COPELAND ZX 22-30HP Simplex ZX Condensing Unit User Manual
- September 9, 2024
- Copeland
Table of Contents
ZX 22-30HP Simplex ZX Condensing Unit
“`html
Product Information
Specifications
- Model: Large ZX 22-30HP condensing unit
- Manufacture Date: July 2024
- Refrigerant: HFC
- Lubricant: Emkarate RL 32 3MAF
- Capacity: 22-30HP
Product Usage Instructions
Safety Information
It is crucial to follow safety guidelines and recommendations
provided in the manual to ensure personal safety and proper
functioning of the unit.
Installation & Commissioning
Installation and commissioning work should only be carried out
by qualified refrigeration personnel. Ensure electrical connections
are made by qualified electricians.
Refrigerant & Lubricant
Use only approved refrigerants and refrigeration oils. The
compressor comes with an initial oil charge of Emkarate RL 32 3MAF
for HFC refrigerant use.
Start-up
Before starting the unit, ensure that all safety precautions are
followed. Release pressure from both high and low sides of the
compressor before servicing.
Troubleshooting
If you encounter any issues with the unit, refer to the
troubleshooting section of the manual for guidance. If problems
persist, contact qualified service personnel.
FAQ
Q: Can I install and commission the unit myself?
A: No, installation and commissioning should only be done by
qualified refrigeration personnel.
Q: What refrigerant should I use with this unit?
A: Use the correct refrigerant designed to work within the safe
operating envelope of the unit. The recommended lubricant is
Emkarate RL 32 3MAF for HFC refrigerants.
“`
JULY 2024
USER MANUAL
Large ZX 22-30HP condensing unit
Table of contents
Introduction & disclaimer
3
Safety information
4
Nomenclature
5
Scope of supply
5
PI diagram
6
CDU models / data
7
Features & benefits
9
Physical layout
10
CoreSense controller
12
Networking
18
Electrical connections
19
Installation & start-up
20
Troubleshooting
26
Operational check sheet
29
About Copeland
32
2
Thank you for purchasing Copeland Simplex ZX Condensing Unit for refrigeration
applications. This unit comes with high effciency Copeland fxed capacity
scroll compressor and liquid / vapor injection technology. This is the best in
class unit within the capacity and operating range available in the market.
Copeland ZX series has been highly successful in global market and has proven
success with its energy savings and customer friendly electronic features.
This document is designed to help the contractor and customer for the
installation, commissioning and operation of Copeland’s Simplex ZX condensing
unit.
Disclaimer
Please read through this operation manual to familiarize yourself with the
installation, commissioning, and operation of this product. Please do read the
following information in this page before proceeding with the rest of the
manual. The Copeland Simplex ZX scroll refrigeration condensing units should
only be installed by suitably qualifed and experienced refrigeration
technicians. No responsibility can be accepted for damage caused by
inexperienced or inadequately trained site technicians or improper system
design. All instructions and procedures described in this manual are based on
good refrigeration trade practices as applicable to this particular product.
The installation contractor may prefer to use variations to these
recommendations. However, the methods described in this manual represent the
minimum requirements to avoid any subsequent warranty claims for this
equipment and its components. These instructions do not cover the fundamentals
of good electrical or refrigeration practice and are therefore intended for
use only by qualifed and/or experienced personnel or technicians. For any
additional query, please consult your local sales offce, quoting unit model
and serial number as shown on the nameplate. In case of ambiguity, the wiring
diagram supplied with each unit takes precedence over the diagram in this
manual.
3
1. Safety Information
1.1 Installation and commissioning work on CDU shall be carried out only by
qualifed, refrigeration personnel who have been trained and instructed.
1.2 Simplex ZX condensing unit is manufactured according to the latest safety
standards. Emphasis has been placed on the user’s safety. For relevant
standards please refer to the manufacturer’s declaration, available on
request. You are strongly advised to follow these safety instructions.
1.3 Icon explanation
WARNING This icon indicates instructions to avoid personal injury and material
damage.
High Voltage This icon indicates operations with a danger of electric shock
Danger of burning or frostbite This icon indicates operations with a danger of
burning or frostbite
Explosion hazard This icon indicates operations with a danger of explosion
CAUTION This icon indicates instructions to avoid property damage and possibel
personal injury IMPORTANT This icon indicates instructions to avoid
malfunction of the compressor
This word indicates a recommendation for easier operation
1.5 General Instructions
Warning System breakdown! Personal injuries! Never install a system in the
feld and leave it unattended when it has no charge, a holding charge, or with
the service valves closed without electrically locking out the system.
Only approved refrigerants and refrigeration oils must be used. Warning High
shell temperature! Burning! Do not touch the compressor until it has cooled
down. Ensure that other materials in the area of the compressor do not get in
touch with it. Lock and mark accessible sections.
Do not get contact with the compressor Caution Overheating! Bearing damage! Do
not operate compressors without refrigerant charge or without being connected
to the system. Caution Compressors contain oil and refrigerant under pressure.
Release pressure from both high and low side of compressor before servicing.
Caution Tube brazing and compressor operation can produce hot surfaces. To
avoid burns, allow surfaces to cool.
1.4 Safety Statements
a. Only qualifed and authorized refrigeration personnel are permitted to
install, commission, and maintain this equipment.
b. Electrical connections must be made by qualifed electrical personnel.
c. All valid standards for connecting electrical and refrigeration equipment
must be observed.
d. The national legislation and regulations regarding personnel protection
must be observed.
1.6 Safety Refrigerants/Lubricant a. Please use correct refrigerant as
designed to work in safe operating envelope. b. Compressor is supplied with an
initial oil charge. The standard oil charge for use with HFC refrigerant is
polyol ester (POE) lubricant Emkarate RL 32 3MAF.
1.7 Receiving your unit
All units are flled with an ideal gas at a positive pressure before
transportation.
Use personal safety equipment. Safety goggles, gloves, protective clothing, safety boots and hard hats should be worn where necessary.
When you receive the unit from Copeland or an authorized representative, it is
important to check the pressure of each unit. If the unit found to be without
any pressure on receipt, please contact Copeland or their authorized
distributor.
Damage to the unit caused by the transportation / handling should fall within
the category of insurance claims and not be a manufacturing defect. It is also
advisable to inspect the rest of the unit for any physical damage and inform
Copeland or authorized distributor.
4
2. Nomenclature
ZX
L
250
B
E
TFD
521
Condensing Unit Family L = Low Temp Blank = Medium Temp 22 to 30 HP Generation E = Ester Oil TFD = 380V/420V 3Ph = 50Hz 522 = Without Door
Base Model
3. Standard Scope of Supply
521 BOM
Replaceable Core Liquid Line Filter Drier Moisture Indicator Liquid Line
Isolation Valve Oil Separator with Discharge Check Valve Accumulator
Adjustable HP / LP Switch Fixed LP Safety Switch HP Transducer HP / LP
pressure Gauge Compressor Isolation Valves Compressor Sound Jacket Compressor
Oil level Monitoring Circuit breaker and contactor Fan speed control 0 10 V
CoreSense Protection Intelligent store ready Receiver certifcation (PED)
Receiver with Outlet Isolation Valve Pressure Relief Valve
Elect Code
BOM
ZX
ZXL
521
521
5
4. PI Diagram
LP Switch
HP
DLT
Switch Sensor
LP Catridge
Oil Return
Access Port
HP Transducer
Check Valve
Oil Separator
Condenser
Service Port Liquid Receiver PRV
Filter Drier Sight Glass
Service Valve
Liquid Injection EXV
Service
Customer Side Port
BVS
ZX
POS
1 2 3 4 5 6 7 8 9 10 11
F5
B2
B3 B4 B5 B6
Description
Compressor M1 with isolation valves Oil separator Crank case heater R2
Condenser
Receiver
…
Electronic expansion valve
Filter drier/Sight glass
Ball valve, Liquid line
…
Fixed LP cartridge switch
Adjustable HP/LP dual pressure switch
Pressure transmitter, HP
Discharge line temperature sensor
… … Ambient temperature sensor
LP Switch
HP Switch
DLT Sensor
Oil Return Access Port
HP Transducer
Check Valve
Oil Separator
Service
T-ambient
Port Liquid Receiver
Condenser
PRV
Sight Glass Filter Drier
Service Valve
Customer Side Service Port BVS
T-vapor out
P H E
T-vapor in
EXV
T-vapor in
ZXL with EVI Technology
POS
1
2 3 4 5 6
7
8 9 10
Description
Compressor M1 with isolation valves
Oil separator
Crank case heater R2
Condenser
Receiver Brazed plate economizer Electronic expansion valve
Filter drier/Sight glass
Ball valve, Liquid line Accumulator
F5
Adjustable HP/LP dual pressure switch
B2
Pressure transmitter, HP
B3
Discharge line temperature sensor
B4
Vapour in temperature sensor
B5
Vapour out temperature sensor
B6
Ambient temperature sensor
6
5. CDU Models/Data
POS ZX220BE ZX250BE ZX300BE
Ambient temperature
(°C)
27 32 38 43 27 32 38 43 27 32 38 43
Capacity evaporating temperature (°C)
Power evaporating temperature (°C)
27.40 32.90 92.10 45.90 53.40 61.70 15.05 15.45 15.90 16.50 17.15 18.00
25.70 30.80 36.50 42.80 49.80 57.50 16.40 16.85 17.35 17.90 18.55 19.35
28.10 33.30 39.00 45.40 52.40
18.70 19.25 19.85 20.50 21.20
30.60 35.80 41.60 48.00
21.10 21.70 22.30 23.10
33.50 40.10 47.30 55.40 64.10 73.50 18.95 19.55 20.30 21.10 22.00 23.20
31.30 37.40 44.10 51.50 59.60 68.40 20.70 21.40 22.10 22.90 23.90 25.00
34.10 40.10 46.80 54.10 62.00
23.80 24.70 25.50 26.50 27.60
42.70 49.30 56.50
28.00 29.00 30.10
41.20 49.20 58.10 67.90 78.60 90.00 22.80 23.60 24.40 25.40 26.60 28.00
38.50 45.90 54.10 63.20 73.00 83.70 24.90 25.80 26.70 27.70 28.90 30.30
51.90 49.20 57.30 66.20 75.80
28.70 29.70 30.80 32.00 33.40
52.30 60.30 69.10
33.80 35.00 36.40
Technical data MT, 22 – 30 HP TWM: 380~420V/3Ph/50Hz
Nominal rating Model name
Family
Performance Sound Pressure Level
Compressor Fan Motor
Rated Load Ampere Locked Rotor Ampere Oil Type Oil Recharge Volume Qty
Diameter Maximum Speed Air Flow Total Fan Motor Power
Oil Separator Receiver Volume
Other
Pipes Dimension
Weight
Horsepower HP
@1m
dB(A)
Amp Amp
Total Input Volume R404a Suction OD Liquid OD WXDXH Nett Gross
Liters Pieces
mm rpm m3/hr W Liters kg Inch Inch mm Kg Kg
22 ZX220BE
ZX 25 ZX250BE
30 ZX300BE
73
73
74
31.4 225 4.38
29592 2300
1 5/8 7/8 400 465
41.4
57.9
272
310
POE
6.51
6.00
2
710
1010
29592
25200
2300
2600
0.6
31.8
2 1/8
1 1/8
2013 x 872 x 2120
410
420
475
485
7
Performance table
LT 25 – 30 HP R404A
Model ZXL250BE ZXL300BE
Ambient temperature
(°C)
27 32 38 43 27 32 38 43
Capacity evaporating temperature (°C)
Power evaporating temperature (°C)
-40 -35 -30 -25 -20 -15 -40 -35 -30 -25 -20 -15
18.25 21.80 26.30 31.60 37.80 44.90 13.60 14.40 15.20 16.15 17.20 18.40
17.75 21.40 25.80 30.90 36.70 43.40 14.90 15.75 16.70 17.70 18.75 19.95
16.80 20.70 25.00 29.90 35.30 41.40 16.70 17.70 18.75 19.80 20.90 22.20
19.70 24.10 28.80 34.00 39.70
19.55 20.70 21.90 23.10 24.30
23.00 27.50 33.00 39.70 47.50 56.40 16.50 17.45 18.50 19.65 21.00 22.40
22.30 27.00 32.50 38.80 46.10 54.40 18.05 19.15 20.30 21.50 22.90 24.40
21.10 26.00 31.40 37.50 44.40 51.90 20.20 21.50 22.80 24.20 25.60 27.10
30.20 36.20 42.70 49.70
25.20 26.70 28.20 29.80
Technical data LT, 10 – 20 HP TEM: 380~420V/3Ph/50Hz
Nominal rating Model name
Family
Performance
Sound Pressure Level
Compressor Fan Motor
Rated Load Ampere Locked Rotor Ampere Oil Type Oil Recharge Volume Qty
Diameter Maximum Speed Air Flow Total Fan Motor Power
Oil Separator Receiver Volume
Other
Pipes Dimension
Weight
Horsepower
HP
@1m
Total Input Volume R404a Suction OD Liquid OD WXDXH Nett Gross
dB(A)
Amp Amp
Liters Pieces
mm rpm m3/hr W Liters kg Inch Inch mm Kg Kg
ZX
22
30
ZX220BE
ZX300BE
75
75
37.1
46.7
246
310
POE
6.00
2
710
1010
29592
25200
2300
2600
0.6
31.8
2 1/8
7/8
2013 x 872 x 2120
440
455
505
520
8
6. Features and benefts
Simplex ZX platform condensing units were designed based on demands by
industry users:
Energy effciency Utilizing Copeland scroll compressor technology, variable
speed fan motor, large capacity condenser coil and advanced control
algorithms, energy consumption is signifcantly reduced. End users can save
more than 20% on annual energy costs compared to equivalent reciprocating
units.
Reliability Combining the proven reliability of Copeland scroll compressors
with advanced electronics controller and diagnostics, equipment reliability is
greatly enhanced. Fault code alerts and fault code retrieval capabilities
provide information to help improve speed and accuracy of system diagnostics.
Integrated electronics provide protection against over current, over heating,
incorrect phase rotation, compressor cycling, high pressure resets, low
pressure cut outs. It can also send out a warning message to an operator when
there is liquid food back, which can prevent critical damage on the unit.
Intelligent Store Highest efficiency Reliability
Better decision making Lower enery bills Lower maintenance cost
Condensing unit features:
· Copeland scroll compressor technology Highly effcient, ultra quiet and
highly reliable.
· Confgured with CoreSense controller Provides electronic diagnosis,
protection, and communication modules for energy saving and reliable unit
control. Analogue modulation for fans.
· Enhanced vapor injection (ZXL only)
Vapor injection provide high effciency for refrigeration application
Well tuned electronics algorithm with one big PHE for supplying sub cooled
liquid to the evaporator thus increasing the refrigeration effect and
supplying cool gas into the compressor through the EVI port cooling the
discharge of the compressor.
Design features
9 Real time monitoring of compressor operating conditions
9 Compressor reverse rotation protection 9 Compressor over current protection
9 Compressor internal motor protector 9 Discharge gas overheat protection 9
Over voltage protection 9 Under voltage protection 9 High pressure protection
9 Low pressure protection 9 Refrigerant food back warning 9 Compressor minimum
off time 9 Compressor oil level protection 9 Intelligent store solution:
Communication and retail
store monitoring
9
7. Physical layout of the unit
ZX: 22-30 HP MT
Check Valve
Oil Separator
Control Box
Compressor HP/LP Switch
Liq. Receiver Filter Drier
10
ZXL: 25-30 HP LT
Oil Separator
Compressor HP/LP Switch
Check Valve Control Box
Liq. Receiver Filter Drier
11
8. CoreSense controller
EV: EXV Connection port
VNR: Remote display connection port
H-K: Hot key connection port
485: RS485 Connection port
DI3: LP Switch connection Port
AI2 AI7: Temp sensor connection ports
AI1: Pressure transducer connection ports
Supply: Power supply connection port (24VAC from transformer)
Current transformer holes
R-S-T:
Voltage measurement
connector
TO1:
Triac output
1 (Fan motor
connecter)
TO2: Triac output 2 (Digital valve connecter)
DI1: Unit on/off control
DO4:
Neutral:
Crankcase
Common terminal connector (TFD/PFJ/ heater
TF7: neutral; TF5: common) terminal) connector
DO5: Alarm dry contact output connector DO1/DO2/C1: Reserved connector
DO3: Compressor contactor output connector C2: HP switch input connector
12
LED descriptions
LED
1 2
Status
On Flashing
On Flashing
On
On On Flashing
Description
Compressor 1 is running
Compressor 1 is ready to start Compressor 2
is running Compressor 2 is ready to start
Condensing fan is running1
Digital compressor is unloading
Display with C
Programmable mode
LED
!
!
Status
On Flashing
On Flashing
On On
_
Description
Browsing the service menu Browsing the fast access menu
A new alarm happened
Browsing the alarm menu
An alarm is occuring
Liquid line solenoid valve on
Reserved
Keyboard descriptions – Single button
Set Displays target set point; In programming mode, select a parameter or
confrm an operation. Start Reset Hold for 5 seconds to reset any lockouts if
the current state of the controller allow for it to be reset.
Up Enter the fast access menu; In programming mode, browse the parameter codes
or increases the displayed value. Down In programming mode it browses the
parameter code or decreases the displayed value Service Enter the service and
alarm menu. Defrost Hold for 3 seconds to start a manual defrost or terminate
an active defrost (Not available at the moment).
Keyboard descriptions – Combined buttons
Press and hold for about 3 seconds to lock (Pon) or unlock (Pof) the keyboard.
Pressed together to exit programming mode or menu; under rtC and PAr, this
combination allows the user to go back to previous level. Pressed together for
3 seconds allows access to frst level of programming mode.
Pressed together for 3 seconds allows access to EXV manual setting.
13
Refrigerants
Step
Action
1
Press
2
Press
3
Press
4
Press
5
Press
6
Press
7
Press
8
Press
Phenomenon and description Enter menu to select PAr (parameter) or rtC Select PAr (parameter) Confrm selection Browse to parameter C07 Confrm selection Select refrigerant to be used The number will fash for 3 seconds and confrm the refrigerant selection Exit (or exit automatically after waiting for 120 seconds)
Replacing controller
After a new controller is replaced and initial power is on, it is critical to reset parameters defined on the label below the nameplate on the unit panel. Here is an example of a label:
Model Parameter
H07
Controller Parameter Default Setting Description
Digital compressor MCC
Default Value
H09
Digital compressor current protection
H27
Fixed compressor MCC
H28
Fixed comrpessor current protection
H13
MIN. operating voltage
H14
Max. operating voltage
C07*
Refrigerant
Notes: *Ensure that parameters C07 is set to match the actual refrigerant used. If not, set C07 following label “Unit Operation Settig After Installation”.
14
Pr1 parameter (1st level) browse and modification
Step
Action
Phenomenon and description
1
Press
Enter menu to select PAr (parameter) or rtC
2
Press
Select PAr (parameter)
3
Press
Confrm, select, and browse Pr1 parameters
4
Press
Browse to Pr1 parameters
5
Press
View the actual number of the Pr1 parameters
6
Press
7
Press
8
Press
Modify the actual number of the Pr1 parameters
Press SET: the number will fash for 3 seconds and confrm the modifcations;
Will go to the next Pr1 parameter
Exit (or exit automatically after waiting for 120 seconds)
Quick access menu browse – Sensor status and actual values
Step
Action
Phenomenon and description
1
Press
Enter quick access menu, will display P1P (Press Up or Down to view other sensors)
2
Press
View the actual value of P1P
3
Press
Change to next sensor code
4
Press
Exit (or exit automatically after waiting for 60 seconds)
P1P Suction pressure sensor
P2P Condensing pressure sensor
P3t Digital compressor discharge line temperature sensor
P4t PHE vapor inlet temperature sensor
P5t PHE vapor outlet temperature sensor
P6t Ambient temperature sensor
P7t ON OFF compressor discharge line temperature sensor
5H PHE superheat
oPP EXV opening percentage Sensor code and values descriptions (nP, noP, or nA means that the sensor does LL5 Solenoid valve status (not used)
not exist; Err means that the sensor fails,
Std Condensing temperature set point
out of range, disconnected, or does not configure properly)
Aoo Fan’s analog output signal percentage dso Percentage of PWM output driving the valve of the Digital Scroll compressor
Lt Minimum cold room temperature (unused)
Ht Maximum cold room temperature (unused)
tU1 #1 voltage sensor
tU2 #2 voltage sensor
tU3 #3 voltage sensor
tA` #1 current sensor
TA2 #2 current sensor
Hm Time menu
15
Access alarm code (Maximum of 50 record)
Step
Action
1
Press
Display SEC
Phenomenon and description
2
Press
Display A01
3
Press
Display alarm code in A01
4
Press
Display A02
5
Press
Display alarm code in A02
6
…
…
7
Press
Exit (or exit automatically after waiting for 15 seconds)
Exact timing of the alarm
Step
Action
1
Press
2
Press
3
Press
4
Press
5
Press
6
Press
7
Press
8
Press
9
Press
10
Press
11
Press
12
Press
13
Press
14
Press
Display SEC
Phenomenon and description
Display A01
Display alarm code in A01
Display Hr
Display the alarm exact timing: hour
Display Min
Display the alarm exact timing: minute
Display dAy
Display the alarm exact timing: day
Display Mon
Display the alarm exact timing: month
Display yEA
Display the alarm exact timing: year
Exit (or exit automatically after waiting for 15 seconds)
16
Upload the program from the controller to Hot-Key
Step
Action
Phenomenon and description
1
Insert Hot key when the controller is on
2
Press
The uPL message will appear followed by a fashing End label (Note: If Err is displayed, it means it failed to upload the program to hot key. Please restart the process.)
3
Press
End will stop fashing
4
Turn off the controller and remove the Hot key
5
Turn on the controller
Download the program from Hot-key to controller
Step
Action
Phenomenon and description
1
Turn off the controller
2
Insert Hot key
3
Turn on the controller
The doL message will blink followed by a fashing End label (Note: If Err is displayed, it means it failed to download the program to Hot key. Please restart the process.)
4
Controller will restart working with the new parameters after 10 seconds
5
Remove Hot key
17
9. Networking
Dixell XWEBPRO Serial Address – Wiring
· Connect to the ModBUS network using cable with 2 or 3 shielded wires,
minimum section 0.5mm2 (e.g. BELDEN8772) · Do not connect shield to ground. ·
Do not connect the “Gnd” terminal. · Remember to draw a map of the line. This
will assist you in finding fault with communication issues. · Please respect
the polarity of RS485 devices.
ZX CDU Connected to XWEB PRO
· ZX CDU connected to the Dixell XWEBPRO with the Intelligent Store Solution
Module using RS485 ModBUS. · Connect the ZX CDU to the ModBUS network as shown
in Figure 5. Connect the network cable to the three terminal connec
tor on the XWEB port that has been configured as ModBUS port (COM 12, 13, 14).
· Connect port “13” of XWEBPRO to port “RS485 +” of CoreSenseTM and port “12”
of XWEB300D to port “RS485 ” of CoreSense
for RS485 communication.
XWEB300D Connected to the Intelligent Store Solution Module
Correct Network Wiring
Incorrect Network Wiring
18
ZX/ZXL-TWM/TEM Condensing Unit Electrical Wiring Diagram
TWM/TEM : 380/420V, 50Hz, 3Ph + N NOTES:
BU
U
1.Dashed Line ”
” is wired by installer
2.Earth “E” wire termination not shown for clarity.
BU
YE
V
052-3885-00 04/13/2023
EXV
P LP SW
YE
DISCHARGE PRESSURE TRANSDUCER
DISCHARGE SENSOR DLT
PHE SENSOR VAPOR-IN
PHE SENSOR VAPOR-OUT
FIXED LP SAFETY SWITCH
ELECTRONIC EXPANSION VALVE
19
RD
W
RD BK
N PE
E Q1
BU YE RD
K1
BU YE RD
T1 T2 T3 M1
2/T1
1/L1
4/T2
3/L2
6/T3
5/L3
RS485
RD
Q2
Q3
9
95
96
A1-RST 10
/B:3
BU
1
2
3
BN BK BU
RD 8
GY
F5
5
1
3
2
BK 11
4
6 A1-DI1 /B:2
BN
L1 L2 M21
L3
WH 4
RD 5
ANALOG INPUT (0-10V)
WH
RD
ANALOG INPUT (0-10V)
L1 L2 L3 M22
YE BU
YE BU
6 GY
7 /B:3 BU
A11
T2
T1
M2
M1
A1
EV + – G + – VNR + – DI3 AI7 AI6 AI5 AI4 AI3 AI2 AI1 H-K COMMUNICATE
F1
T1
T2 ANALOG OUTPUT (0-10V)
-+
R S T TO1 TO2
CONTROLLER
250VAC 5A
NEUTRAL
DI1 DO4 C2 DO3 DO2 C1 DO1 DO5
B U Y E
R D
B N
B K
B N
B K
B K
B K
B K
B K
B K
B U
G Y
R D
Y E
B U
A1-T01 /B:3
45
12
/B:7
/A:5
/B:5 /A:3
19
18
17
R2
K1
BK
B3
BU 15
BU 8
1 RD
16 BN
24VAC 20VA
7 BN
TF2
230V 3
BK
BN BU
13 BN
14
A1-C2 /B:2
RD 1
7 BN
230V BK 3
TF1
24VAC 20VA
8 BU
ALARM
AL1 AL2
ZX ONLY
SENSOR AMBIENT
ZXL ONLY
ZXL ONLY
10. Electrical Connections
11. Installation, System processing and commissioning
Utmost care must be taken while handling the Simplex ZX condensing unit.
Please go through the contents below to ensure proper handling. 11.1 Location
and Fixing Simplex ZX unit should always be installed in a location that
ensures suffcient air fow. The minimum operating space for unit is described
in below fgure. Both service access and airfow have been considered in making
these recommendations. Where multiple units are to be installed in the same
location, the contractor needs to consider each individual case carefully.
There can be many variations of unit quantities and available space and it is
not the intention of this manual to go over these. Ideally, the unit should be
mounted on a solid concrete slab with anti vibration pads between unit feet
and concrete. However, the Simplex ZX condensing unit has also been designed
for wall mounting on suitable brackets. Wall mounting brackets are not
included. Another factor to consider in fnding a good installation site is the
direction of the prevailing wind. For example, if the air leaving the
condenser faces the prevailing wind, the air fow through the condenser can be
impeded, causing high condensing temperatures ultimately resulting in reducing
unit life. A baffe or defector plate could be a remedy for this situation.
11.2 Location and Fixing All interconnecting pipes should be of refrigeration
grade, clean, dehydrated and must remain capped at both ends until
installation. Even during installation, if the system is left for any
reasonable period (say two hours), pipes should be re capped to prevent
moisture and contaminants from entering the system. Do not assume that the
service connection sizes on the unit (at the service valves) are the correct
size to run your interconnecting refrigeration pipes. The service valve sizes
have been selected for convenience of installation and in some cases (larger
units) these may be considered too small. However, for the very short pipe run
within our units, these service connection sizes are adequate. The pipe should
be sized to ensure optimum performance and proper oil return. The sizing must
also consider the full capacity range through which this particular unit will
need to operate. Pipe runs should be kept as short as possible, using the
minimum number of directional changes. Use large radius bends and avoid
trapping of oil and refrigerant. This is particularly important for the
suction line. The suction line should ideally slope gently towards the unit.
Recommendation slope is 1/200~1/250. P traps, double risers and reduced pipe
diameters may be required for suction lines where long vertical risers cannot
be avoided. All pipes should be adequately supported to prevent sagging which
can create oil traps.
20
The recommended pipe clamp support distance is shown in the table.
Tube Size 1/2 inch 5/8 inch 7/8 inch 1 1/8inch 1 5/8inch
Max distance between 2 clamp supports 1.20 m 1.50 m 1.85 m 2.10 m 2.27 m
11.3 Refrigerant line insulation · Insulate suction lines from the evaporators
to the condensing unit with minimum 1″ thickness closed cell type
insulation on low temperature circuits. · Liquid lines of vapour injection
(ZXL unit) to be minimum of 3/4″ insulation. · Suction and liquid lines should
never be taped or soldered together.
11.4 Electrical · All electrical work must be done in accordance with the
National Electrical Code and existing local codes. · Power supply must be the
same as specifed on the unit’s name plate. · Voltage fuctuations in excess of
10 percent must be corrected. · Before starting the unit, ensure that all
protective devices are in place and that all wiring is secure.
11.5 Brazing Recommendation
Maintain a fow of oxygen free nitrogen through the system at a very low
pressure during brazing. Nitrogen displaces the air and prevents the formation
of copper oxides in the system. If copper oxidization is allowed to form, the
copper oxide material can later be swept through the system and block screens
such as those protecting capillary tubes, thermal expansion valves, and
accumulator oil return holes. This minimizes any entry of contaminants and
moisture. · Remove the liquid line connection cap. · Then remove the suction
connection cap. · Open both valves midway. · Care should be taken to avoid the
holding charge from releasing too quickly. · Be sure tube ftting inner
diameter and tube outer diameter are clean prior to assembly. · Since both
tubes are extended from the condensing unit housing, we recommend insulating
the housing by using a
wet cloth on the copper tubing. · Recommended brazing materials: a copper /
phosphorous or copper / phosphorous / silver alloy rod should be used
for joining copper to copper whereas to join dissimilar or ferrous metals, use
a silver alloy rod, either fux coated or use additional fux. · Use a double
tip torch.
OUTSIDE
INSIDE UNIT
End of Tube
During brazing protect housing with damp cloth
During brazing pull back fire
insulation
21
11.6 Expansion Valve Selection Consideration
As the Simplex ZXL units are with vapour injection compressors, (except the ZX
units), need to consider subcooled liquid temperature while selecting the
expansion valve as given below.
Standard supply temperature °C
R404A
Evaporation temperature °C
40 35 30 25 20 15
Ambient temperature °C
20
27
32
38
43
48
8
1
3
8
13
19
4
2
6
11
15
21
0
6
9
13
18
23
5
10
13
17
21
26
9
14
17
20
24
30
13
18
21
24
28
34
11.7 Start-up & Operation
Initial pressure test (by vacuum and nitrogen).
Step by step:
a. Use a 4 port gauge manifold with 3/8″ hose and connections to the vacuum
pump. The vacuum gauge does not have to be connected for this part of the
process.
b. Connect the gauges to service ports provided on receiver valve and suction
tube. In order to remove any non condensable that may have entered the system
during installation, follow these steps:
c. Start the vacuum pump. The evaporator fan should be running, and the
compressor crankcase heater is energized at this point. This will involve
powering up the unit so it is important to disconnect the live feed wire to
the compressor contactor (so the compressor cannot run, and the crankcase
heater can be energized).
d. Open both valves on the manifold and then open the main vacuum valve on the
pump. Run the system until the vacuum level of 0.85 bar (as read on manifold
gauge) is achieved.
e. Shut off the main vacuum pump valve. Check for vacuum rise using the
manifold compound gauge. A rise would indicate a large leak.
f. If vacuum holds for 10 minutes, break vacuum with nitrogen and pressurize
to 20 bar. Check for leaks and repair leakage.
Leak Check
The success of all the subsequent commissioning depends on a leak free system,
free of contaminants, free of oxides, free of non condensable’ s, that has
been evacuated to a low vacuum and charged with the prescribed refrigerant.
Leak test is particularly important for feld connected systems. Typically,
feld systems lose as much as 20%30% of their refrigeration charge annually.
This is not only an unnecessary expense but also damages the environment.
Compressor oil can be lost at the same time as refrigerant and eventually lead
to compressor failure. (Time spent on leak test will eventually reduce the
time spent on the evacuation process).
Ensure that all service valves are open during the leak test process. It is
important to recheck all joints within the unit as well as the external
joints. · The unit is shipped with a holding charge of dry nitrogen and should
be leak free. · Ensure that the test pressure do not exceed the system design
pressures. · Do not expose system pressure control LP to test pressures below
the design pressure. This can damage the pressure
controls. · Using an approved, calibrated electronic gas leak detector, leak
test the entire system paying attention to all joints.
22
· Periodically check functionality of the electronic leak detector during this
process. · To further check system integrity, spray a soapy water solution
over joins then visually inspect for bubbles. · Leave the system under
pressure for a designated period (24 Hours). · Check and record the ambient
temperatures and the system pressure with calibrated approved instruments.
This process is
to be carried out every 8 12 hours during the pressure testing process. · If
the test pressures cannot be maintained, repeat the leak testing process
employing the isolation of sections of the system
to determine the source of leaks. Repair the leak and repeat the leak testing
process until system can be signed off as leak free and approved by authorized
personnel. · Record findings and confirm pressure testing process completion.
Evacuation · After the system is leak checked, connect approved dual stage
vacuum pump sized to application with fresh oil in the
vacuum pump. · Ensure all inline system shut off valves and solenoid valves
are fully open. · Evacuate the system to 300 microns. · In case of non
availability of micron gauge, a triple evacuation is recommended.
Charging and commissioning reminders: · The scroll compressor design requires
system charging with liquid refrigerant into the liquid line. · Do not vapor
charge the Simplex ZX Scroll unit. After ensuring all valves are opened and
system is vacuumed properly, only
then start the refrigerant charging process.
Step by step: a. Ensure that there is no power supply to the Simplex ZX unit.
The Liquid Line solenoid needs to be kept open for the charging
process and this may require a temporary power feed to it. b. Connect the
refrigerant cylinder to main service hose and purge line at the manifold end.
c. Ensure correct orientation of the refrigerant cylinder. Follow cylinder
labeling/instructions so that liquid refrigerant can be
charged into the system. This will be charged through the high pressure side
of the manifold and Simplex ZX unit liquid service valve. Charge at least 70%
of the required refrigerant in the system before starting the comp. Please do
not bypass LP cutout during initial operation. d. The compressor can then be
started, and the unit continued to be charged (with controlled liquid
refrigerant through the suction service valve). The quantity of charge should
always be measured. See note. e. The system needs to be operated down to its
design evaporating temperature before you can be sure the charge is correct.
It is at this point that the normal refrigeration operational checks can be
carried out such as checking the liquid line sight glass for violent bubbles
and the operating pressures. Continue to charge about 1 kg after all the
bubbles are gone in the liquid line sight glass. During this charging process
the controller might show alarms E47 (EXV fully open) and E48 (injection
shortage) which is to be ignored as unit is not completely charged.
Refrigerant charging is regarded full/complete when the operating temperature
of the system has been stable for some time and the liquid line sight glass is
clear.
23
11.8 Additional Oil Charing in the System
Copeland Simplex ZX units are supplied with oil charge in the compressor as
well as the oil separator / reservoir. However, depends on the length of
interconnecting piping and the refrigerant charge in the system, there might
be additional oil requirement. If the oil level in the oil reservoir goes
below the lower sight glass after the system running for some time, customer
needs to charge additional oil charge through suction line using manual oil
pump and raise the oil level at least up to mid level of the lower sight
glass.
Qualifed refrigerant and oil
Refrigerant R404A
Oil
Emkarate RL 32 3MAF Mobil EAL Arctic 22 CC
11.9 Additional Oil Charing in the System · Check all the valved are fully opened · Check the oil level of compressor and the reservoir after running the unit for some time. · Check the discharge line temperature which is to be below 125 deg C. · Suction and discharge pressures are within the operating envelope. · The operating current is corresponding to the suction and discharge pressures. · The compressor bottom shell is within the safe range as shown below
Oil sump temperature (°C)
100 90 80 70 60 50 40 30 20 10 0
-10
Evaporation temperature (°C)
-20
-15
-10
-5
0
5
Safe Area
Feasible
Insecure area (Excessive cooling diluent)
0
10
20
30
40
Evaporation temperature (°C)
10 30 20 10 0 -10
50
Oil sump temperature (°C)
24
11.10 Maintenance Condenser Fins Condenser fns become dirty over time as
ambient air is induced to the condenser. Dirty coil surfaces result in high
condensing temperatures and poor unit performance. Regular cleaning is
recommended with frequency depending on the installation and the surrounding
environment. As a general guide, it is advisable to do this at least once
every two months. Fins should be cleaned with liquid detergent diluted with
clean water. Before washing, a light brush downward (in the direction of the
fns) should be done to remove heavy deposits. Electrical Connections Check
tightness of electrical connections occasionally Routine Leak Test All joints
should be checked for leaks during site visits. All joints should be leak
tested once a year. Condenser Fan(s) and Motor(s), an annual inspection of
these items is recommended. Fastenings may loosen, bearings may wear, and fans
may require cleaning of solid deposits which can cause imbalance.
TURN OFF OR DISCONNECT THE ELECTRICAL POWER SOURCE BEFORE CLEANING THE
CONDENSER COIL OR DOING MAINTENANCE.
25
12. Troubleshooting
Alarm codes
Level
Warning Alarm Lock
Description
The unit (including the compressor) will keep running, but some status & data
is already in an unsafe range; alarm dry contact will not close; reset
automatically The unit (including the compressor) may run not with full
functions; alarm dry contact will not close; reset automatically The unit
(including the compressor) stops working; alarm dry contact will close; manual
reset is needed
Diagnostics
Alarm code
Description
Possible reason Hardware error
Action
E01
Suction pressure probe failure alarm
Probe failure or out of range
No (ZXD Unit Only)
Reset
Automatic Reset when the probe restarts working
E02
Condensing temperature probe failure alarm
Probe failure or out of range Function: fan speed control is Automatic Reset when the
( 40 ~ 110°C)
disabled
probe restarts working
E03
Discharge temperature probe failure alarm
Probe failure or out of range ( 40 ~ 180°C)
Function: discharge temperature protection is
disabled
Automatic Reset when the probe restarts working
E04
PHE vapor inlet temperature Probe failure or out of range
probe failure alarm
( 40 ~ 110°C)
Function: PHE Superheat Control is disabled(ZXL/ZXB
unit only)
Automatic Reset when the probe restarts working
E05
PHE vapor outlet temperature
probe failure alarm
Probe failure or out of range ( 40 ~ 110°C)
Function: PHE Superheat Control is disabled (ZXL/ZXB unit only)
Automatic Reset when the probe restarts working
E06
Ambient temperature probe Probe failure or out of range
failure alarm
( 40 ~ 110°C)
Related functions are disabled
Automatic Reset when the probe restarts working
E09 Current sensor 1 error alarm
Out of range
Related functions are disabled
Automatic Reset when the probe restarts working
E10 Current sensor 2 error alarm
Out of range
Related functions are disabled
Automatic Reset when the probe restarts working
E11 Voltage sensor 1 error alarm
Out of range
Related functions are disabled
Automatic Reset when the probe restarts working
E12 Voltage sensor 2 error alarm
Out of range
Related functions are disabled
Automatic Reset when the probe restarts working
E13 Voltage sensor 3 error alarm
Out of range
Related functions are disabled
Automatic Reset when the probe restarts working
26
Alarm code
E20 L20
L21 E22 E23
Description Missing phase alarm Missing phase lock
Possible reason
Action
Electrical Error
One or two phases of compressor power supply lost or Voltage sensors do not
work (3 ph unit only)
The compressor will be tripped
Missing phase alarm happened frequently
The compressor will be tripped and the unit will be
locked
Wrong phase sequence lock
Compressor power supply has wrong sequence (3 phase
unit only)
The compressor will be tripped and the unit will be
locked
Imbalanced 3 phase warning
3 Ph currents are not balanced
(3 phase unit only)
No
Over current alarm
Compressor current is larger than settings
The compressor will be tripped
Reset
Automatically with time delay
Press Start >5 sec or manually power off and
power on
Press Start >5 sec or manually power off and
power on
Automatically with time delay
Automatically with time delay
L23
Over current lock
Over current alarm happens frequently
The compressor will be tripped and the unit will be
locked
Press Start >5 sec or manually power off and
power on
E24
Compressor running circuit open alarm
Compressor running circuit open
(1 phase unit only)
The compressor will be tripped
Automatically with time delay
L24
Compressor running circuit
open lock
Running circuit open alarm happens frequently
The compressor will be tripped and the unit will be
locked
Press Start >5 sec or manually power off and
power on
E25
Compressor starting circuit
open alarm
Compressor starting circuit open
(1 phase unit only)
The compressor will be tripped
Automatically with time delay
Compressor starting
Compressor starting circuit
The compressor will be
Press Start >5 sec or
L25
circuit
open alarm happens
tripped and the unit will be manually power off and
open lock
frequently
locked
power on
E26
Low voltage alarm
Voltage is lower than settings; or voltage sensors do not work
The compressor will be tripped
Automatically with time delay
L26
Low voltage lock
Low voltage alarm happens frequently
The compressor will be tripped and the unit will be
locked
Press Start >5 sec or manually power off and
power on
E27
Over voltage alarm
Voltage is higher than settings
The compressor will be tripped
Automatically with time delay
L27
Over voltage lock
Over voltage alarm happens frequently
The compressor will be tripped and the unit will be
locked
Press Start >5 sec or manually power off and
power on
E28
Compressor internal protector open warning
Compress internal protector is open; or current sensors do
not work
No
The compressor will be tripped
E30
No controller power supply alarm
Controller lost power supply
27
Alarm code
E40 L40 E41 E44 L44 E46 E47 E48 E50 E56 L56
Description
Possible reason
Action
Reset
High pressure switch alarm
High pressure switch lock
Refrigeration system error
High pressure switch is open
High pressure switch alarm happens frequently
The compressor will be tripped
The compressor will be tripped and the unit will
be locked
Automatically when HP switch closes
Press Start >5 sec or manually power off and power on
Low pressure switch alarm
Low pressure switch is open
The compressor will be tripped
Automatically when LP switch closes and time delay
High discharge temperature alarm
Higher discharge temperature lock
High condensing temperature alarm
EXV Full open warning
Less injection warning
High side liquid back warning
Compressor oil shortage alarm Compressor oil shortage lock
Discharge temperature is higher than settings
High discharge temperature alarm happens frequently
Condensing temperature is higher than settings
Less refrigerant charge or leakage
Less refrigerant charge or leakage
Suction liquid back or injection too much
Compressor lack of oil
Compressor lack of oil alarm happens frequently
The compressor will be tripped
The compressor will be tripped and the unit will
be locked
No
No
No
No
The digital compressor will be tripped
The compressor will be tripped and the unit
will be locked
Automatically when discharge temperature is lower than settings and time delay
Press Start >5 sec or manually power off and power on
Automatically when condensing temperature is lower than settings
Automatically when EXV is not at full open
Automatically when PHE super heat is smaller than settings
Automatically when the difference of discharge temperature and condensing
temperature is higher than settings and time delay
Automatically with time delay
Press “Start” > 5 seconds or man ually power cycle
Misc. Error
E80
RTC warning
The time is confgured for the new controller
No
Automatically when fnish time confguration
E81
RTF warning
Communication error between MCU and unit clock
No
Automatically when the communication recovers
E82
Probe confguration error alarm
The same probes are confgured
Automatically when the
No
probes are confgured
correctly
E83
Digital inputs confguration
error alarm
The same digital inputs are confgureds
The related functions will be disabled
Automatically when the digital inputs are confgured
correctly
E84
Compressor confguration error alarm
Digital compressor and solenoid valve confguration
does not match
The compressor will not work
Manually power off and power on after the compressor confguration
is right
E85
Injection probe confguration
error alarm
EXV and injection confguration do not match
EXV will not work
Automatically when injection probe is confgured correctly
Hold “start” button for 5s or
manual power off and on,
L86
EEPROM R/W error lock
write/read error into EEPROM
The compressor will tripped and the unit will be locked
alarm will disappear when the communication
between MCU and
EEPROM is success.
28
13. System Start-Up and Operational Check Sheet
Facility/Customer Name: Address:
Contact Details: Installer”
Installation Date:
CDU Model: Serial Number: CDU Location: Indoor Unit Make/Model:
Client Details Condensing Unit Info:
Room/Case ID :
System Details
Pipe Length (approx.) :
OAT @ Start-Up/Check :
PSI Leak Test :
PSIG
Duration :
Hours
System is Leak Tight :
Y/N
Triple Evacuation :
Y/N
Micron Gauge Reading:
microns
Total Evacuation :
PSIG @ # of Hrs
Refrigerant :
Total Charge :
Kg.
Sight Glass Clear :
Y/N
Evap. Fans Running :
Y/N
Liquid Line Insulation :
Y/N
Sound and Vibration :
System Operation
COMP Voltage :
V
COMP Current :
A
Standing Pressure
PSIG/Bar
Suction Pressure :
PSIG/Bar
Liquid Line Pressure :
PSIG/Bar
COMP Suction Temp :
°C
COMP Disch. Temp :
°C
Liquid Line Temp :
°C
Compressor SH :
K
Subcooling :
K
Adjustable LP Setpoint :
PSIG
Design/Operating Temp:
°C
Actual Room/Case Temp :
°C
Condenser Fins :
Comments
Prepared by: Date:
Confirmed by: Date:
29
Notes
30
Contact us:
United Arab Emirates Jebel Ali Free Zone P.O. Box 26382, Dubai United Arab
Emirates Toll Free: 8000 441 3428 Tel: +971 4 8118100 Fax: +971 4 8865465
South Africa Workshop 17 Fire station 16 Baker Street Rosebank Gauteng, South
Africa, 2196 South Africa Toll Free: 0800 980 3711 Tel: +27 10 599 0301
Saudi Arabia P.O. Box 34332 3620 2nd Industrial City, 67 St. Dammam, Saudi
Arabia Toll Free: 8008 443 426 Tel: +966 3 8147560 Fax: +966 3 8147570
Egypt P.O. Box 11799 11 Mustafa Refaat Street Sheraton, Heliopolis Cairo,
Egypt Tel: +20 2 226 5854
31
About Copeland
Copeland, a global provider of sustainable climate solutions, combines
categoryleading brands in compression, controls, software and monitoring for
heating, cooling and refrigeration. With best inclass engineering and design
and the broadest portfolio of modulated solutions, we’re not just setting the
standard for compressor leadership; we’re pioneering its evolution. Combining
our technology with our smart energy management solutions, we can regulate,
track and optimize conditions to help protect temperaturesensitive goods over
land and sea, while delivering comfort in any space. Through energyeffcient
products, regulationready solutions and expertise, we’re revolutionizing the
next generation of climate technology for the better.
Scan to visit:
Copeland To learn more, visit copeland.com
©2024 Copeland LP. All rights reserved.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>