resideo AM-1 Series Proportional Thermostatic Mixing Valve Installation Guide
- September 11, 2024
- resideo
Table of Contents
resideo AM-1 Series Proportional Thermostatic Mixing Valve
APPLICATION
The AM-1 Series family of quality valves in a variety of temperature ranges
and connections, for master mixing or diverting applications.
SPECIFICATIONS
- Media Temperature Ranges:
- Cold Inlet: 39°F-80°F (4°C-27°C)
- Hot Inlet: 120°F-180°F (49°C-82°C)
- Mixed Outlet:
- C Model: 70°F-120°F (21°C-49°C)
- Standard Model: 70°F-145°F (21°C-63°C)
- Connections:
- Straight-through design (HOT and COLD at same level).
- Construction:
- Nickel plated brass construction. EPDM o-rings. Made in USA.
- Lead Free Plumbing Code Compliance: The wettable surfaces of lead free models contain less than .25% of lead by weighted average
- Operating Pressure: 150 psi (1034 kPa) maximum.
Patent Information: U.S. Patent No. 6,079,625.
Temperature Gauge Adapter: Lead-free brass, EPDM o-ring.
INSTALLATION
IMPORTANT: Mounting must comply with all local codes.
NOTE TO INSTALLER: This product should be installed by a qualified individual, in accordance with local codes and ordinances. It is the responsibility of the installer to properly select, install and adjust these devices as specified in these instructions. For installations which require compliance with Building/Mechanical/Plumbing Codes, the appropriate AM-1 Series valve must be chosen and installed, and the discharge temperature set and locked according to these instructions. AM-1 “C” Series models with the temperature range, 70°F– 120°F (21°C–49°C) and “Standard” models with temperature range 70°F–145°F (21°C–63°C) are ASSE® 1017 (point of source application) certified, and CSA®a and IAPMO® listed. These models shall be used to supply water to tubs, showers, bathing facilities and other outlets. These valves should be installed where they will be accessible for cleaning, servicing or adjustment.
ASSE 1017 Applications—Point of Source
These AM-1 Series models can be installed in any position consistent with the
intended use. For domestic hot water supply, the valve must be installed as
shown in Fig. 1. There shall be no shut-off valves installed between the cold
water line and the cold water connection on the AM-1 Series valve. Check
valves shall be installed as indicated for NPT models; all AM-1 models with
union fittings are supplied with integral check valves on both the hot and
cold ports. A cold water service valve may be installed, as indicated, between
the cold water supply line to the distribution system and the cold water line
supplying both the water heater and the AM-1 Series valve.
Installation of Union Sweat, CPVC, Union Press, Push Connect and PEX Connections
- Union sweat connections, if used, should be soldered prior to assembly to the valve, or without the sealing gasket or optional check valve present. After the joint has cooled, the sealing gasket and/or check valves may be installed.
- CPVC fittings are limited to a system maximum temperature of 180° F (82° C) and 100 psi (689 kPa).
- PEX fitting and crimp ring (provided by Installer) are deigned to meet ASTM F1807 requirements.
- PEX tubing used with PEX fittings must meet ASTM F876 requirements.
- Press connections, use press tools and installation practices compatible with Viega systems.
- Push connect fittings can be used with both copper and PEX (plastic).
Installation of Temperature Gauge Adapter
IMPORTANT
Union sweat connections must be soldered before the thermowell with O-ring and
sealing gasket are installed. Install the thermowell with O-ring and sealing
gasket after the joint has cooled.
- Install thermowell with O-ring to the thermometer adapter body.
- Tighten to 75 LB-IN ± 10 LB-IN. DO NOT OVERTIGHTEN.
- Install the thermometer into the thermowell until seated and tighten the set screw to secure in place.
VALVE ADJUSTMENT
To adjust temperature setting of the mixing valve, attach thermostrip
(supplied with the valve) to the piping connected to the Mix port of the
valve. Loosen handwheel screw, lift handwheel and turn to desired temperature
as indicated on the thermostrip. Reposition the hand wheel and retighten
screw.
Temperature Setting Procedure
It is possible to limit the temperature range. To use this feature:
Thermostrip Installation
Clean pipe and firmly apply Thermostrip on mix outlet of valve. Flow water and
adjust mixed outlet temperature for desired setting range. Actual mixed water
temperature is indicated in green with 2° F (1° C) increments. Blue means
slightly lower and brown means slightly higher.
WARNING
Water Temperature above 120°F (49° C) can cause serious injury. Mixing valve
temperature setting should be done by licensed contractor per local code
requirement. To ensure correct temperature control, use water thermometer at
faucet outlet.
The thermostrip is ONE TIME USE ONLY for initial system temperature setting. Check expiration date printed on temperature strip to ensure temperature reading accuracy. If necessary, contact your Resideo distributor to obtain a replacement thermostrip, part number TS205-064. Thermostrip only included in models without the temperature gauge.
Post Installation Procedure
- Write temperature setting on CAUTION label and sign in space provided.
- Attach CAUTION label to AM-1 valve.
- Explain CAUTION label to owner.
- Deposit this instruction sheet with owner.
OPERATION
The AM-1 series valve provides for automatic operation through the use of a thermostatic element in the product. The element will control the mixing of the hot and cold supply to provide mixed tempered water to connected fixtures. This provides constant water temperature under different working conditions.
MAINTENANCE PROCEDURES
Hard water conditions may result in scale deposits, causing binding of
internal parts in extreme cases. Cleaning the internal parts will usually
restore the valve to proper operating conditions. In some cases, it may be
necessary to replace the lower assembly.
To clean and/or replace the lower assembly, shut off water and:
- With a screwdriver, remove screw and handwheel.
- Loosen upper nut (do not remove) to allow engaging an adjustable wrench on lower nut. Unscrew lower nut (counterclockwise). This removes top assembly.
- Brass top assembly will pop up. Remove lower assembly, diffuser and spring.
- Carefully remove any scaling (calcium deposit) or foreign particles from valve seat and other internal parts. Use vinegar to remove calcium. Soak parts until calcium becomes soft and can be scrubbed and washed off. Do not use solvents or scratch metallic / Teflon® coated surfaces.
- Replace cleaned spring, diffuser and lower assembly following instructions below or use new replacement kit assembly. For correct kit number, see Table 1.
Install spring, diffuser and lower assembly:
- Insert spring onto diffuser.
- Insert diffuser with spring end first into body.
- Fit valve top assembly into lower assembly and insert into valve.
- Tighten lower nut.
- Reposition handwheel and insert screw. Turn handwheel to desired temperature setting.
Table 1. AM-1 Series Replacement Kits.
Part No. | Description |
---|---|
AM1-BODY-1LF/U | AM1 BODY ONLY STANDARD 70F-145F |
AM1-RBODY-1/U | AM1 BODY ONLY RADIANT 70F-180F |
AM1-1070BODY-1LF/U | AM1 BODY ONLY C1070 70F-120F |
AM08-038LF/U | (3) 1/2″ Lead-free Sweat Tailpieces, Nuts, Gaskets |
AM08-039LF/U | (3) 3/4″ Lead-free Sweat Tailpieces, Nuts, Gaskets |
AM08-040LF/U | (3) 1″ Lead-free Sweat Tailpieces, Nuts, Gaskets |
AM08-041LF/U | (3) 1/2″ Lead-free NPT Tailpieces, Nuts, Gaskets |
AM08-042LF/U | (3) 3/4″ Lead-free NPT Tailpieces, Nuts, Gaskets |
AM08-043LF/U | (3) 1″ Lead-free NPT Tailpieces, Nuts, Gaskets |
AM100-SB/U | (3) 1/2” Lead-free Push Connect Tailpieces, Nuts, Gaskets |
AM101-SB/U | (3) 3/4” Lead-free Push Connect Tailpieces, Nuts, Gaskets |
AM102-SB/U | (3) 1” Lead-free Push Connect Tailpieces, Nuts, Gaskets |
AM206-039/U | (3) 1/2″ Lead-free CPVC Tailpieces, Nuts, Gaskets |
AM206-040/U | (3) 3/4″ Lead-free CPVC Tailpieces, Nuts, Gaskets |
AM206-041LF/U | (3) 1/2″ Lead-free PEX Tailpieces, Nuts, Gaskets |
AM206-042LF/U | (3) 3/4″ Lead-free PEX Tailpieces, Nuts, Gaskets |
TS205-064/U | Thermal Temperature Indicator Strip <140F |
TS206-080/U | Thermal Temperature Indicator Strip <180F |
AM1-TAIL100-3UP-LF | (3) 1/2″ Lead-free Press Tailpieces, Nuts, Gaskets |
AM1-TAIL101-3UP-LF | (3) 3/4″ Lead-free Press Tailpieces, Nuts, Gaskets |
AM1-TAIL102-3UP-LF | (3) 1″ Lead-free Press Tailpieces, Nuts, Gaskets |
TG200-UT/U | Thermometer, 2” Dial w/Threaded Well |
TG250-UT/U | Thermometer, 2.5” Dial w/Threaded Well |
AM-1-020RP/U | REPLACEMENT ASSEMBLY ‘B’ and ‘C’ MODEL |
AM-1-025RP/U | REPLACEMENT ASSEMBLY STD and ‘R’ MODEL |
AM-1-030RP/U | REPLACEMENT ASSEMBLY C1070 MODEL |
AMCU100/U | CHECKVALVE KIT FITS ALL AM1 EXCEPT FNPT |
AMU200-RP/U | (3) Gasket Kit |
AM1-TEMPGAUGE/U | (1) Lead-free AM1 Temp Gauge Adapter Universal |
- ASSE® is a registered trademark of the American Society of Sanitary Engineering.
- CSA® is a registered trademark of the Canadian Standards Association.
- IAPMO® is a registered trademark of the International Association of Plumbing and Mechanical Officials.
- ASTM® is a registered trademark of the American Society for Testing and Materials.
- Teflon® is a registered trademark of E.I. du Pont de Nemours and Company.