IDEAL 102 Luminaire Disconnects Installation Guide
- September 9, 2024
- IDEAL
Table of Contents
102 Luminaire Disconnects
“`html
Specifications
-
Voltage Rating: 600 Volts Maximum
-
Current Rating: 6 Amps Maximum
-
Wire Range:
- Solid: 12-18 AWG
- Stranded: 12-14 AWG (19 Strand or less)
- Stranded Tin Bonded: 12-14 AWG (19 Strand or less), 16 AWG (26
Strand or less), 18 AWG (16 Strand or less)
-
Temperature Rating: 105°C (221°F) maximum
-
Flame Rated UL94V-0
Product Usage Instructions
Conductor Installation
-
Wiring must comply with all applicable electrical codes.
-
Turn off power before removing or installing disconnect.
-
Strip wires to 3/8 inch (9.5 mm).
-
Grip black ballast wire firmly and push conductor into the
white cap port marked with a black circle. -
Grip white ballast wire firmly and push conductor into the same
side of the connector in the port marked with a white circle. -
Grip black supply wire firmly and push conductor into the port
opposite the black ballast wire. -
Grip white supply wire firmly and push conductor into the
remaining port. -
Use only one conductor per port and ensure that no copper is
exposed on any of the wires inserted. -
Refer to disconnect de-mate/mate installation instructions
below when replacing ballasts. -
The wire insertion side of this product is listed for ONE TIME
USE ONLY. DO NOT REMOVE AND REPLACE WIRES.
Disconnect De-Mate / Mate Installation
-
To de-mate, grasp the disconnect at each end and pull apart to
separate the disconnect halves. Do NOT pull on wires. -
To mate the disconnect, grasp each disconnect half, align
halves, and push together. -
Insert black ballast wire into the port marked with a black
circle.
FAQ
Q: What should I do if I need to replace the ballasts?
A: When replacing ballasts, refer to the disconnect de-mate/mate
installation instructions provided in the manual.
Q: Can I reuse the wire insertion side of the product?
A: No, the wire insertion side is listed for ONE TIME USE ONLY.
Do NOT remove and replace wires once inserted.
“`
PowerPlug® Luminaire Disconnect Model 102
Installation Instructions:
To be sold only with installation instructions.
WARNING: This is a current rated device. Use in applications involving amperage beyond its rating can be dangerous and cause electrical fires. See note on this page for allowable current and voltage levels and do not exceed those levels.
Instructions:
Conductor installation:
1. Wiring must comply with all applicable electrical codes.
2. Turn off power before removing or
3/8″ Strip Length Indicator
installing disconnect.
3. Strip wires to 3/8 inch (9,5 mm).
4. Grip black ballast wire firmly and push conductor
into white cap port marked with black circle.
5. Grip white ballast wire firmly and push conductor
into same side of connector in port marked with
white circle.
6. Grip black supply wire firmly and push conductor into port opposite black ballast wire.
7. Grip white supply wire firmly and push conductor into remaining port.
8. Use only one conductor per port and assure that no copper is exposed on any of the wires
inserted.
9. See disconnect de-mate/mate installation instructions below when replacing ballasts.
10. The wire insertion side of this product is listed for ONE TIME USE ONLY. DO NOT
REMOVE AND REPLACE WIRES.
DANGER NEVER remove wires from product as contact with electricity can cause serious injury or death. Shut off power at the circuit breaker or remove fuse when installing this product.
SAFETY NOTICE Improperly installed electrical wiring can be dangerous and cause electrical fires. This product must be used in accordance with the current rating and wire sizes listed. Consult local building code before doing any electrical work. COPPER TO COPPER ONLY. Do not use on Aluminum. Temperature rating: 105 C (221F) maximum. Flame Rated UL94V-0.
Voltage Rating: 600 Volts Maximum Current Rating: 6 Amps Maximum Rated for a limited number of current-interrupting operations.
Wire Range: Solid: Stranded: Stranded Tin Bonded:
12-18 AWG 12-14 AWG (19 Strand or less) 12-14 AWG (19 Strand or less) 16 AWG (26 Strand or less) 18 AWG (16 Strand or less)
Disconnect de-mate / mate installation 1. To de-mate, grasp disconnect at each
end and pull
apart to separate the disconnect halves. Do NOT pull on wires. 2. To mate the
disconnect, grasp each disconnect half, align halves, and push together.
Insert black ballast wire into port marked with a black circle
Line Side Wires 12 – 18 AWG
Load Side Ballast Wires 18 AWG (typ.)
IDEAL INDUSTRIES, INC. 1375ParkAvenue
Sycamore, IL 60178, U.S.A. 800-435-0705
Customer Assistance
www.idealind.com ND 6184-9
PowerPlug® Luminaire Disconnect Model 102
Installation Instructions:
To be sold only with installation instructions.
WARNING: This is a current rated device. Use in applications involving amperage beyond its rating can be dangerous and cause electrical fires. See note on this page for allowable current and voltage levels and do not exceed those levels.
Instructions:
Conductor installation:
1. Wiring must comply with all applicable electrical codes.
2. Turn off power before removing or
3/8″ Strip Length Indicator
installing disconnect.
3. Strip wires to 3/8 inch (9,5 mm).
4. Grip black ballast wire firmly and push conductor
into white cap port marked with black circle.
5. Grip white ballast wire firmly and push conductor
into same side of connector in port marked with
white circle.
6. Grip black supply wire firmly and push conductor into port opposite black ballast wire.
7. Grip white supply wire firmly and push conductor into remaining port.
8. Use only one conductor per port and assure that no copper is exposed on any of the wires
inserted.
9. See disconnect de-mate/mate installation instructions below when replacing ballasts.
10. The wire insertion side of this product is listed for ONE TIME USE ONLY. DO NOT
REMOVE AND REPLACE WIRES.
DANGER NEVER remove wires from product as contact with electricity can cause serious injury or death. Shut off power at the circuit breaker or remove fuse when installing this product.
SAFETY NOTICE Improperly installed electrical wiring can be dangerous and cause electrical fires. This product must be used in accordance with the current rating and wire sizes listed. Consult local building code before doing any electrical work. COPPER TO COPPER ONLY. Do not use on Aluminum. Temperature rating: 105 C (221F) maximum. Flame Rated UL94V-0.
Voltage Rating: 600 Volts Maximum Current Rating: 6 Amps Maximum Rated for a limited number of current-interrupting operations.
Wire Range: Solid: Stranded: Stranded Tin Bonded:
12-18 AWG 12-14 AWG (19 Strand or less) 12-14 AWG (19 Strand or less) 16 AWG (26 Strand or less) 18 AWG (16 Strand or less)
Disconnect de-mate / mate installation 1. To de-mate, grasp disconnect at each
end and pull
apart to separate the disconnect halves. Do NOT pull on wires. 2. To mate the
disconnect, grasp each disconnect half, align halves, and push together.
Insert black ballast wire into port marked with a black circle
Line Side Wires 12 – 18 AWG
Load Side Ballast Wires 18 AWG (typ.)
IDEAL INDUSTRIES, INC. 1375ParkAvenue
Sycamore, IL 60178, U.S.A. 800-435-0705
Customer Assistance
www.idealind.com ND 6184-9
PowerPlug® Conector acoplador para accesorios luminosos – Model 102
Instrucciones de Instalación:
Para vender únicamente con instrucciones de instalación.
ADVERTENCIA: Éste es un dispositivo especificado por corriente. No exceda los niveles máximos de corriente y voltaje.
Instrucciones:
Instalación de los conductores:
1. El cableado debe cumplir todos los
códigos eléctricos aplicables.
2. Desconecte la alimentación eléctrica
Indicador de
antes de quitar o instalar el conector
longitud de
acoplador.
pelado de
3. Pele los cables 3/8″ (9,5mm).
9.5 mm (3/8″)
4. Tome firmemente el cable negro del reactor
y coloque el conductor a presión en el orificio
marcado con el círculo negro.
5. Tome firmemente el cable blanco del reactor
y coloque el conductor a presión en el ortificio
adyacente al cable negro del resactor.
6. Tome firmemente el cable negro del suministro
eléctrico y coloque el conductor a presión en el
orificio opuesto al cable negro del reactor.
7. Tome firmemente el cable blanco del suministro eléctrico y coloque el conductor a presión
en el orificio restante.
8. Use sólo un conductor por orificio y asegúrese de que no quede el cobre expuesto en
ninguno de los cuatro cables insertados.
9. Cuando reemplace los reactores, vea las instrucciones de desacoplamiento y acoplamiento
incluidas más abajo.
10. El lado de inserción de conductores de este producto está especificado para USAR UNA
SOLA VEZ. NO RETIRE Y VUELVA A COLOCAR LOS CONDUCTORES.
PELIGRO NUNCA retire los cables del producto, puesto que el contacto con la electricidad puede causar graves lesiones o la muerte. Desconecte el suministro eléctrico en el disyuntor o quite el fusible cuando vaya a instalar este producto.
AVISO SOBRE LA SEGURIDAD
El cableado eléctrico instalado incorrectamente puede ser peligroso y causar incendios eléctricos.
Este producto se debe usar de acuerdo con la especificación de corriente y los tamaños de cable
indicados. Consulte el código de construcción local antes de hacer un trabajo eléctrico.
COBRE A COBRE ÚNICAMENTE. No use el producto en aluminio. Temperatura nominal: 105°
(221°F) máximo CLASIFICACIÓN DE LLAMA UL94V-0.
Este dispositivo de desconexión está especificado para 600 V / 6 A máximo.
Clasificado para un número limitado de operaciones de interrupción de corriente
Rango de cables:
Macizos:
12-18 AWG
Trenzados:
12-14 AWG (19 hilos o menos)
Trenzado estañado: 12-14 AWG (19 hilos o menos)
16 AWG (26 hilos o menos)
18 AWG (16 hilos o menos)
Disconnect de-mate / mate installation
1. Para desacoplar, tome el dispositivo de
desconexión por ambos extremos y tire para
separar las mitades del mismo.
2. Para acoplar el dispositivo de desconexión,
tome ambas mitades del mismo, alinéelas y
presiónelas para unirlas.
Inserte el conductor negro del balasto en el orificio marcado con un círculo negro. Conductores del lado de la línea 12-18 AWG
Conductores del balasto del lado de la carga 18 AWG (típ)
IDEAL INDUSTRIES, INC. 1375ParkAvenue
Sycamore, IL 60178, U.S.A. 800-435-0705
Asistencia al cliente
www.idealind.com ND 6184-9
PowerPlug® Conector acoplador para accesorios luminosos – Model 102
Instrucciones de Instalación:
Para vender únicamente con instrucciones de instalación.
ADVERTENCIA: Éste es un dispositivo especificado por corriente. No exceda los niveles máximos de corriente y voltaje.
Instrucciones:
Instalación de los conductores:
1. El cableado debe cumplir todos los
códigos eléctricos aplicables.
2. Desconecte la alimentación eléctrica antes de quitar o instalar el conector
Indicador de longitud de
acoplador.
pelado de
3. Pele los cables 3/8″ (9,5mm).
9.5 mm (3/8″)
4. Tome firmemente el cable negro del reactor
y coloque el conductor a presión en el orificio
marcado con el círculo negro.
5. Tome firmemente el cable blanco del reactor
y coloque el conductor a presión en el ortificio
adyacente al cable negro del resactor.
6. Tome firmemente el cable negro del suministro
eléctrico y coloque el conductor a presión en el
orificio opuesto al cable negro del reactor.
7. Tome firmemente el cable blanco del suministro eléctrico y coloque el conductor a presión
en el orificio restante.
8. Use sólo un conductor por orificio y asegúrese de que no quede el cobre expuesto en
ninguno de los cuatro cables insertados.
9. Cuando reemplace los reactores, vea las instrucciones de desacoplamiento y acoplamiento
incluidas más abajo.
10. El lado de inserción de conductores de este producto está especificado para USAR UNA
SOLA VEZ. NO RETIRE Y VUELVA A COLOCAR LOS CONDUCTORES.
PELIGRO NUNCA retire los cables del producto, puesto que el contacto con la electricidad puede causar graves lesiones o la muerte. Desconecte el suministro eléctrico en el disyuntor o quite el fusible cuando vaya a instalar este producto.
AVISO SOBRE LA SEGURIDAD
El cableado eléctrico instalado incorrectamente puede ser peligroso y causar incendios eléctricos.
Este producto se debe usar de acuerdo con la especificación de corriente y los tamaños de cable
indicados. Consulte el código de construcción local antes de hacer un trabajo eléctrico.
COBRE A COBRE ÚNICAMENTE. No use el producto en aluminio. Temperatura nominal: 105°
(221°F) máximo CLASIFICACIÓN DE LLAMA UL94V-0.
Este dispositivo de desconexión está especificado para 600 V / 6 A máximo.
Clasificado para un número limitado de operaciones de interrupción de corriente
Rango de cables:
Macizos:
12-18 AWG
Trenzados:
12-14 AWG (19 hilos o menos)
Trenzado estañado: 12-14 AWG (19 hilos o menos)
16 AWG (26 hilos o menos)
18 AWG (16 hilos o menos)
Disconnect de-mate / mate installation
1. Para desacoplar, tome el dispositivo de
desconexión por ambos extremos y tire para
separar las mitades del mismo.
2. Para acoplar el dispositivo de desconexión,
tome ambas mitades del mismo, alinéelas y
presiónelas para unirlas.
Inserte el conductor negro del balasto en el orificio marcado con un círculo negro. Conductores del lado de la línea 12-18 AWG
Conductores del balasto del lado de la carga 18 AWG (típ)
IDEAL INDUSTRIES, INC. 1375ParkAvenue
Sycamore, IL 60178, U.S.A. 800-435-0705
Asistencia al cliente
www.idealind.com ND 6184-9