LEVITON ODC20-MDW Multi-Technology Ceiling-Mount Occupancy Sensor User Manual

June 3, 2024
Leviton

LEVITON ODC20-MDW Multi-Technology Ceiling-Mount Occupancy Sensor

LEVITON ODC20-MDW Multi-Technology Ceiling-Mount Occupancy
Sensor

Occupancy Sensor with Integrated Photocell, Line Voltage, Multi-Tech, Ceiling Mount, 2000SF, 120-277V, Extended Range Lens installed, Provolt™ Occupancy Sensor with Photocell, Provolt™ lighting control, Line Voltage, 8′-12′ Ceiling, Multi-Technology, 2000 sq ft, Daylighting, Auto-Calibration, 120-277V AC/CA 50/60HZ. UL/CE, RoHS & CEC Title 20/24 compliant. Color: White. The Leviton Provolt™ Series combine line voltage occupancy sensors and photocells into a self-contained unit. The integrated design alleviates the need for separate power pack and occupancy sensor wiring making it a low-cost, efficient energy solution for new construction and retrofits.

Technical Information

Product Features

  • Application : Code Compliance, Auto ON/Auto OFF, Manual ON/Auto OFF
  • Color : White
  • Feature : Line Voltage
  • Grade : Commercial
  • Mounting : Ceiling Mount
  • Product Line : Provolt
  • Sensor Technology : Multi-Technology: Passive Infrared (PIR)/Ultrasonic (US)
  • Sensor Type : Occupancy, Photocell Title 24 Compliant : Yes
  • Performance Specifications
  • Coverage (Sq.Ft.) : 2000
  • Pattern : 360°

Electrical Specifications

  • Current Consumption : 60-30ma
  • Frequency : 50/60Hz
  • Load Rating : 120V, 50/60Hz: 8A, Electronic Ballast, 800W/VA, Tungsten, Ballast, 1/4 HP Motor – 230V, 50Hz: 6A/6AX, Electronic Ballast, Magnetic Ballast,
  • 1200W/VA, 1/3 HP Motor -277V, 50/60Hz: 5A, Electronic Ballast, 1200VA, 1/3 HP Motor
  • Neutral Wire Connection : Required
  • Voltage : 120/230/277 VAC

Standards and Certifications

  • Listings : Can be used to comply with IECC, ASHRAE 90.1 and Title 24, Part 6 occupancy/vacancy sensing, automatic shut off and daylight harvesting requirements, UL
  • 773A (Occupancy Standard), UL 924 (Emergency Equipment), cUL listed, CE compliant, NOM certified, RoHS compliant, NY LLC48 compliant

Mechanical Specifications

  • Mounting Type : Ceiling Mount
  • Size : Width 4.80″ (121.92mm), Depth 2.39″ (60.71mm)
  • Environmental Specifications
  • Relative Humidity : 0% to 90% non-condensing
  • Storage Temperature Range : -15° to 160°F (-26° to 71°C)

Type

  • Product Type : Occupancy Sensor and Photocell

Warranty

  • Warranty : 5-Year Limited

Features and Benefits

  • Sensors combine both PIR and U/S technology for unrivaled performance and reliability. Sensors use PIR technology to initially turn lights ON, and use U/S technology to keep the lights ON. Exclusive false-detection software assures lights are ON only when needed.
  • Auto-Adapting: Time delay and sensitivity are continually adjusted to occupancy pattern of use
  • Configurable for Manual ON/Auto OFF or Auto ON/Auto OFF
  • Delayed OFF Timer: The sensor will turn lights OFF if no motion is detected after a specified time
  • Exclusive Walk-through Feature: Provides increased energy savings by not leaving the lights ON for an extended period after only momentary occupancy
  • False Detection Timer: (M/T) The PIR scans for movement and shuts lights off after 31 minutes preventing false triggers from HVAC systems
  • Time delay and saved settings are protected during power outages and will return to the last known state
  • Output short circuit protection
  • Industry-exclusive self-configuring local manual switch input: Momentary or maintained switches are supported
  • Presentation Mode feature for slide or film presentations allows push buttons to turn lights OFF and keep them OFF while the room is occupied
  • Adjustable Time Delay: 30s, 5min, 10min, 20min, 30min
  • Test Mode for simplified commissioning
  • Manual Switch and Emergency Override are Class 1 and Class 2 circuits. Class 2 circuits provided for flexibility
  • Industry-exclusive “fail-safe” circuitry: In the event of product failure, Return-to-Closed feature causes the relay to default ON which eliminates life safety concerns
  • Industry-exclusive H.I.S. (High Inrush Stability) technology designed to handle today’s high inrush electronic ballast loads and offer unmatched durability and service
  • Robust and reliable mechanically held 10A latching relay provides dependability and robust performance for all load types and provides energy savings over electronically held relays
  • Lenses are easily replaceable and color-coded red (mid-range) and black (extended range) for contractors and end-users to easily identify lenses from the ground
  • Red Visual LED indicator – Blinks when infrared is detecting motion and during photocell manual calibration; solid during device malfunction
  • Green Visual LED indicator – Blinks when U/S is detected; solid during auto calibration
  • Yellow Visual LED indicator – Blinks during test mode; solid with emergency/BMS input

LEVITON ODC20-MDW Multi-Technology Ceiling-Mount Occupancy Sensor
1

Leviton Manufacturing Co., Inc.
201 North Service Road, Melville, NY 11747
Telephone: +1-800-323-8920 · FAX: +1-800-832-9538 · Tech Line (8:30AM-7:30PM E.S.T. Monday- Friday):+1-800-824-3005

Leviton Manufacturing of Canada, Ltd.
165 Hymus Boulevard, Pointe Claire, Quebec H9R 1E9 · Telephone: +1-800-469-7890 ·
FAX: +1-800-824-3005 · www.leviton.com/canada

Leviton S. de R.L. de C.V.
Lago Tana 43, Mexico DF, Mexico CP 11290 · Tel.: (+52)55-5082-1040 · FAX: (+52)5386-
1797 · www.leviton.com.mx

Visit our Website at:www.leviton.com
© 2021 Leviton Manufacturing Co., Inc. All Rights Reserved. Subject to change without notice.

Leviton has a global presence.
If you would like to know where your local Leviton office is located please go to: www.leviton.com/international/contacts/

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals