDERATIONS
Installing, starting up, and servicing air-conditioning equipment can be hazardous due to system pressures, electrical components, and equipment location.
Only trained, qualified installers and service mechanics should install, start up, and service this equipment.
Untrained personnel can perform basic maintenance functions, such as cleaning coils. All other operations should be performed by trained service personnel. Qualified installers and service tech nicians are required to have been trained on the following topics when installing and servicing air-conditioning equipment with A2L refrigerant such as R-32:
- Explosive potential of A2L refrigerants
- Potential ignition sources
- Safety measures for unventilated and ventilated rooms or enclosures
- Refrigerant detectors
- Concept of sealed components and sealed enclosures according to IEC 60079-15:2010
- Correct work procedures for the following:
- Commissioning
- Maintenance
- Repair
- Decommissioning
- Disposal
See Controls and Troubleshooting Guide for complete guidelines.
When working on the equipment, observe precautions in the literature and on tags, stickers, and labels attached to the equipment.
- Follow all safety codes.
- Keep quenching cloth and fire extinguisher nearby when brazing.
- Wear safety glasses and work gloves.
- Use care in handling, rigging, and setting bulky equipment.
IMPORTANT: This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with these instructions, may cause radio interference. It has been tested and found to comply with the limits of a Class A computing device pursuant to International Standard in North America EN 61000-2/3, which are designed to provide reasonable protection against such interference when operated in a commercial environment.
CAUTION
This system uses an A2L refrigerant (R-32) which have higher pressures than R-22 and other refrigerants. No other refrigerant can be used in this system. Failure to use gauge set, hoses, and recovery systems designed to handle refrigerant R-32 may result in equipment damage or personal injury. Refer to Check Refrigerant Circuit section of the 30RC or 38RC chiller installation instructions for guidelines on proper A2L refrigerant handling and equipment used for A2L refrigerant. If unsure about equipment, consult the equipment manufacturer.
WARNING
This product can expose you to chemicals including lead and lead components, which are known to the State of California to cause cancer and birth defects or other reproductive harm. For more information, go to www.P65Warnings.ca.gov.
WARNING
Electrical shock can cause personal injury and death. Shut off all power to this equipment during installation and service. There may be more than one disconnect switch. Tag all disconnect locations to alert others not to restore power until work is completed.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Catalog No. 04-53300279-01 Printed in U.S.A. Form No. 30-6ASI Pg 1 5-24 Replaces: NEW
CAUTION
DO NOT re-use compressor oil or any oil that has been ex posed to the atmosphere. Dispose of oil per local codes and regulations. DO NOT leave refrigerant system open to air any longer than the actual time required to service the equipment. Seal circuits being serviced and charge with dry nitrogen to prevent oil contamination when timely repairs cannot be com
Table 1 — Greenspeed® Accessory Usage
MODEL/UNIT SIZES
30RC 020-030
30RC 035-050
30RC 055, 060
PART NO. VOLTAGE 30RC70004901
30RC70005001 230 30RC70005101
pleted. Failure to follow these procedures may result in dam
30RC70005301
38RC 025,030
38RC 035-050
38RC 055, 060
age to equipment.
30RC70005401 380/460 30RC70005501
WARNING
30RC70005701
38RC 025,030
38RC 035-050
38RC 055, 060
DO NOT USE TORCH to remove any component. System contains oil and refrigerant under pressure.
To remove a component, wear protective gloves and goggles and proceed as follows:
- Shut off electrical power to unit.
- Recover refrigerant to relieve all pressure from system using both high-pressure and low pressure ports. c. Traces of vapor should be displaced with nitrogen and the work area should be well ventilated. Refrigerant in contact with an open flame produces toxic gases. d. Cut component connection tubing with tubing cutter and remove component from unit. Use a pan to catch any oil
30RC70005801 575 30RC70005901
Inspect Shipment
Inspect contents of the accessory package before installing. File a claim with the shipping company if there is shipping damage. Contact your local Carrier Representative if any parts are missing. See Table 1 for Greenspeed accessory usage. See Table 2 for VFD Usage and Table 3 for accessory package contents.
Table 2 — VFD Usage
that may come out of the lines and as a gauge for how
30RC/38RC
VOLTAGE
208/230
380
460
575
208/230
380
460
575
208/230
380
460
575
208/230
380
460
575
208/230
380
460
575
208/230
380
460
575
208/230
380
460
575
208/230
380
460
575
208/230
380
460
575
much oil to add to the system.
- Carefully un-sweat remaining tubing stubs when necessary. Oil can ignite when exposed to torch flame.
UNIT SIZE FAN DRIVE PART NO. HR46ZP007
HR46ZP008
020
Failure to follow these procedures may result in personal inju ry or death.
GENERAL
025
This book contains instructions for the installation of the Greenspeed Variable Speed Fan Control.
The Greenspeed accessory uses a single variable frequency drive 030
(VFD) to control the speed of the condenser fans. All fans will op erate at the same speed. This can reduce energy usage and noise at off design conditions. The VFD is controlled on the unit LEN bus. The PIC6 controller on the unit monitors all pressure and tempera ture inputs to determine the most efficient and stable fan speed.
035
Typically the fan speed will increase with high ambient tempera ture to reduce head pressure. Opposite is true for lower ambient temperatures.
This accessory will also allow the unit to run down to –20°F ambi ent with the addition of the wind baffle accessory. At low ambient
040
conditions, high winds can have a detrimental effect on head pres sure control. The wind baffles prevent wind from blowing across the condenser coil to alleviate this issue.
045
IMPORTANT: Wind baffles are required for ambient temperatures below 35°F if wind velocity is anticipated to be greater than 5 mph (8 km/h).
050
055
060
HR46ZP008 HR46ZP003 HR46ZP007 HR46ZP008 HR46ZP008 HR46ZP003 HR46ZP007 HR46ZP008 HR46ZP008 HR46ZP003 HR46ZQ001 HR46ZR001 HR46ZR001 HR46ZQ002 HR46ZQ001 HR46ZR001 HR46ZR001 HR46ZQ002 HR46ZQ001 HR46ZR001 HR46ZR001 HR46ZQ002 HR46ZQ001 HR46ZR001 HR46ZR001 HR46ZQ002 HR46ZS001 HR46ZS005 HR46ZS005 HR46ZR003 HR46ZS001 HR46ZS005 HR46ZS005 HR46ZR003
2
Table 3 — Accessory Package Contents
VOLTAGE | PART NUMBER | QTY |
---|---|---|
230/380/460/575 | 30RCHSCALXCA10 | 1 |
38AP404952 | 3 | |
38AP504900 | 1 | |
38AP504273 | 1 | |
38APMACBFG-A00 | 1 | |
See Table 2. | 1 | |
38APHLSBF1-A00 | 1 | |
38APHLSSF2-A00 | 1 | |
38APHSCSFV-A01 | 1 | |
AL04AU166 | 4 | |
AL01AU168 | 2 | |
HY84DA022 | 1 | |
00PPN500000302A | 6 | |
AL56ZA003 | 30 | |
AA06BR200 | 6 | |
AU02AB202 | 6 | |
38AP504929 | 1 | |
30-6ASI | 1 | |
230 | 38AP504954 | 1 |
38AP504972 | 1 | |
2004592371 | 1 | |
2004606726 | 1 | |
2004590453 | 1 | |
30RCHSCALXCA30 | 1 | |
38AP404952 | 3 | |
See Table 2. | 1 | |
38APHLSBF1-A00 | 1 | |
38APHLSSF2-A00 | 1 | |
38APHLSMF3-A00 | 1 | |
38APHSCSFV-A21 | 1 | |
HY10JK040 | 3 | |
JT60060 | 3 | |
AL04AU166 | 4 | |
HW60HH006 | 1 | |
38APPAAAAA-A00 | 1 | |
AL01AU168 | 2 | |
HY84DA022 | 1 | |
00PPN500000302A | 6 | |
AL56ZA003 | 35 | |
AA06BR200 | 6 | |
AU02AB202 | 6 | |
38AP504929 | 1 | |
30-6ASI | 1 |
ACCESSORY DESCRIPTION LEN Cable
Conduit
Drive Mounting Plate
Drive Enclosure
Terminal Block Shroud
Fan (VFD)
OFM-1 Harness (25-60 Ton)
30RC70004901
30RC70005301
30RC70005701
(20-30 Ton)
30RC70005001 (35-50 Ton)
OFM-2 Harness (40-60 Ton)
Low Ambient Harness (10-15 Ton) No. 8, 1/2 in. long Trilobe
No. 8, 3/4 in. long Trilobe
3 Pole 600-v Terminal Block
Mounting Hardware – Drive (6 mm) Mounting Hardware – Sheet Metal Mounting Hardware – 5/16 x 1
Mounting Hardware – Washer
Grill
Instructions
Drive Mounting Plate
Drive Enclosure
RH Side Adapter Plate (35-60 Ton Only) LH Side Adapter Plate (35-60 Ton Only) Top Adapter Plate (35-60 Ton Only) LEN Cable
Conduit
Fan (VFD)
OFM-1 Harness (40-60 Ton)
OFM-2 Harness (40-60 Ton)
OFM-3 Harness (40-60 Ton)
Greenspeed® Harness (230-v, 35-60 Ton) Class J Quick Blow Fuse (40A 600-v) Class J Fuse Holder (35-60A 600-v) No. 8, 1/2 in. long Trilobe
1.00 in. Conduit Clamp
1 in. x 12 in. Varnish Cloth
No. 8, 3/4 in. long Trilobe
Terminal Block (3 Pole, 600-v)
Mounting Hardware – Drive (6 mm) Mounting Hardware – Sheet Metal Mounting Hardware – 5/16 x 1
Mounting Hardware – Washer
Grill
Instructions
3
Table 3 — Accessory Package Contents (cont)
VOLTAGE | PART NUMBER | QTY |
---|---|---|
460/380/575 | 38AP504954 | 1 |
38AP504972 | 1 | |
2004592371 | 1 | |
2004606726 | 1 | |
2004590453 | 1 | |
30RCHSCALXCA30 | 1 | |
38AP404952 | 3 | |
See Table 2. | 1 | |
38APHLSBF1-A00 | 1 | |
38APHLSSF2-A00 | 1 | |
38APHLSMF3-A00 | 1 | |
38APHSCSFV-A11 | 1 | |
HY10JK025 | 3 | |
JT60030 | 3 | |
AL04AU166 | 4 | |
HW60HH006 | 1 | |
38APPAAAAA-A00 | 1 | |
AL01AU168 | 2 | |
HY84DA022 | 1 | |
00PPN500000302A | 6 | |
AL56ZA003 | 35 | |
AA06BR200 | 6 | |
AU02AB202 | 6 | |
38AP504929 | 1 | |
30-6ASI | 1 | |
230 | 38AP504954 | 1 |
38AP504972 | 1 | |
2004592371 | 1 | |
2004606726 | 1 | |
2004590453 | 1 | |
30RCHSCALXCA30 | 1 | |
38AP404952 | 3 | |
38APHLSBF1-A00 | 1 | |
38APHLSSF2-A00 | 1 | |
38APHLSMF3-A00 | 1 | |
38APHLSMF4-A00 | 1 | |
38APHSCSFV-A21 | 1 | |
HY10JK040 | 3 | |
JT60060 | 3 | |
AL04AU166 | 4 | |
HW60HH006 | 1 | |
38APPAAAAA-A00 | 1 | |
AL01AU168 | 2 | |
HY84DA022 | 1 | |
00PPN500000302A | 6 | |
AL56ZA003 | 35 | |
AA06BR200 | 6 | |
AU02AB202 | 6 | |
38AP504929 | 1 | |
30-6ASI | 1 |
ACCESSORY DESCRIPTION Drive Mounting Plate
Drive Enclosure
RH Side Adapter Plate (35-60 Ton Only)
LH Side Adapter Plate (35-60 Ton Only)
Top Adapter Plate (35-60 Ton Only)
LEN Cable
Conduit
Fan (VFD)
OFM-1 Harness (40-60 Ton)
OFM-2 Harness (40-60 Ton)
OFM-3 Harness (40-60 Ton)
30RC70005401, 30RC70005801 (35-50 Ton)
30RC70005101 (55-60 Ton)
Greenspeed® Harness (35-60 Ton) Class J Quick Blow Fuse 25A 600-v 1-30A 600-v Class J Fuse Holder No. 8, 1/2 in. long Trilobe
1.00 in. Conduit Clamp
1 in. x 12 in. Varnish Cloth
No. 8, 3/4 in. long Trilobe
Terminal Block (3 Pole 600-v)
Mounting Hardware – Drive (6 mm) Mounting Hardware – Sheet Metal Mounting Hardware – 5/16 x 1
Mounting Hardware – Washer
Grill
Instructions
Drive Mounting Plate
Drive Enclosure
RH Side Adapter Plate (35-60 Only) LH Side Adapter Plate (35-60 Only) Top Adapter Plate (35-60 Only)
LEN Cable
Conduit
OFM-1 Harness (40-60 Ton)
OFM-2 Harness (40-60 Ton)
OFM-3 Harness (40-60 Ton)
OFM-4 Harness (40-60 Ton)
Greenspeed® Harness (230-v, 35-60 Ton) Class J Quick Blow Fuse (40A, 600-v) Class J Fuse Holder (35-60A, 600-v) No. 8, 1/2 in. long Trilobe
1.00 in. Conduit Clamp
1 in. x 12 in. Varnish Cloth
No. 8, 3/4 in. long Trilobe
Terminal Block (3 Pole 600-v)
Mounting Hardware – Drive (6 mm) Mounting Hardware – Sheet Metal Mounting Hardware – 5/16 x 1
Mounting Hardware – Washer
Grill
Instructions
4
Table 3 — Accessory Package Contents (cont)
ACCESSORY DESCRIPTION
30RC70005501, 30RC70005901 (55-60 Ton)
VOLTAGE | PART NUMBER | QTY |
---|---|---|
460/380/575 | 38AP504954 | 1 |
38AP504972 | 1 | |
2004592371 | 1 | |
2004606726 | 1 | |
2004590453 | 1 | |
30RCHSCALXCA30 | 1 | |
38AP404952 | 3 | |
38APHLSBF1-A00 | 1 | |
38APHLSSF2-A00 | 1 | |
38APHLSMF3-A00 | 1 | |
38APHLSMF4-A00 | 1 | |
38APHSCSFV-A11 | 1 | |
HY10JK025 | 3 | |
JT60030 | 3 | |
AL04AU166 | 4 | |
HW60HH006 | 1 | |
38APPAAAAA-A00 | 1 | |
AL01AU168 | 2 | |
HY84DA022 | 1 | |
00PPN500000302A | 6 | |
AL56ZA003 | 35 | |
AA06BR200 | 6 | |
AU02AB202 | 6 | |
38AP504929 | 1 | |
30-6ASI | 1 |
Drive Mounting Plate
Drive Enclosure
RH Side Adapter Plate (35-60 Only) LH Side Adapter Plate (35-60 Only) Top Adapter Plate (35-60 Only) LEN Cable
Conduit
OFM-1 Harness (40-60 Ton)
OFM-2 Harness (40-60 Ton)
OFM-3 Harness (40-60 Ton)
OFM-4 Harness (40-60 Ton)
Greenspeed® Harness (35-60 Ton) Class J Quick Blow Fuse (25A, 600-v) Class J Fuse Holder (1-30A, 600-v) No. 8 1/2 in. long Trilobe
1.00 in. Conduit Clamp
1 in. x 12 in. Varnish Cloth
No. 8 3/4 in. long Trilobe
3 Pole 600-v Terminal Block
Mounting Hardware – Drive (6 mm) Mounting Hardware – Sheet Metal Mounting Hardware – 5/16 x 1 Mounting Hardware – Washer Grill
Instructions
5
INSTALLATION
Step 1 — Install Wind Baffle Accessory Kit If the chiller is expected to run in ambient temperatures below 35°F and winds above 5 mph are expected, a wind baffle accesso ry kit is required. See below for part numbers that require the wind baffle accessory kit.
- 30RA-900—065 (sizes 020, 035, 040)
- 30RA-900—066 (sizes 020, 030, 045-060)
NOTE: Unit sizes 035-060 require two kits.
Step 2 — Mount the VFD
Verify the drive nameplate rating versus the unit nameplate rating for correct voltage range. Check the VFD part number from Table 2.
Remove panel on side of unit where VFD will be mounted. This panel can be discarded. See Fig. 1.
Mount VFD to VFD mounting bracket using 6 mm thread form ing screw. Attach drive enclosure to mounting plate using sheet metal screw. See Fig. 2.
Connect 3 conduit assemblies to the 3 holes on the side of the en closure. Conduit nut should be on the inside of the enclosure, to wards the VFD, and conduit should be outside of the enclosure.
30RC 020-030 Size Units
38RC 025-030 Size Units
Place drive inside unit enclosure and mount to unit base. Use 5/16 x 1 screws for VFD mounting plate and sheet metal screw for enclosure. On most units the VFD assembly can be rotated to fit through the VFD opening in the unit side panel. On some of the smaller units where internal piping may interfere with this proce- dure, the side panel of the unit should be removed. If removing the side panel, brace the weight of the control panel to prevent dam age to the center post of the unit. The VFD assembly enclosure will be flush with side panel on 20-30 ton units after mounting. On 35-60 ton units, the enclosure will mount with a 1 in. gap between the enclosure and the side panel.
CAUTION
Internal refrigerant tubing is under high pressure. Do not damage piping while mounting VFD assembly. Serious injury may occur.
20-30 TON UNITS
Fasten drive enclosure to unit side panel using sheet metal screws. 35-60 TON UNITS
Use spacer brackets to mount VFD assembly to unit side panel. Attach with sheet metal screws. See Fig. 3.
30RC 035-060 Size Units
38RC 040-060 Size Units
Control Panel
Control Panel
Drive Mounting
Plate
Drive Enclosure
VFD Mounting
Position
Fig. 1 — Drive Mounting Location Fan VFD
VFD Mounting
Position
Adapter Plates
Fig. 2 — Drive to Enclosure Assembly Fig. 3 — VFD Assembly to Unit Side Panel (35-60 Ton)
6
Step 3 — Control Panel Wiring
- Mount fuse block, terminal block, and terminal block cover per panel layout. See Fig. 4 and 5. Wiring for 20-30 ton units will require fuse blocks and fuses that already exist in the panel. Fan contactors may be removed if more panel space is needed. If contactors are removed, remove any power wires attached to them. Control wires may be cut and terminated to assure they cannot ground to panel.
- Replace fan motor cables with cables supplied. Connect con trol box end to VFD terminal block installed in “Mount the VFD” on page 6. See Fig. 6 for identification of fan motor designations. Use wire ties to secure fan wire routing. At fan motor, ensure a drip loop is created when routing the wire to the motor. See Fig. 7.
- Install Greenspeed harness between control panel and VFD. This consists of two cables. One cable takes power from the
- Install communication cable (LEN) between control panel and VFD. Connect per markings on the harness. Ground the shield at the VFD. Do not ground it in the control panel. Do not run communication cable with power wires to the VFD. This could cause interference with the communication signal. 5. Install fuses into fuse block. See Table 4.
Table 4 — Fuse Replacement
FUSE REPLACEMENT TABLE FOR FB1/FB2
VOLTAGE | FUSE |
---|---|
208/230 | LP-CC-20 |
380
460
575
208/230| LP-CC-20
380
460
575
208/230| FNQ-R-30
380| FNQ-R-20
460| FNQ-R-17-1/2
575| FNQ-R-15
UNIT SIZE FUSE BLOCK 020-030
VFD fuse block to the drive input, L1/L2/L3. The other cable takes power from the drive output (U/V/W), to the VFD ter minal block to power the fans. Route cables through conduit sections at VFD enclosure.
Cooler Heater and
Reverse Rotation
035-050
055-060
VFD Fuse Blocks
FB1/FB2
| | | | |
| | | | |
| | | | |
| C| | | |
| | | | |
| | | | |
| | | | |
Power Input
CIOB Stack Location (1 or 2)
Auxillary
Board
LEGEND
CB — Circuit Breaker
CCN — Carrier Comfort Network CHR — Evaporator Heater Relay CIOB — Carrier Input/Output Board FB — Fuse Block
FC — Fan Contactor
Remote Connectivity
FU — Fuse
RRB — Reverse Rotation Board/Phase Monitor TRAN — Transformer
TB — Terminal Block
SW — Switch
VFD Terminal Block
Fig. 4 — Control Panel Layout (20-30 Ton)
7
VFD Fuse Blocks
Main Box
Transformer
(Compressors) Low Ambient
Remote
Connectivity
Auxilliary
Display CIOB
(Stack of 3)
CHR
Main Box
(Compressors) RRB Power Input
| |
---|---|---
| |
---|---|---
| |
|
| |
---|---|---
| |
---|---|---
|
| | | | | | | | | | |
---|---|---|---|---|---|---|---|---|---|---|---
| | | | | | | | | |
| | | | | | | | | | |
| | | | | | | |
| | | | | | | | | |
| | | | | | | | | |
| | | | | | | | | | |
| |
---|---|---
| |
| |
|
|
|
|
|
|
|
|
|
| | |
---|---|---|---
|
---|---
|
|
|
---|---
| | | |
| | |
| | | |
| | | |
|
|
|
|
|
|
|
|
---|---
|
|
|
|
|
| |
---|---|---
| |
---|---|---
| |
| |
| | | | |
---|---|---|---|---|---
| | | | |
| | | | |
| | | | |
| | | | |
| | | | |
| | | | |
| | | | |
| | | | |
| | | | |
|
---|---
|
|
|
|
| |
---|---|---
| |
| |
| |
| |
VFD Terminal
Block
LEGEND
CCN — Carrier Comfort Network
CB — Circuit Breaker
CIOB — Carrier Input/Output
CHR — Evaporator Heater Relay
RRB — Reverse Rotation Board/Phase Monitor
VFD — Variable Frequency Drive
Pumps 2 x 30 Position TB
CCN Board
2 x TB From Main Harness
2 x Switch
4 x 5 Amp CB
| | | | | |
---|---|---|---|---|---|---
Control Box
OFM1 OFM2
Fig. 5 — Control Panel Layout (35-60 Ton)
Wire
(To Fan Motor)
Wire Tie
|
---|---
|
|
Conduit
(From Control Box)
Top View
Sizes 020-030
OFM1 OFM1 Control Box
Control Box
OFM3
Drip loop to prevent water
entering into the conduit and
then to the control box.
OFM3
OFM2
Fig. 7 — Fan Motor Wiring Connection Routing
OFM2 OFM4
Top View Top View Sizes 035-050 Sizes 055, 060
Fig. 6 — Condenser Fan Layout
8
Step 4 — Setup
Once all wiring is terminated and all covers are back in place,
power unit. See Fig. 8-10.
Set the address on the variable frequency drive (VFD) to 184. (Pa- rameter 8-31 = 184) This will allow the controller to send correct
operating parameters to the VFD. See Fig. 9.
|
---|---
|
At the PIC6 controller, configure the unit for Greenspeed control.
( MainMenu → Configuration → Factory → _vfansel =1).
NOTE: This will require a reboot of the controller.
IMPORTANT: The control power must be cycled with the correct VFD address and correct controller configuration before the variable speed fans will operate.
In the controller menu go to Quick Test1 ( MainMenu → Quick
|
---|---
|
Test1 ). Enable the quick test menu. Scroll down to Q-VFAN. En
ter 50 to drive fans to 50%. Fans should start and run at 30 Hz.
This confirms the fan VFD is operational. Enter 0 for Q-VFAN
and disable quick test. See Fig. 8.
Install grill over VFD opening. Unit is now ready for operation.
|
---|---
|
|
| |
---|---|---
| |
| |
| |
| |
| |
|
| |
---|---|---
| |
Fig. 8 — Fan Motor Power Wiring
NOTE: Address for FVFD is 184 (Parameter 8-31)Fig. 9 — LEN BUS Wiring
9
| | | | | |
---|---|---|---|---|---|---
| | | |
| | |
| | | | | |
| | | | | |
|
---|---
|
---|---
|
---|---
|
---|---
|
|
|
|
---|---
|
---|---
|
|
|
---|---
| |
---|---|---
| | | | | | | | | | | | | | |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---
| | | | | | | | | | | | | |
| | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | |
| | | | | | | | | | | | | | |
| | | | | | | | | | | |
| | | | | | | | | | | |
| | | | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | |
| | | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | |
| | | | | | | | | | | | | | |
| | | | | | | | | | | |
| | | | | | | | | | | |
| | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | |
| |
---|---|---
|
|
| |
---|---|---
| |
| |
| |
|
| | | | | |
---|---|---|---|---|---|---
| | | | | |
| | | |
| | | |
| | | |
| | | |
| | | |
| | | | |
| | | | | |
| | | | | | | | | |
---|---|---|---|---|---|---|---|---|---|---
| | | | | | |
| | | | | | |
| | | | | |
| | | | | |
| | | | | | |
|
---|---
|
|
---|---
Fig. 10 — 30RC 010-060 Power Schematic
10
© 2024 Carrier
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Catalog No. 04-53300279-01 Printed in U.S.A. Form No. 30-6ASI Pg 12 5-24 Replaces: NEW
30RC 020-060 Variable Speed Fan Control
Product Information
Specifications
-
Models: 30RC 020-060, 38RCS 025-050
-
Part Numbers: 30RC70004901, 30RC70005001, 30RC70005101,
30RC70005301, 30RC70005401, 30RC70005501, 30RC70005701,
30RC70005801, 30RC70005901 -
Catalog No.: 04-53300279-01
-
Printed in: U.S.A.
-
Form No.: 30-6ASI
Product Usage Instructions
Safety Considerations
-
Follow all safety codes.
-
Keep quenching cloth and fire extinguisher nearby when
brazing. -
Wear safety glasses and work gloves.
-
Use care in handling, rigging, and setting bulky
equipment. -
Observe precautions in the literature and on tags, stickers,
and labels attached to the equipment.
Installation and Service
-
Shut off all power to the equipment during installation and
service. -
Tag all disconnect locations to alert others not to restore
power until work is completed. -
Dispose of compressor oil properly per local codes and
regulations. -
Do not leave refrigerant system open to air longer than
necessary.
Component Removal
-
Shut off electrical power to the unit.
-
Recover refrigerant from the system using high-pressure and
low-pressure ports. -
Displace traces of vapor with nitrogen in a well-ventilated
area. -
Wear protective gloves and goggles to remove components.
-
Cut component connection tubing with a tubing cutter and remove
the component from the unit.
FAQ (Frequently Asked Questions)
Q: What should I do if I encounter a warning about lead
exposure?
A: If you encounter a warning about lead exposure, refer to
www.P65Warnings.ca.gov for more information and take necessary
precautions to minimize exposure.
Q: How should I handle disposing of compressor oil?
A: Dispose of compressor oil per local codes and regulations to
ensure proper handling and environmental protection.
30RC 020-060,
38RCS 025-050,
38RCD 025-060 Greenspeed® Variable Speed Fan Control
Installation Instructions
Part No: 30RC70004901, 30RC70005001, 30RC70005101, 30RC70005301, 30RC70005401,
30RC70005501, 30RC70005701, 30RC70005801, 30RC70005901
CONTENTS
Page SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . 1 GENERAL . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Inspect
Shipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Step 1 — Install Wind Baffle Accessory Kit . . . . . . . 6 Step 2 — Mount the
VFD . . . . . . . . . . . . . . . . . . . . . . 6 · 20-30 TON UNITS · 35-60
TON UNITS Step 3 — Control Panel Wiring . . . . . . . . . . . . . . . . . 7
Step 4 — Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
SAFETY CONSIDERATIONS
Installing, starting up, and servicing air-conditioning equipment can be
hazardous due to system pressures, electrical components, and equipment
location. Only trained, qualified installers and service mechanics should
install, start up, and service this equipment. Untrained personnel can perform
basic maintenance functions, such as cleaning coils. All other operations
should be performed by trained service personnel. Qualified installers and
service technicians are required to have been trained on the following topics
when installing and servicing air-conditioning equipment with A2L refrigerant
such as R-32: 1. Explosive potential of A2L refrigerants 2. Potential ignition
sources
3. Safety measures for unventilated and ventilated rooms or enclosures
4. Refrigerant detectors
5. Concept of sealed components and sealed enclosures according to IEC
60079-15:2010
6. Correct work procedures for the following:
a. Commissioning b. Maintenance c. Repair d. Decommissioning e. Disposal See
Controls and Troubleshooting Guide for complete guidelines.
When working on the equipment, observe precautions in the literature and on
tags, stickers, and labels attached to the equipment. 1. Follow all safety
codes. 2. Keep quenching cloth and fire extinguisher nearby when
brazing. 3. Wear safety glasses and work gloves. 4. Use care in handling,
rigging, and setting bulky equipment.
IMPORTANT: This equipment generates, uses, and can radiate radio frequency
energy and, if not installed and used in accordance with these instructions,
may cause radio interference. It has been tested and found to comply with the
limits of a Class A computing device pursuant to International Standard in
North America EN 61000-2/3, which are designed to provide reasonable
protection against such interference when operated in a commercial
environment.
CAUTION
This system uses an A2L refrigerant (R-32) which have higher pressures than
R-22 and other refrigerants. No other refrigerant can be used in this system.
Failure to use gauge set, hoses, and recovery systems designed to handle
refrigerant R-32 may result in equipment damage or personal injury. Refer to
Check Refrigerant Circuit section of the 30RC or 38RC chiller installation
instructions for guidelines on proper A2L refrigerant handling and equipment
used for A2L refrigerant. If unsure about equipment, consult the equipment
manufacturer.
WARNING
This product can expose you to chemicals including lead and lead components,
which are known to the State of California to cause cancer and birth defects
or other reproductive harm. For more information, go to
www.P65Warnings.ca.gov.
WARNING
Electrical shock can cause personal injury and death. Shut off all power to
this equipment during installation and service. There may be more than one
disconnect switch. Tag all disconnect locations to alert others not to restore
power until work is completed.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53300279-01
Printed in U.S.A.
Form No. 30-6ASI
Pg 1
5-24
Replaces: NEW
CAUTION
DO NOT re-use compressor oil or any oil that has been exposed to the
atmosphere. Dispose of oil per local codes and regulations. DO NOT leave
refrigerant system open to air any longer than the actual time required to
service the equipment. Seal circuits being serviced and charge with dry
nitrogen to prevent oil contamination when timely repairs cannot be completed.
Failure to follow these procedures may result in damage to equipment.
WARNING
DO NOT USE TORCH to remove any component. System contains oil and refrigerant
under pressure.
To remove a component, wear protective gloves and goggles and proceed as
follows:
a. Shut off electrical power to unit.
b. Recover refrigerant to relieve all pressure from system using both high-
pressure and low pressure ports.
c. Traces of vapor should be displaced with nitrogen and the work area should
be well ventilated. Refrigerant in contact with an open flame produces toxic
gases.
d. Cut component connection tubing with tubing cutter and remove component
from unit. Use a pan to catch any oil that may come out of the lines and as a
gauge for how much oil to add to the system.
e. Carefully un-sweat remaining tubing stubs when necessary. Oil can ignite
when exposed to torch flame.
Failure to follow these procedures may result in personal injury or death.
GENERAL
This book contains instructions for the installation of the Greenspeed
Variable Speed Fan Control.
The Greenspeed accessory uses a single variable frequency drive (VFD) to
control the speed of the condenser fans. All fans will operate at the same
speed. This can reduce energy usage and noise at off design conditions. The
VFD is controlled on the unit LEN bus. The PIC6 controller on the unit
monitors all pressure and temperature inputs to determine the most efficient
and stable fan speed. Typically the fan speed will increase with high ambient
temperature to reduce head pressure. Opposite is true for lower ambient
temperatures.
This accessory will also allow the unit to run down to 20°F ambient with the
addition of the wind baffle accessory. At low ambient conditions, high winds
can have a detrimental effect on head pressure control. The wind baffles
prevent wind from blowing across the condenser coil to alleviate this issue.
IMPORTANT: Wind baffles are required for ambient temperatures below 35°F if
wind velocity is anticipated to be greater than 5 mph (8 km/h).
Table 1 — Greenspeed® Accessory Usage
PART NO. 30RC70004901 30RC70005001 30RC70005101
MODEL/UNIT SIZES 30RC 020-030 30RC 035-050 30RC 055, 060
VOLTAGE 230
30RC70005301 30RC70005401 30RC70005501
38RC 025,030 38RC 035-050 38RC 055, 060
380/460
30RC70005701
38RC 025,030
30RC70005801
38RC 035-050
575
30RC70005901
38RC 055, 060
Inspect Shipment
Inspect contents of the accessory package before installing. File a claim with
the shipping company if there is shipping damage. Contact your local Carrier
Representative if any parts are missing. See Table 1 for Greenspeed accessory
usage. See Table 2 for VFD Usage and Table 3 for accessory package contents.
30RC/38RC UNIT SIZE
020 025 030 035 040 045 050 055 060
Table 2 — VFD Usage
VOLTAGE
208/230 380 460 575
208/230 380 460 575
208/230 380 460 575
208/230 380 460 575
208/230 380 460 575
208/230 380 460 575
208/230 380 460 575
208/230 380 460 575
208/230 380 460 575
FAN DRIVE PART NO.
HR46ZP007 HR46ZP008 HR46ZP008 HR46ZP003 HR46ZP007 HR46ZP008 HR46ZP008
HR46ZP003 HR46ZP007 HR46ZP008 HR46ZP008 HR46ZP003 HR46ZQ001 HR46ZR001
HR46ZR001 HR46ZQ002 HR46ZQ001 HR46ZR001 HR46ZR001 HR46ZQ002 HR46ZQ001
HR46ZR001 HR46ZR001 HR46ZQ002 HR46ZQ001 HR46ZR001 HR46ZR001 HR46ZQ002
HR46ZS001 HR46ZS005 HR46ZS005 HR46ZR003 HR46ZS001 HR46ZS005 HR46ZS005
HR46ZR003
2
ACCESSORY
30RC70004901 30RC70005301 30RC70005701 (20-30 Ton)
30RC70005001 (35-50 Ton)
Table 3 — Accessory Package Contents
VOLTAGE 230/380/460/575
230
PART NUMBER 30RCHSCALXCA10
38AP404952 38AP504900 38AP504273 38APMACBFG-A00 See Table 2. 38APHLSBF1-A00
38APHLSSF2-A00 38APHSCSFV-A01 AL04AU166 AL01AU168 HY84DA022 00PPN500000302A
AL56ZA003 AA06BR200 AU02AB202 38AP504929
30-6ASI 38AP504954 38AP504972 2004592371 2004606726 2004590453 30RCHSCALXCA30
38AP404952 See Table 2. 38APHLSBF1-A00 38APHLSSF2-A00 38APHLSMF3-A00
38APHSCSFV-A21 HY10JK040
JT60060 AL04AU166 HW60HH006 38APPAAAAA-A00 AL01AU168 HY84DA022 00PPN500000302A
AL56ZA003 AA06BR200 AU02AB202 38AP504929
30-6ASI
QTY 1 3 1 1 1 1 1 1 1 4 2 1 6 30 6 6 1 1 1 1 1 1 1 1 3 1 1 1 1 1 3 3 4 1 1 2 1 6 35 6 6 1 1
DESCRIPTION LEN Cable Conduit Drive Mounting Plate Drive Enclosure Terminal Block Shroud Fan (VFD) OFM-1 Harness (25-60 Ton) OFM-2 Harness (40-60 Ton) Low Ambient Harness (10-15 Ton) No. 8, 1/2 in. long Trilobe No. 8, 3/4 in. long Trilobe 3 Pole 600-v Terminal Block Mounting Hardware – Drive (6 mm) Mounting Hardware – Sheet Metal Mounting Hardware – 5/16 x 1 Mounting Hardware – Washer Grill Instructions Drive Mounting Plate Drive Enclosure RH Side Adapter Plate (35-60 Ton Only) LH Side Adapter Plate (35-60 Ton Only) Top Adapter Plate (35-60 Ton Only) LEN Cable Conduit Fan (VFD) OFM-1 Harness (40-60 Ton) OFM-2 Harness (40-60 Ton) OFM-3 Harness (40-60 Ton) Greenspeed® Harness (230-v, 35-60 Ton) Class J Quick Blow Fuse (40A 600-v) Class J Fuse Holder (35-60A 600-v) No. 8, 1/2 in. long Trilobe 1.00 in. Conduit Clamp 1 in. x 12 in. Varnish Cloth No. 8, 3/4 in. long Trilobe Terminal Block (3 Pole, 600-v) Mounting Hardware – Drive (6 mm) Mounting Hardware – Sheet Metal Mounting Hardware – 5/16 x 1 Mounting Hardware – Washer Grill Instructions
3
ACCESSORY
30RC70005401, 30RC70005801 (35-50 Ton)
30RC70005101 (55-60 Ton)
Table 3 — Accessory Package Contents (cont)
VOLTAGE 460/380/575
230
PART NUMBER 38AP504954 38AP504972 2004592371 2004606726 2004590453
30RCHSCALXCA30 38AP404952 See Table 2.
38APHLSBF1-A00 38APHLSSF2-A00 38APHLSMF3-A00 38APHSCSFV-A11
HY10JK025 JT60030
AL04AU166 HW60HH006 38APPAAAAA-A00 AL01AU168 HY84DA022 00PPN500000302A
AL56ZA003 AA06BR200 AU02AB202 38AP504929
30-6ASI 38AP504954 38AP504972 2004592371 2004606726 2004590453 30RCHSCALXCA30
38AP404952 38APHLSBF1-A00 38APHLSSF2-A00 38APHLSMF3-A00 38APHLSMF4-A00
38APHSCSFV-A21 HY10JK040
JT60060 AL04AU166 HW60HH006 38APPAAAAA-A00 AL01AU168 HY84DA022 00PPN500000302A
AL56ZA003 AA06BR200 AU02AB202 38AP504929
30-6ASI
QTY 1 1 1 1 1 1 3 1 1 1 1 1 3 3 4 1 1 2 1 6 35 6 6 1 1 1 1 1 1 1 1 3 1 1 1 1 1 3 3 4 1 1 2 1 6 35 6 6 1 1
DESCRIPTION Drive Mounting Plate Drive Enclosure RH Side Adapter Plate (35-60 Ton Only) LH Side Adapter Plate (35-60 Ton Only) Top Adapter Plate (35-60 Ton Only) LEN Cable Conduit Fan (VFD) OFM-1 Harness (40-60 Ton) OFM-2 Harness (40-60 Ton) OFM-3 Harness (40-60 Ton) Greenspeed® Harness (35-60 Ton) Class J Quick Blow Fuse 25A 600-v 1-30A 600-v Class J Fuse Holder No. 8, 1/2 in. long Trilobe 1.00 in. Conduit Clamp 1 in. x 12 in. Varnish Cloth No. 8, 3/4 in. long Trilobe Terminal Block (3 Pole 600-v) Mounting Hardware – Drive (6 mm) Mounting Hardware – Sheet Metal Mounting Hardware – 5/16 x 1 Mounting Hardware – Washer Grill Instructions Drive Mounting Plate Drive Enclosure RH Side Adapter Plate (35-60 Only) LH Side Adapter Plate (35-60 Only) Top Adapter Plate (35-60 Only) LEN Cable Conduit OFM-1 Harness (40-60 Ton) OFM-2 Harness (40-60 Ton) OFM-3 Harness (40-60 Ton) OFM-4 Harness (40-60 Ton) Greenspeed® Harness (230-v, 35-60 Ton) Class J Quick Blow Fuse (40A, 600-v) Class J Fuse Holder (35-60A, 600-v) No. 8, 1/2 in. long Trilobe 1.00 in. Conduit Clamp 1 in. x 12 in. Varnish Cloth No. 8, 3/4 in. long Trilobe Terminal Block (3 Pole 600-v) Mounting Hardware – Drive (6 mm) Mounting Hardware – Sheet Metal Mounting Hardware – 5/16 x 1 Mounting Hardware – Washer Grill Instructions
4
ACCESSORY
30RC70005501, 30RC70005901 (55-60 Ton)
Table 3 — Accessory Package Contents (cont)
VOLTAGE 460/380/575
PART NUMBER 38AP504954 38AP504972 2004592371 2004606726 2004590453
30RCHSCALXCA30 38AP404952
38APHLSBF1-A00 38APHLSSF2-A00 38APHLSMF3-A00 38APHLSMF4-A00 38APHSCSFV-A11
HY10JK025 JT60030
AL04AU166 HW60HH006 38APPAAAAA-A00 AL01AU168 HY84DA022 00PPN500000302A
AL56ZA003 AA06BR200 AU02AB202 38AP504929
30-6ASI
QTY 1 1 1 1 1 1 3 1 1 1 1 1 3 3 4 1 1 2 1 6 35 6 6 1 1
DESCRIPTION Drive Mounting Plate Drive Enclosure RH Side Adapter Plate (35-60 Only) LH Side Adapter Plate (35-60 Only) Top Adapter Plate (35-60 Only) LEN Cable Conduit OFM-1 Harness (40-60 Ton) OFM-2 Harness (40-60 Ton) OFM-3 Harness (40-60 Ton) OFM-4 Harness (40-60 Ton) Greenspeed® Harness (35-60 Ton) Class J Quick Blow Fuse (25A, 600-v) Class J Fuse Holder (1-30A, 600-v) No. 8 1/2 in. long Trilobe 1.00 in. Conduit Clamp 1 in. x 12 in. Varnish Cloth No. 8 3/4 in. long Trilobe 3 Pole 600-v Terminal Block Mounting Hardware – Drive (6 mm) Mounting Hardware – Sheet Metal Mounting Hardware – 5/16 x 1 Mounting Hardware – Washer Grill Instructions
5
INSTALLATION
Step 1 — Install Wind Baffle Accessory Kit
If the chiller is expected to run in ambient temperatures below 35°F and winds
above 5 mph are expected, a wind baffle accessory kit is required. See below
for part numbers that require the wind baffle accessory kit. · 30RA-900—065
(sizes 020, 035, 040) · 30RA-900—066 (sizes 020, 030, 045-060) NOTE: Unit
sizes 035-060 require two kits.
Step 2 — Mount the VFD
Verify the drive nameplate rating versus the unit nameplate rating for correct
voltage range. Check the VFD part number from Table 2. Remove panel on side of
unit where VFD will be mounted. This panel can be discarded. See Fig. 1. Mount
VFD to VFD mounting bracket using 6 mm thread forming screw. Attach drive
enclosure to mounting plate using sheet metal screw. See Fig. 2. Connect 3
conduit assemblies to the 3 holes on the side of the enclosure. Conduit nut
should be on the inside of the enclosure, towards the VFD, and conduit should
be outside of the enclosure.
30RC 020-030 Size Units
38RC 025-030 Size Units
Place drive inside unit enclosure and mount to unit base. Use 5/16 x 1 screws
for VFD mounting plate and sheet metal screw for enclosure. On most units the
VFD assembly can be rotated to fit through the VFD opening in the unit side
panel. On some of the smaller units where internal piping may interfere with
this procedure, the side panel of the unit should be removed. If removing the
side panel, brace the weight of the control panel to prevent damage to the
center post of the unit. The VFD assembly enclosure will be flush with side
panel on 20-30 ton units after mounting. On 35-60 ton units, the enclosure
will mount with a 1 in. gap between the enclosure and the side panel.
CAUTION
Internal refrigerant tubing is under high pressure. Do not damage piping while
mounting VFD assembly. Serious injury may occur.
20-30 TON UNITS Fasten drive enclosure to unit side panel using sheet metal
screws.
35-60 TON UNITS Use spacer brackets to mount VFD assembly to unit side panel.
Attach with sheet metal screws. See Fig. 3.
30RC 035-060 Size Units 38RC 040-060 Size Units
Control Panel
Control Panel
VFD Mounting Position
Fig. 1 — Drive Mounting Location
VFD Mounting Position
Drive Mounting Plate
Fan VFD
Adapter Plates
Drive Enclosure
Fig. 2 — Drive to Enclosure Assembly
Fig. 3 — VFD Assembly to Unit Side Panel (35-60 Ton)
6
Step 3 — Control Panel Wiring
1. Mount fuse block, terminal block, and terminal block cover per panel
layout. See Fig. 4 and 5. Wiring for 20-30 ton units will require fuse blocks
and fuses that already exist in the panel. Fan contactors may be removed if
more panel space is needed. If contactors are removed, remove any power wires
attached to them. Control wires may be cut and terminated to assure they
cannot ground to panel.
2. Replace fan motor cables with cables supplied. Connect control box end to
VFD terminal block installed in “Mount the VFD” on page 6. See Fig. 6 for
identification of fan motor designations. Use wire ties to secure fan wire
routing. At fan motor, ensure a drip loop is created when routing the wire to
the motor. See Fig. 7.
3. Install Greenspeed harness between control panel and VFD. This consists of
two cables. One cable takes power from the VFD fuse block to the drive input,
L1/L2/L3. The other cable takes power from the drive output (U/V/W), to the
VFD terminal block to power the fans. Route cables through conduit sections at
VFD enclosure.
Cooler Heater and Reverse Rotation
4. Install communication cable (LEN) between control panel and VFD. Connect
per markings on the harness. Ground the shield at the VFD. Do not ground it in
the control panel. Do not run communication cable with power wires to the VFD.
This could cause interference with the communication signal.
5. Install fuses into fuse block. See Table 4.
Table 4 — Fuse Replacement
FUSE REPLACEMENT TABLE FOR FB1/FB2
UNIT SIZE
VOLTAGE
FUSE
FUSE BLOCK
208/230
380
020-030
460
LP-CC-20
575
208/230
380 035-050
460
LP-CC-20
FB1/FB2
575
208/230
FNQ-R-30
055-060
380
FNQ-R-20
460
FNQ-R-17-1/2
575
FNQ-R-15
VFD Fuse Blocks
CIOB Stack
(1 or 2)
C
Auxillary Board
LEGEND
CB — CCN — CHR — CIOB — FB — FC —
Circuit Breaker Carrier Comfort Network Evaporator Heater Relay Carrier Input/Output Board Fuse Block Fan Contactor
Remote Connectivity
VFD Terminal Block
FU — Fuse RRB — Reverse Rotation Board/Phase Monitor TRAN — Transformer TB — Terminal Block SW — Switch
Fig. 4 — Control Panel Layout (20-30 Ton)
7
Power Input Location
Transformer
Main Box (Compressors)
VFD Fuse Blocks
Low Ambient
Remote Connectivity
Auxilliary Display
CIOB (Stack of 3)
CHR
Main Box (Compressors)
RRB
Power Input
LEGEND
VFD Terminal Block
CCN — Carrier Comfort Network CB — Circuit Breaker CIOB — Carrier Input/Output CHR — Evaporator Heater Relay RRB — Reverse Rotation Board/Phase Monitor VFD — Variable Frequency Drive
2 x 30 Position TB
CCN Board 2 x TB From Main Harness 2 x Switch
4 x 5 Amp CB
Fig. 5 — Control Panel Layout (35-60 Ton)
Pumps
OFM1
Wire (To Fan Motor)
Wire Tie
Control Box
OFM2
Top View Sizes 020-030
Conduit (From Control Box)
Control Box Control Box
OFM1 OFM3
OFM2
OFM1 OFM3 OFM2 OFM4
Top View Sizes 035-050
Top View Sizes 055, 060
Fig. 6 — Condenser Fan Layout
Drip loop to prevent water entering into the conduit and then to the control
box.
Fig. 7 — Fan Motor Wiring Connection Routing
8
Step 4 — Setup
Once all wiring is terminated and all covers are back in place, power unit.
See Fig. 8-10.
Set the address on the variable frequency drive (VFD) to 184. (Parameter 8-31
= 184) This will allow the controller to send correct operating parameters to
the VFD. See Fig. 9.
At the PIC6 controller, configure the unit for Greenspeed control.
(MainMenuConfigurationFactoryvfan_sel =1). NOTE: This will require a reboot of
the controller.
IMPORTANT: The control power must be cycled with the correct VFD address and
correct controller configuration before the variable speed fans will operate.
In the controller menu go to Quick Test1 (MainMenuQuick Test1). Enable the
quick test menu. Scroll down to Q-VFAN. Enter 50 to drive fans to 50%. Fans
should start and run at 30 Hz. This confirms the fan VFD is operational. Enter
0 for Q-VFAN and disable quick test. See Fig. 8.
Install grill over VFD opening. Unit is now ready for operation.
Fig. 8 — Fan Motor Power Wiring
NOTE: Address for FVFD is 184 (Parameter 8-31)
Fig. 9 — LEN BUS Wiring
9
Fig. 10 — 30RC 010-060 Power Schematic 10
© 2024 Carrier
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53300279-01
Printed in U.S.A.
Form No. 30-6ASI
Pg 12
5-24
Replaces: NEW
References