Carrier FB4CNF Fan Coil Units Installation Guide
- September 10, 2024
- Carrier
Table of Contents
FB4CNF Fan Coil Units
Product Information
Specifications:
- Model: FB4CNF, FB4CNP, FX4D
- Product Type: Fan Coil Units for R-410A Refrigerant
- Sizes Available: 018 to 061
Product Usage Instructions
Installation:
Step 1 – Check Equipment:
Unpack the unit and move it to the final location. Inspect the
equipment for any damage before installation. If any damage is
found, file a claim with the shipping company.
Step 2 – Mount Unit:
The unit can be placed on the floor, hung from the ceiling or
wall. Ensure there is enough space for wiring, piping, and
servicing the unit. If installed over a finished ceiling or living
area, a secondary condensate pan may be required as per building
codes.
Step 3 – Air Ducts:
Connect the air ducts according to the unit’s specifications.
Ensure proper airflow for efficient operation.
Step 4 – Electrical Connections:
Make electrical connections following the provided guidelines.
Always turn off power before servicing the unit to avoid electrical
hazards.
Step 5 – Refrigerant Tubing Connection and Evacuation:
Connect the refrigerant tubing carefully and perform evacuation
procedures as instructed to ensure optimal performance.
Step 6 – Refrigerant Flow-Control Device:
Install and set up the refrigerant flow-control device according
to the manufacturer’s recommendations.
Step 7 – Condensate Drains:
Set up condensate drains to prevent water build-up and ensure
proper drainage.
Step 8 – Accessories:
If using any accessories, install them following the provided
instructions for compatibility and functionality.
Step 9 – Sequence of Operation:
Familiarize yourself with the sequence of operation to
understand how the unit functions and troubleshoot if needed.
Start-Up Procedures:
Follow the start-up procedures outlined in the manual to ensure
a smooth and safe operation of the unit.
Care and Maintenance:
Regular maintenance is essential for optimal performance. Refer
to the manual for care and maintenance instructions.
Airflow Performance Tables:
Refer to the airflow performance tables provided to understand
the unit’s airflow capabilities and adjust as needed.
FAQ:
Q: What should I do if I find damage to the unit during
installation?
A: If you find any damage to the unit during
installation, immediately file a claim with the shipping company to
address the issue.
Q: Is it necessary to install a secondary condensate pan under
the unit?
A: Depending on building codes and regulations
in your area, a secondary condensate pan may be required when
installing the unit over a finished ceiling or living area. Consult
local codes for specific requirements.
FB4CNF FB4CNP FX4D
FAN COIL UNITS FOR R-410A REFRIGERANT
SIZES 018 TO 061
Installation Instructions
NOTE: Read the entire instruction manual before starting the installation.
TABLE OF CONTENTS
PAGE
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . . 1
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. 1
HEATER PACKAGES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . 2
Step 1 — Check Equipment . . . . . . . . . . . . . . . . . . . . . . . . . 2
Step 2 — Mount Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. 2
Step 3 — Air Ducts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. 4
Step 4 — Electrical Connections . . . . . . . . . . . . . . . . . . . . . 4
Step 5 — Refrigerant Tubing Connection and Evacuation . . 7 Step 6 —
Refrigerant Flow-Control Device . . . . . . . . . . . . . 7
Step 7 — Condensate Drains . . . . . . . . . . . . . . . . . . . . . . . . 7
Step 8 — Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. 8
Step 9 — Sequence of Operation . . . . . . . . . . . . . . . . . . . . . 8
START-UP PROCEDURES . . . . . . . . . . . . . . . . . . . . . . . . . . 9
CARE AND MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . 9
AIRFLOW PERFORMANCE TABLES . . . . . . . . . . . . . . . . . 9
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service, maintenance, or use
can cause explosion, fire, electrical shock, or other conditions which may
cause death, personal injury or property damage. Consult a qualified
installer, service agency, or your distributor or branch for information or
assistance. The qualified installer or agency must use factory-authorized kits
or accessories when modifying this product. Refer to the individual
instructions packaged with kits or accessories when installing. Follow all
safety codes. Wear safety glasses, protective clothing and work gloves. Have a
fire extinguisher available. Read these instructions thoroughly and follow all
warnings or cautions included in literature and attached to the unit. Consult
local building codes and the current editions of the National Electrical Code
(NEC) NFPA 70. In Canada, refer to the current editions of the Canadian
Electrical Code CSA C22.1. Recognize safety information. This is the safety-
alert symbol . When you see this symbol on the unit and in instruction
manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, and CAUTION. These words are used
with the safety-alert symbol. DANGER identifies the most serious hazards which
will result in severe personal injury or death. WARNING signifies hazards
which could result in personal injury or death. CAUTION is used to identify
unsafe practices which may result in minor personal injury or product and
property damage. NOTE is used to highlight suggestions which will result in
enhanced installation, reliability, or operation.
! WARNING
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal injury or death.
Before installing or servicing unit, always turn off all power to unit. There
may be more than one disconnect switch. Turn off accessory heater power if
applicable. Lock out and tag switch with a suitable warning label.
! CAUTION
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate
protective clothing and gloves when handling parts.
INTRODUCTION
FB4C and FX4D models are R-410A Fan Coils designed for installation
flexibility. These units leave the factory compliant with low leak
requirements of less than 2% cabinet leakage rate at 0.5 inches W.C. and 1.4%
cabinet leakage rate at 0.5 inches W.C. when tested in accordance with ASHRAE
193 standard. FB4CNF(018-048) uses a refrigerant piston metering device. A TXV
is used on FB4CNP and FX4D(018-061). All these fan coils use a multi-tap ECM
motor for efficiency. The units have be designed for upflow, downflow (kit
required), and horizontal orientations, including manufactured and mobile home
applications. These units require a field supplied air filter, and are
designed specifically for R-410A refrigerant air conditioners and heat pumps
as shipped. These units are available for systems of 18,000 through 60,000
BTUh nominal cooling capacity. Factory- authorized, field – installed electric
heater packages are available in sizes 5 through 30kW. See Product Data
literature for all available accessory kits.
HEATER PACKAGES
This unit may or may not be equipped with an electric heater package. For
units not equipped with factory-installed heat, a factory-approved, field-
installed, UL listed heater package is available from your equipment supplier.
See unit rating plate for a list of factory-approved heaters. Heaters that are
not factory approved could cause damage which would not be covered under the
equipment warranty. If fan coil contains a factory-installed heater package,
minimum circuit ampacity (MCA) and maximum fuse/breaker may be different than
units with a same size field-installed accessory heater. The differences is
not an error and is due to calculation difference per UL guidelines.
INSTALLATION
Step 1 — Check Equipment
Unpack unit and move to final location. Remove carton taking care not to
damage unit. Inspect equipment for damage prior to installation. File claim
with shipping company if shipment is damaged or incomplete.
NOTE: If the door gasket is damaged or missing, the unit may not meet the
ASHRAE 193 standard for cabinet air leakage. Contact your supplier and order
kit #344994-751.
Locate unit rating plate which contains proper installation information. Check
rating plate to be sure unit matches job specifications.
Step 2 — Mount Unit
Unit can stand or lie on floor, or hang from ceiling or wall. Allow space for
wiring, piping, and servicing unit.
IMPORTANT: When unit is installed over a finished ceiling and/or living area,
building codes may require a field-supplied secondary condensate pan to be
installed under the entire unit. Some localities may allow as an alternative,
the running of a separate, secondary condensate line. Consult local codes for
additional restrictions or precautions.
NOTE: Nuisance sweating may occur if the unit is installed in a high humidity environment with low airflow.
A. Upflow Installation
If return air is to be ducted through a floor, set unit on floor over opening and use 1/8 to 1/4-in (3 to 6 mm) thick fireproof resilient gasket between duct, unit, and floor.
Side return is a field option on slope coil models. Cut opening per dimensions. (See Fig. 1.) A field-supplied bottom closure is required.
POWER ENTRY OPTIONS
018 – 048 21″ (533 mm) FRONT SERVICE 060 – 060 24″ (610mm) CLEARANCE
A COIL UNITS
FIELD SUPPLIED SUPPLY DUCT
LOW VOLT ENTRY OPTIONS
UNIT
018, 024 025 – 030
036
A 12″ (305 mm) 17″ (432 mm) 19″ (483 mm)
UPFLOW/DOWNFLOW SECONDARY DRAIN
UPFLOW/DOWNFLOW PRIMARY DRAIN
UPFLOW/DOWNFLOW SECONDARY DRAIN
1.5″ (38 mm) 19″ (483 mm)
2.5″ A
(64 mm)
FIELD MODIFIED SIDE RETURN LOCATION FOR SLOPE COIL UNITS ONLY
UPFLOW/DOWNFLOW PRIMARY DRAIN
FIELD SUPPLIED RETURN PLENUM
A07565
Fig. 1 – Slope Coil Unit in Upflow Application
B. Downflow Installation In this application, field conversion of the
evaporator is required using accessory downflow kit along with an accessory
base kit. Use fireproof resilient gasket, 1/8 to 1/4-in (3 to 6 mm) thick,
between duct, unit, and floor.
! CAUTION
UNIT OR PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in product or property damage.
The conversion of the fan coil to downflow requires special procedures for the
condensate drains on both A-coil and slope units. The vertical drains have an
overflow hole between the primary and secondary drain holes. This hole is
plugged for all applications except downflow, but must be used for downflow.
During the conversion process, remove the plastic cap covering the vertical
drains only and discard. Remove the plug from the overflow hole and discard.
At completion of the downflow installation, caulk around the vertical pan
fitting to door joint to retain the low air leak performance of the unit.
NOTE: To convert units for downflow applications, refer to Installation
Instructions supplied with kit for proper installation. For slope fan coils,
use kit Part No. KFADC0201SLP. For A-coils, use kit Part No. KFADC0401ACL. Use
fireproof resilient gasket, 1/8 to 1/4-in (3 to 6 mm) thick, between duct,
unit, and floor. NOTE: Gasket kit number KFAHD0101SLP is also required for all
downflow applications to maintain low air leak/low sweat performance. C.
Horizontal Installation Units must not be installed with access panels facing
up or down. All other units are factory built for horizontal left
installation. (See Fig. 2 and 3.) When suspending unit from ceiling, dimples
in casing indicate suitable location of screws for mounting metal support
straps. (See Fig. 2.) For horizontal applications having high return static
and humid return air, the Water Management Kit, KFAHC0125AAA, may need to be
used to assist in water management.
! CAUTION
PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in product or property damage.
For optimum condensate drainage performance in horizontal installations, unit
should be leveled along its length and width.
A-COIL HORIZONTAL LEFT
LOW VOLT ENTRY OPTIONS
FIELD SUPPLIED HANGING STRAPS
UNIT
SECONDARY DRAIN
PRIMARY DRAIN
018-048 21″ (533 mm) 060-060 24″ (610 mm) FRONT SERVICE CLEARANCE (FULL FACE OF UNIT)
1.75″ (44 mm) FILTER ACCESS CLEARANCE
POWER ENTRY OPTIONS
SECONDARY DRAIN
PRIMARY DRAIN
A07566
Fig. 2 – Slope Coil Unit in Horizontal Left Application
2
A
FACTORY SHIPPED HORIZONTAL LEFT
APPLICATION
B C
COIL BRACKET
COIL SUPPORT
RAIL
DRAIN PAN SUPPORT BRACKET
COIL BRACKET
HORIZONTAL DRAIN PAN
AIR SEAL ASSEMBLY
PRIMARY DRAIN HORIZONTAL LEFT
REFRIGERANT CONNECTIONS
SECONDARY DRAIN HORIZONTAL LEFT
A00072
Fig. 3 – A-Coil in Horizontal Left Application
NOTE: Modular units can be disassembled and components moved separately to installation area for reassembly. This process accommodates small scuttle holes and limiting entrances to installation sites. (See Fig. 4 .)
2 SCREWS
BLOWER BOX 2 SCREWS
REAR CORNER BRACKET
COIL BOX
2 SCREWS
A95293
Fig. 4 – Removal of Brackets on Modular Units Horizontal Right Conversion of
Units With Slope Coils
NOTE: Gasket kit number KFAHD0101SLP is required for horizontal slope coil
conversion to maintain low air leak/low sweat performance.
1. Remove blower and coil access panel and fitting panel. (See Fig. 5.)
2. Remove coil mounting screw securing coil assembly to right side casing
flange.
3. Remove coil assembly.
4. Lay fan coil unit on its right side and reinstall coil assembly with
condensate pan down. (See Fig. 5.)
5. Attach coil to casing flange using coil mounting screw previously removed.
6. Make sure the pan cap in the fitting door is properly seated on the
fitting door to retain the low air leak rating of the unit.
7. Add gaskets from kit KFAHD per kit instructions.
8. Align holes with tubing connections and condensate pan connections, and
reinstall access panels and fitting panel.
Make sure liquid and suction tube grommets are in place to prevent air leaks
and cabinet sweating. Install after brazing.
COIL MOUNTING SCREW
BLOWER ASSEMBLY
COIL SUPPORT
RAIL
SLOPE COIL SKI
DRAINPAN
REFRIGERANT CONNECTIONS
PRIMARY DRAIN
SECONDARY DRAIN
A03001
Fig. 5 – Conversion for Horizontal Right Applications
Horizontal Right Conversion of Units With A-Coils 1. Remove blower and coil access panels. (See Fig. 6.)
REFRIGERANT CONNECTIONS
COIL SUPPORT
RAIL
COIL BRACKET
AIR SEAL ASSEMBLY
A
HORIZONTAL RIGHT
APPLICATION
B C
DRAIN PAN SUPPORT BRACKET
COIL SUPPORT
RAIL
COIL BRACKET
HORIZONTAL DRAIN PAN
PRIMARY DRAIN HORIZONTAL RIGHT SECONDARY DRAIN HORIZONTAL RIGHT
A00071
Fig. 6 – Conversion for Horizontal Right Applications Using A-Coil
2. Remove metal clip securing fitting panel to condensate pan. Remove fitting
panel.
3. Remove 2 snap-in clips securing A-coil in unit.
4. Slide coil and pan assembly out of unit.
5. Remove horizontal drain pan support bracket from coil support rail on left
side of unit and reinstall on coil support rail on right side of unit. (See
Fig. 7.)
DRAIN PAN SUPPORT BRACKET
Fig. 7 – Drain Pan Support Bracket
A07571
3
6. Convert air-seal assembly for horizontal right. a. Remove air-seal
assembly from coil by removing 4 screws. (See Fig. 6.)
b. Remove air splitter (B) from coil seal assembly by removing 3 screws. (See
Fig. 3-factory shipped inset.)
c. Remove filter plate (A) and install air splitter (B) in place of filter
plate.
d. Install filter plate (A) as shown in horizontal right application.
e. Remove condensate troughs (C) and install on opposite tube sheets.
f. Install hose onto plastic spout.
7. Install horizontal pan on right side of coil assembly.
8. Slide coil assembly into casing. Be sure coil bracket on each corner of
vertical pan engages coil support rails.
9. Reinstall 2 snap-in clips to correctly position and secure coil assembly
in unit. Be sure clip with large offsets is used on right side of unit to
secure horizontal pan.
10. Remove two oval fitting caps from the left side of the coil door and
fitting panel.
11. Remove insulation knockouts on right side of coil access panel.
12. Remove 2 oval coil access panel plugs and reinstall into holes on left
side of coil access panel and fitting panel.
13. Install condensate pan fitting caps (from item 10) in the right side of
the coil door making sure that the cap snaps and seats cleanly on the back
side of the coil door. Make sure no insulation interferes with seating of the
cap.
14. Reinstall access fitting panels, aligning holes with tubing connections
and condensate pan connections. Be sure to reinstall metal clip between
fitting panel and vertical condensate pan.
Make sure liquid and suction tube grommets are in place to prevent air leaks
and cabinet sweating.
D. Manufactured and Mobile Home Housing Applications 1. Fan coil unit must be
secured to the structure using field- supplied hardware. 2. Allow a minimum of
24-in (610 mm) clearance from access panels.
3. Recommended method of securing for typical applications:
a. If fan coil is away from wall, attach pipe strap to top of fan coil using
no. 10 self-tapping screws. Angle strap down and away from back of fan coil,
remove all slack, and fasten to wall stud of structure using 5/16-in. lag
screws. Typical both sides of fan coil.
4″ (102mm) MAX
SECURE FAN COIL TO STRUCTURE UNIT AWAY FROM WALL PIPE STRAP (TYPICAL BOTH
SIDES)
OR
UNIT AGAINST WALL .125″ (3mm) MOUNTING BRACKET (TYPICAL BOTH SIDES)
DOWN FLOW BASE KIT (KFACB)
SECURE UNIT TO FLOOR ANGLE BRACKET OR PIPE STRAP
4″ (102mm) MAX
Fig. 8 – A-Coil
A07567
b. If fan coil is against wall, secure fan coil to wall stud using 1/8-in (3 mm) thick right-angle brackets. Attach brackets to fan coil using no. 10 self- tapping screws and to wall stud using 5/16-in. lag screws. (See Fig. 8.)
Step 3 — Air Ducts
Connect supply-air duct over the outside of 3/4-in (19 mm) flanges provided on
supply-air opening. Secure duct to flange, using proper fasteners for type of
duct used, and seal duct-to-unit joint. If return-air flanges are required,
install factory-authorized accessory kit.
Use flexible connectors between ductwork and unit to prevent transmission of
vibration. When electric heater is installed, use heat-resistant material for
flexible connector between ductwork and unit at discharge connection. Ductwork
passing through
unconditioned space must be insulated and covered with vapor barrier. Units
equipped with 20-30kW electric heaters require a 1-in (25 mm) clearance to
combustible materials for the first 36-in (914 mm) of supply duct.
Ductwork Acoustical Treatment Metal duct systems that do not have a 90_ elbow and 10-ft (3m) of main duct to first branch takeoff may require internal acoustical insulation lining. As an alternative, fibrous ductwork may be used if constructed and installed in accordance with the latest edition of SMACNA construction standard on fibrous glass ducts. Both acoustical lining and fibrous ductwork shall comply with National Fire Protection Association as tested by UL Standard 181 for Class 1 air ducts.
Step 4 — Electrical Connections
FB4C units from the factory protect the low voltage circuit with a 3 amp automotive type fuse in-line on the wire harness and Does Not contain a circuit board. Motor speeds and time delay function are built into the motor (see section E for clarification). When a factory-approved accessory control package has been installed, check all factory wiring per unit wiring diagram and inspect factory wiring connections to be sure none were loosened in transit or installation. If a different control package is required, see unit rating plate.
4
! CAUTION
PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in product or property damage.
If a disconnect switch is to be mounted on unit, select a location where drill
or fastener will not contact electrical or refrigerant components.
Before proceeding with electrical connections, make certain that supply
voltage, frequency, phase, and ampacity are as specified on the unit rating
plate. See unit wiring label for proper field high- and low-voltage wiring.
Make all electrical connections in accordance with the NEC and any local codes
or ordinances that may apply. Use copper wire only. The unit must have a
separate branch electric circuit with a field-supplied disconnect switch
located within sight from, and readily accessible from, the unit. On units
with a factory-installed disconnect with pull-out removed, service and
maintenance can be safely performed on only the load side of the control
package.
! WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Field wires on the line side of the disconnect found in the fan coil unit
remain live, even when the pull-out is removed. Service and maintenance to
incoming wiring cannot be performed until the main disconnect switch (remote
to the unit) is turned off.
A. Line Voltage Connections If unit will contain accessory electric heater,
remove and discard power plug from fan coil and connect male plug from heater
to female plug from unit wiring harness. (See Electric Heater Installation
Instructions.) For units without electric heater:
1. Connect 208/230v power leads from field disconnect to yellow and black
stripped leads.
2. Connect ground wire to unit ground lug. NOTE: Units installed without
electric heat should have a field-supplied sheet metal block-off plate
covering the heater opening. This will reduce air leakage and formation of
exterior condensation. B. 24-v Control System Connection To Unit Wire low
voltage in accordance with wiring label on the blower. (See Fig. 9 through
12.) Use no. 18 AWG color-coded, insulated (35_C minimum) wire to make the
low-voltage connections between the thermostat, the unit, and the outdoor
equipment. If the thermostat is located more than 100-ft (30 m) from the unit
(as measured along the low-voltage wire), use no. 16 AWG color-coded,
insulated (35_C minimum) wire. All wiring must be NEC Class 1 and must be
separated from incoming power leads.
THERMOSTAT
FAN COIL (CONTROL)
R
RED
R
G
GRY G
WHT
W
WHT
W2
BLU W3
VIO E
BRN C
Y
AIR COND. C Y
Fig. 9 – Wiring Layout Air Conditioning Unit
(Cooling Only)
THERMOSTAT
FAN COIL (CONTROL)
R
RED
R
G
GRY G
WHT
W WHT
W2
BLU W3
VIO E
BRN C
AIR COND.
C
Y
Y
A94058
Fig. 10 – Wiring Layout Air Conditioning Unit (Cooling and 1-Stage Heat)
THERMOSTAT R G
FAN COIL (CONTROL)
RED R GRY G
HEAT PUMP (CONTROL)
R
C
BRN C
C
W2
WHT BLU
W2 W3
E
VIO E
L
W2
A94059
O
O
Y
Y
A94060
Fig. 11 – Wiring Layout Heat Pump Unit (Cooling and 2-Stage Heat with No
Outdoor Thermostat)
THERMOSTAT
FAN COIL (CONTROL)
HEAT PUMP (CONTROL)
R
R
R
G
G
C
C
C
W2
W2
W2
W3
E
E
L
ODTS
O
O
Y
Y
A03088
Fig. 12 – Wiring Layout Heat Pump Unit (Cooling and 2-Stage Heat for
Manufactured Housing)
5
Refer to outdoor unit wiring instructions for any additional wiring procedure
recommendations.
Transformer Information Transformer is factory-wired for 230v operation. For
208v applications, disconnect the black wire from the 230v terminal on
transformer and connect it to the 208v terminal. (See Fig. 13.)
SECONDARY
BRN RED
C 208 230
YEL BLK
PRIMARY
Fig. 13 – Transformer Connections
A05182
Heater Staging
If electric heat staging is required, a multi-stage heating room thermostat is required. Consult your equipment supplier for a suitable thermostat.
C. Manufactured Housing
In manufactured housing applications, the Code of Federal Regulations, Title 24, Chapter XX, Part 3280.714 requires that supplemental electric heat be locked out at outdoor temperatures above 40_F (4_C), except for a heat pump defrost cycle. Refer to Fig. 12 for typical low voltage wiring with outdoor thermostat.
D. Ground Connections
! WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
According to NEC, ANSI/NFPA 70, and local codes, the cabinet must have an
uninterrupted or unbroken ground to minimize personal injury if an electrical
fault should occur. The ground may consist of electrical wire or metal conduit
when installed in accordance with existing electrical codes. If conduit
connection uses reducing washers, a separate ground wire must be used.
NOTE: Use UL-listed conduit and conduit connector for connecting supply
wire(s) to unit to obtain proper grounding. Grounding may also be accomplished
by using grounding lugs provided in control box.
E. Minimum CFM and Motor Speed Selection
The fan speed selection is done at the motor connector. Units with or without
electric heaters require a minimum CFM. Refer to the unit wiring label to
ensure that the fan speed selected is not lower than the minimum fan speed
indicated.
Tap 1
Low
90 sec off delay
Tap 2
Medium
90 sec off delay
Tap 3
High
90 sec off delay
Tap 4
Electric heat
0 sec off delay
Tap 5
Max
0 sec off delay
electric heat airflow is same CFM as Tap 3, except 0 sec off delay high static applications, see airflow tables for max airflow
To change motor speeds disconnect the BLUE fan lead from motor connector
terminal #2 (factory default position) and move to desired speed-tap; 1, 2, 3,
or 5.
Speed-taps 1, 2, and 3 have a 90 second blower off time delay pre-programmed
into the motor. Speed-tap 4 is used for electric heat only (with 0 second
blower time delay) and the WHITE wire should remain on tap 4. Speed-tap 5 is
used for high static applications, but has a 0 second blower time delay pre-
programmed into the motor. See Airflow Performance tables for actual CFM.
Also, see Fig. 14 for motor speed selection location.
NOTE: In low static applications, lower motor speed tap should be used to
reduce possibility of water being blown off coil.
1 2 3 4 5
Speed Taps may be located on motor, or on plug close to motor.
1 2 3 4 5
C LG N
Fig. 14 – Motor Speed Selection
A11048
Step 5 — Refrigerant Tubing Connection and Evacuation
Use accessory tubing package or field-supplied tubing of refrigerant grade.
Suction tube must be insulated. Do not use damaged, dirty, or contaminated
tubing because it may plug refrigerant flow-control device. ALWAYS evacuate
the coil and field-supplied tubing to 500 microns before opening outdoor unit
service valves.
6
! CAUTION
PRODUCT DAMAGE HAZARD
Failure to follow this caution may result in product or property damage.
A brazing shield MUST be used when tubing sets are being brazed to the unit
connections to prevent damage to the unit surface and condensate pan fitting
caps.
Units have sweat suction and liquid tube connections. Make suction tube
connection first.
1. Cut tubing to correct length. 2. Insert tube into sweat connection on unit
until it bottoms. 3. Braze connection using silver bearing or non-silver
bearing
brazing materials. Do not use solder (materials which melt below 800_F /
427_C). Consult local code requirements. 4. Evacuate coil and tubing system to
500 microns using deep vacuum method.
! CAUTION
PRODUCT DAMAGE HAZARD
Failure to follow this caution may result in product or property damage. Wrap
a wet cloth around rear of fitting to prevent damage to piston assembly or TXV
and factory-made joints.
Step 6 — Refrigerant Flow-Control Device
FB4CNF units contain a factory installed piston with Teflon ring for sizes 018
thru 048 only. The FB4CNP and FX4D(018-061) size units come equipped with a
R-410A refrigerant TXV. If a piston replacement is required, check piston size
shown on indoor unit rating plate to see if it matches required outdoor piston
size. The outdoor piston size will be found on the outdoor unit rating
plate, product data or installation instructions depending on the model. If
the fan coil piston does not match, replace indoor piston
with correct outdoor piston. With some outdoor units a piston is shipped with
outdoor unit; if no piston is shipped with the outdoor unit one can be ordered
from Replacement Components. When changing piston, use a back-up wrench. (See
Fig. 15). Hand tighten hex nut, then tighten with wrench 1/2 turn. Do not
exceed 30 ft-lbs.
BRASS HEX NUT
TEFLON SEAL
DISTRIBUTOR
TEFLON RING
PISTON
FLOW IN COOLING PISTON RETAINER
BRASS HEX BODY
NOTE: The indoor piston contains a Teflon ring (or seal) which is used to seat
against the inside of distributor body, and must be installed properly to
ensure proper seating in the direction for cooling operation.
Always use outdoor units designed to match indoor fan coil applications.
! CAUTION
PRODUCT OPERATION HAZARD
Failure to follow this caution may result in improper product operation. If
using a TXV in conjunction with a single-phase reciprocating compressor, a
compressor start capacitor and relay are required. Consult outdoor unit pre-
sale literature for start assist kit part number.
Step 7 — Condensate Drains
To connect drains, the cap openings must be removed. Use a knife to start the
opening near the tab and using pliers, pull the tab to remove the disk. Clean
the edge of the opening if necessary and install the condensate line. Finally
caulk around the lines where they exit the fitting to retain the low leak
rating of the unit.
! CAUTION
UNIT OR PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in product or property damage.
The conversion of the fan coil to downflow requires special procedures for the
condensate drains on both A-coil and slope units. The vertical drains have an
overflow hole between the primary and secondary drain holes. This hole is
plugged for all applications except downflow, but must be used for downflow.
During the conversion process, remove the plastic cap covering the vertical
drains only and discard. Remove the plug from the overflow hole and discard.
At completion of the downflow installation, caulk around the vertical pan
fitting to door joint to retain the low air leak performance of the unit.
Units are equipped with primary and secondary 3/4-in. FPT drain connections.
For proper condensate line installations see Fig. 1, 2, 3, 5 and 6. To prevent
property damage and achieve optimum drainage performance, BOTH primary and
secondary drain lines should be installed and include properly-sized
condensate traps. (See Fig. 16 and 17.) Factory-approved condensate traps are
available. It is recommended that PVC fittings be used on the plastic
condensate pan. Finger-tighten plus 1-1/2 turns. Do not over-tighten. Use pipe
dope.
UNIT
2″ MIN (51 mm)
STRAINER
2″ MIN (51 mm)
A09677
Fig. 15 – Refrigerant Flow – Control Device
7
Fig. 16 – Recommended Condensate Trap
A03002
PRIMARY TRAP REQUIRED (USE FACTORY KIT OR
FIELD-SUPPLIED TRAP OF SUFFICIENT DEPTH.
STANDARD P-TRAPS ARE NOT SUFFICIENT. SEE
FIGURE OF RECOMMENDED CONDENSATE TRAP)
FILTER ACCESS PANEL
SECONDARY DRAIN WITH APPROPRIATE TRAP REQUIRED (USE FACTORY KIT OR FIELD-
SUPPLIED TRAP)
Fig. 17 – Condensate Trap and Unit
A03003
! CAUTION
PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in product or property damage.
Shallow running traps are inadequate and DO NOT allow proper condensate
drainage. (See Fig. 18.)
DO NOT USE SHALLOW RUNNING TRAPS!
Fig. 18 – Insufficient Condensate Trap
A03013
NOTE: When connecting condensate drain lines, avoid blocking filter access panel, thus preventing filter removal. After connection, prime both primary and secondary condensate traps.
NOTE: If unit is located in or above a living space where damage may result from condensate overflow, a field-supplied, external condensate pan should be installed underneath the entire unit, and a secondary condensate line (with appropriate trap) should be run from the unit into the pan. Any condensate in this external condensate pan should be drained to a noticeable place. As an alternative to using an external condensate pan, some localities may allow the use of a separate 3/4-in (19 mm) condensate line (with appropriate trap) to a place where the condensate will be noticeable. The owner of the structure must be informed that when condensate flows from the secondary drain or external condensate pan, the unit requires servicing or water damage will occur.
Install traps in the condensate lines as close to the coil as possible. (See Fig. 17.) Make sure that the outlet of each trap is below its connection to the condensate pan to prevent condensate from overflowing the drain pan. Prime all traps, test for leaks, and insulate traps if located above a living area. Condensate drain lines
should be pitched downward at a minimum slope of 1-in (25 mm) for every 10-ft
(3 m) of length. Consult local codes for additional restrictions or
precautions.
Step 8 — Accessories
Humidifier
Connect humidifier and humidistat to fan coil unit as shown in Fig. 19 and
Fig. 20. The cooling lockout relay is optional.
Step 9 — Sequence of Operation
A. Continuous Fan
Thermostat closes R to G. G energizes fan relay on PCB which completes circuit
to indoor blower motor. When G is de-energized, there is a 90-sec delay before
relay opens.
B. Cooling Mode
Thermostat energizes R to G, R to Y, and R to O (heat pump only). G energizes
fan relay on PCB which completes circuit to indoor blower motor. When G is de-
energized, there is a 90-sec delay before fan relay opens. C. Heat Pump
Heating with Auxiliary Electric Heat
Thermostat energizes R to G, R to Y, and R to W. G energizes fan relay on PCB
which completes circuit to indoor blower motor. W energizes electric heat
relay(s) which completes circuit to heater element(s). When W is de-energized,
electric heat relay(s) open, turning off heater elements. When G is de-
energized there is a 90-sec delay before fan relay opens. D. Electric Heat or
Emergency Heat Mode
Thermostat closes R to W. W energizes electric heat relay(s) which completes
circuit to heater element(s). Blower motor is energized through normally
closed contacts on fan relay. When W is de-energized, electric heat relay(s)
opens.
THERMOSTAT
FAN COIL (CONTROL)
R
RED R
G
GRY G
C
BRN C
W2
WHT
WHT BLU
W2 W3
E
VIO E
L
HEAT PUMP (CONTROL)
R
C
W2
O
O
Y
Y
FAN HUMIDIFIER 115V M
RELAY
HUMIDISTAT
A95294
Fig. 19 – Wiring Layout of Humidifier to Heat Pump
8
THERMOSTAT
FAN COIL (CONTROL)
R
RED
R
G
GRY G
WHT
W
WHT
W2
BLU W3
VIO E
BRN C
AIR COND.
C
Y FAN HUMIDIFIER
Y HUMIDISTAT
115V M
A95295
Fig. 20 – Wiring Layout of Humidifier to Fan Coil
With Electric Heat
START-UP PROCEDURES
Refer to outdoor unit Installation Instructions for system start-up
instructions and refrigerant charging method details.
! CAUTION
UNIT COMPONENT HAZARD
Failure to follow this caution may result in product damage.
Never operate unit without a filter. Damage to blower motor or coil may
result. Factory authorized filter kits must be used when locating the filter
inside the unit. For those applications where access to an internal filter is
impractical, a field-supplied filter must be installed in the return duct
system.
CARE AND MAINTENANCE
To continue high performance and minimize possible equipment failure, it is
essential that periodic maintenance be performed on this equipment. Consult
your local dealer as to the proper frequency of maintenance contract. The
ability to properly perform maintenance on this equipment requires certain
mechanical skills and tools. If you do not possess these, contact your dealer
for maintenance. The only consumer service recommended or required is filter
replacement or cleaning on a monthly basis.
AIRFLOW PERFORMANCE TABLES
Table 1 Air Delivery Performance Correction Component Pressure Drop (in. wc) at Indicated Airflow (Dry to Wet Coil)
CFM
UNIT SIZE 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000
018, 019 024 025
030, 031 036 037
042, 043 048 049 060 061
0.034 0.049 0.063 0.034 0.049 0.063 0.076 0.089 0.015 0.026 0.038 0.049 0.059
0.049 0.059 0.070 0.080 0.070 0.080 0.090 0.099 0.055 0.064 0.073 0.081 0.049
0.056 0.063 0.070 0.063 0.070 0.076 0.083 0.090 0.038 0.043 0.049 0.054 0.059
0.049 0.054 0.059 0.065 0.070 0.027 0.031 0.035 0.039 0.043
SIZE
018, 019 024 – 031 036-049 060, 061
400 0.020
–
Table 2 Factory-Installed Filter Static Pressure Drop (in. wc)
CFM
600
800
1000
1200
1400
1600
0.044 0.022
–
0.075 0.048
–
0.072 0.051
–
0.100 0.070
–
0.092 –
0.120 0.086
1800 –
0.152 0.105
2000 –
0.130
HEATER ELEMENTS
0 1 2 3 4
Table 3 Electric Heater Static Pressure Drop (in. wc)
Sizes 018 – 037
EXTERNAL STATIC
kW
PRESSURE
CORRECTION
HEATER ELEMENTS
Sizes 042 – 061
EXTERNAL STATIC
kW
PRESSURE
CORRECTION
0
+.02
0
0
+.04
3, 5
+.01
2
8, 10
+.02
8, 10
0
3
9, 15
0
9, 15
.02
4
20
.02
20
.04
6
18, 24, 30
.10
9
AIRFLOW PERFORMANCE TABLES (cont)
MODEL & SIZE FB4C 018
FB4C 024 / 025 FB4C 030 FB4C 036 FB4C 042 FB4C 048 FB4C 060 FB4C 061
BLOWER SPEED Tap 5 Tap 4 Tap 3 Tap 2 Tap 1 Tap 5 Tap 4 Tap 3 Tap 2 Tap 1 Tap 5 Tap 4 Tap 3 Tap 2 Tap 1 Tap 5 Tap 4 Tap 3 Tap 2 Tap 1 Tap 5 Tap 4 Tap 3 Tap 2 Tap 1 Tap 5 Tap 4 Tap 3 Tap 2 Tap 1 Tap 5 Tap 4 Tap 3 Tap 2 Tap 1 Tap 5 Tap 4 Tap 3 Tap 2 Tap 1
Table 4 FB4C Airflow Performance (CFM)
0.10
0.20
0.30
0.40
767 614 701 614 410 969 826 826 701 617 1108 1026 1026 909 825 1301 1227 1227 1087 1026 1560 1419 1419 1249 1242 1743 1669 1669 1452 1300 1897 1817 1817 1657 1443 2030 1811 1811 1665 1462
739 569 660 569 350 936 795 795 660 592 1090 1000 1000 873 795 1276 1191 1191 1062 1000 1544 1397 1397 1220 1205 1712 1634 1634 1413 1256 1867 1785 1785 1621 1412 1995 1775 1775 1632 1418
702 534 616 534 304 892 766 766 616 552 1065 969 969 842 757 1245 1169 1169 1030 969 1507 1358 1358 1184 1158 1679 1599 1599 1377 1221 1836 1757 1757 1589 1377 1961 1740 1740 1593 1371
669 486 581 486 261 835 743 743 581 507 1034 938 938 799 722 1218 1143 1143 1001 938 1464 1320 1320 1142 1110 1642 1564 1564 1339 1182 1808 1724 1724 1557 1332 1927 1703 1703 1556 1327
0.50
620 436 537 436 228 763 706 706 537 472 1009 899 899 762 674 1176 1105 1105
966 899 1424 1279 1279 1093 1069 1610 1531 1531 1308 1142 1774 1693 1693 1518
1286 1888 1664 1664 1507 1278
0.60
565 398 499 398 203 676 660 660 499 420 974 865 865 724 634 1121 1074 1074 930
865 1358 1239 1239 1052 1026 1574 1499 1499 1271 1101 1736 1655 1655 1474 1243
1842 1613 1613 1453 1228
– Shading – Airflow outside 450 cfm/ton. NOTES:
1. Airflow based upon dry coil at 230v with factory-approved filter and
electric heater (2 element heater sizes 018 through 036, 3 element heater
sizes 042 through 061).
2. For FB4C models, airflow at 208 volts is approximately the same as 230
volts because the multi-tap ECM motor is a constant torque motor. The torque
doesn’t drop off at the speeds the motor operates.
3. To avoid potential for condensate blowing out of drain pan prior to making
drain trap: Return static pressure must be less than 0.40 in. wc. Horizontal
applications of 042 – 061 sizes must have supply static greater than 0.20 in.
wc.
4. Airflow above 400 cfm/ton on 048-061 size could result in condensate
blowing off coil or splashing out of drain pan.
10
AIRFLOW PERFORMANCE TABLES (cont)
MODEL & SIZE
FX4D 019 FX4D 025 FX4D 031 FX4D 037 FX4D 043 FX4D 049 FX4D 061
BLOWER SPEED Tap 5 Tap 4 Tap 3 Tap 2 Tap 1 Tap 5 Tap 4 Tap 3 Tap 2 Tap 1 Tap 5 Tap 4 Tap 3 Tap 2 Tap 1 Tap 5 Tap 4 Tap 3 Tap 2 Tap 1 Tap 5 Tap 4 Tap 3 Tap 2 Tap 1 Tap 5 Tap 4 Tap 3 Tap 2 Tap 1 Tap 5 Tap 4 Tap 3 Tap 2 Tap 1
Table 5 FX4D Airflow Performance (CFM)
EXTERNAL STATIC (in. wc)
0.10
0.20
0.30
0.40
776
745
696
660
683
644
589
548
683
644
589
548
631
563
500
443
625
524
457
417
956
920
891
851
825
795
757
722
825
795
757
722
726
695
635
598
631
563
500
443
1189
1151
1104
1050
1041
998
944
886
1041
998
944
886
924
876
817
752
779
693
628
571
1363
1332
1294
1253
1237
1206
1160
1121
1237
1206
1160
1121
1095
1058
1007
951
1014
885
773
673
1519
1490
1454
1419
1437
1403
1366
1333
1437
1403
1366
1333
1257
1226
1191
1141
1237
1206
1160
1121
1757
1725
1693
1653
1664
1626
1593
1552
1664
1626
1593
1552
1459
1420
1379
1336
1301
1241
1195
1150
2030
1995
1961
1927
1811
1775
1740
1703
1811
1775
1740
1703
1665
1632
1593
1556
1462
1418
1371
1327
0.50 609 494 494 409 367 816 674 674 543 409 1003 837 837 704 526 1207 1070 1070 888 609 1379 1294 1294 1090 1070 1614 1517 1517 1298 1102 1888 1664 1664 1507 1278
0.60 572 461 461 361 319 780 634 634 509 361 959 772 772 660 476 1157 1013 1013 824 549 1332 1245 1245 1033 1013 1576 1477 1477 1259 1039 1842 1613 1613 1453 1228
– Shading – Airflow outside 450 cfm/ton.
NOTES:
1. Airflow based upon dry coil at 230v with factory-approved filter and
electric heater (2 element heater sizes 019 through 037, 3 element heater
sizes 043 through 061).
2. For FX4D models, airflow at 208 volts is approximately the same as 230
volts because the multi-tap ECM motor is a constant torque motor. The torque
doesn’t drop off at the speeds the motor operates.
3. To avoid potential for condensate blowing out of drain pan prior to making
drain trap: Return static pressure must be less than 0.40 in. wc. Horizontal
applications of 043 – 061 sizes must have supply static greater than 0.20 in.
wc.
4. Airflow above 400 cfm/ton on 049-061 size could result in condensate
blowing off coil or splashing out of drain pan.
11
R-410A QUICK REFERENCE GUIDE
S R-410A refrigerant operates at 50-70 percent higher pressures than R-22. Be
sure that servicing equipment and replacement components are designed to
operate with R-410A refrigerant.
S R-410A refrigerant cylinders are rose colored. S Recovery cylinder service
pressure rating must be 400 psig, DOT 4BA400 or DOT BW400. S R-410A
refrigerant systems should be charged with liquid refrigerant. Use a
commercial type metering device in the manifold
hose when charging into suction line with compressor operating S Manifold sets
should be 700 psig high side and 180 psig low side with 550 psig low-side
retard. S Use hoses with 700 psig service pressure rating. S Leak detectors
should be designed to detect HFC refrigerant. S R-410A refrigerant, as with
other HFCs, is only compatible with POE oils. S Vacuum pumps will not remove
moisture from oil. S Do not use liquid-line filter driers with rated working
pressures less than 600 psig. S Do not leave R-410A refrigerant suction line
filter driers in line longer than 72 hours. S Do not install a suction-line
filter drier in liquid line. S POE oils absorb moisture rapidly. Do not expose
oil to atmosphere. S POE oils may cause damage to certain plastics and roofing
materials. S Wrap all filter driers and service valves with wet cloth when
brazing. S A factory approved liquid-line filter drier is required on every
unit. S Do NOT use an R-22 TXV. S If indoor unit is equipped with a R-22 TXV
or piston metering device, it must be changed to a hard-shutoff R-410A
refrigerant
TXV. S Never open system to atmosphere while it is under a vacuum. S When
system must be opened for service, recover refrigerant, evacuate then break
vacuum with dry nitrogen and replace filter
driers. Evacuate to 500 microns prior to recharging. S Do not vent R-410A
refrigerant into the atmosphere. S Do not use capillary tube coils. S Observe
all warnings, cautions, and bold text.
TRAINING
My Learning Center is your central location for professional residential HVAC
training resources that help strengthen careers and businesses. We believe in
providing high quality learning experiences both online and in the classroom.
Access My Learning Center with your HVACpartners credentials at
MLCtraining.com. Please contact us at mylearning@utc.com with questions.
Copyright 2019 CAC / BDP D 7310 W. Morris St. D Indianapolis, IN 46231
Edition Date: 6/19
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
12
Catalog No: IM-FB4C-FX4D-02
Replaces: IM-FB4C-FX4D-01
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>