IDEAL 102x Luminaire Disconnect Installation Guide

September 9, 2024
IDEAL

102x Luminaire Disconnect

“`html

Product Specifications

  • Maximum Voltage: 600 Volts
  • Maximum Amperage: 6 Amps
  • Temperature Rating: 105°C (221°F) maximum
  • Flame Rating: UL94V-0
  • Rated for a limited number of current-interrupting
    operations

Product Usage Instructions

Conductor Installation:

  1. Ensure wiring complies with all applicable electrical
    codes.

  2. Turn off power before removing or installing the
    disconnect.

  3. Strip wires to 3/8 in. (9.5 mm). 18 AWG can be stripped from
    3/8 in. to 1/2 in.

  4. Grip black ballast wire and push into gray cap ports marked
    with black. Follow diagram for correct insertion.

  5. Grip white ballast wire and insert into the ports marked with
    white.

  6. Grip black supply wire and push into the port opposite the
    black ballast wire.

  7. Grip white supply wire and push into the remaining port.

  8. Use only one conductor per port and ensure no copper is exposed
    on any of the wires.

  9. Do not remove and replace wires from the insertion side as it
    is for one-time use only.

Safety Precautions:

  • Never remove wires when product is energized to prevent serious
    injury or death.

  • Shut off power at the circuit breaker or remove the fuse before
    installation.

  • Improperly installed wiring can lead to electrical hazards and
    fires.

  • Consult local building codes before any electrical work.

  • Use copper wires only; do not use on aluminum.

Frequently Asked Questions (FAQ)

Q: Can I exceed the maximum voltage and amperage ratings?

A: Exceeding the maximum voltage and amperage levels can be
dangerous and may cause electrical fires. Always adhere to the
specified ratings.

Q: Can I reuse the wire insertion side?

A: The wire insertion side is designed for one-time use only. Do
not remove and replace wires from this side.

Q: What wire sizes are compatible with the disconnect?

A: Refer to the specifications for wire range compatibility.
Ensure proper wire sizes are used for safe operation.

“`

PowerPlugTM Luminaire Disconnect Model 102x
Installation Instructions:
To be sold only with installation instructions.

WARNING: This is a current rated device. Use in applications involving amperage beyond its rating can be dangerous and cause electrical fires. See note on this page for allowable current and voltage levels and do not exceed those levels.

Instructions:

Conductor installation:

1. Wiring must comply with all

applicable electrical codes. 2. Turn off power before removing or
installing disconnect.

3/8″ Strip Length Indicator

3. Strip wires to 3/8 in. (9,5 mm). 18 AWG

can be 3/8 in. to 1/2 in. strip.

4. Grip black ballast wire firmly and push

conductor into gray cap ports marked

with black. See diagram at right for proper

wire insertion for ballast configuration.

5. Grip white ballast wire firmly and push

conductor into same side of connector

in ports marked with white.

6. Grip black supply wire firmly and push

conductor into port opposite black ballast wire. (black circle)

7. Grip white supply wire firmly and push conductor into remaining port.

8. Use only one conductor per port and assure that no copper is exposed on any of the wires

inserted.

9. See disconnect de-mate/mate installation instructions below when replacing ballasts.

10. The wire insertion side of this product is listed for ONE TIME USE ONLY. DO NOT REMOVE AND

REPLACE WIRES.

DANGER NEVER remove wires from product as contact with electricity can cause serious injury or death. Shut off power at the circuit breaker or remove fuse when installing this product.

SAFETY NOTICE Improperly installed electrical wiring can be dangerous and cause electrical fires. This product must be used in accordance with the current rating and wire sizes listed. Consult local building code before doing any electrical work. COPPER TO COPPER ONLY. Do not use on Aluminum. Temperature rating: 105 C (221F) maximum. Flame Rated UL94V-0.

Rated for a limited number of current-interrupting operations.

This disconnect is rated for 600 Volts/6 Amps maximum.

Wire Range Solid: Stranded: Stranded Tin Bonded:

Line Side (Orange)
12-18 AWG 12-14 AWG (19 Strand or less) 12-14 AWG (19 Strand or less)
16 AWG (26 Strand or less) 18 AWG (16 Strand or less)

Ballast Side (Gray)
18 AWG —
18 AWG (16 Strand or less)

Disconnect de-mate / mate installation 1. To de-mate, grasp disconnect at each end and pull apart to separate the disconnect halves.
Do NOT pull on wires. 2. To mate the disconnect, grasp each disconnect half, align halves, and push together. 3. Completed connection should appear as shown.

Line Side (2 ports)
(Orange Cap)

Ballast Side (4 ports)
(Gray Cap)

Neutral

Hot

BALLAST

IDEAL INDUSTRIES, INC. Becker Place Sycamore, IL 60178, U.S.A. 800-435-0705 Customer Assistance www.idealindustries.com ND 7210-2