legrand 1517 Over Floor Raceway Installation Guide
- September 3, 2024
- Legrand
Table of Contents
legrand 1517 Over Floor Raceway
Product Specifications
Brand: Wiremold / Open Space
- Product Name: 1500 Series Overfloor Raceway
- Code Reference: cULus Listed Underfloor Raceways: File E4376 Guide RJBT. Fittings: File E41751 Guide RJPR. Meets Article 386 of NEC. Meets Section 12-1600 of CEC.
- Color Options: Available in galvanized steel unless otherwise indicated in the part number description.
Product Usage Instructions
System Components
The 1500 Series Raceway system includes various components such as:
- G. 1517 Internal Elbow
- H. 1518 External Elbow
- I. 2642D Junction Box
- J. 2686FO Transition Feed Fitting
- K. 2600 Series Overfloor Steel Raceway
- L. 2400 Series Raceway
- M. V500 500/700 Series Raceway
- N. 1500 Raceway Base & Cover
- O. 1/2 Conduit or Armored Cable
Wire Fill Capacities
The raceway supports different cable/wire sizes for both communications and
power:
- Communications:
- Unshielded Twisted Pair
- Coaxial Fiber
- Refer to the provided table for wire fill capacities based on cable/wire size.
- Power:
- THHN/THWN Wire Size (14 AWG, 12 AWG, 10 AWG)
- Refer to the provided table for wire fill capacities based on wire size.
Installation Instructions
Follow these steps to install the 1500 Series Overfloor Raceway:
- Identify the layout and components needed for your installation.
- Securely attach the raceway base to the floor using appropriate fasteners.
- Assemble the raceway components including elbows, junction boxes, and transition fittings as required.
- Route the cables/wires through the raceway ensuring proper organization and fill capacities are maintained.
- Secure the raceway cover in place.
Frequently Asked Questions (FAQ)
-
Q: What are the available color options for the 1500 Series Raceway components?
A: The components are available in galvanized steel unless specified otherwise in the part number description. -
Q: How do I determine the wire fill capacities for communications and power cables?
A: Refer to the provided tables in the user manual that list the wire fill capacities based on cable/wire size for communications and power applications. -
Q: Are there specific tools required for cover removal or installation?
A: Yes, a cover removal tool is available for the 1500 and 2600 Series Overfloor Raceways to assist in cover removal.
WIREMOLD / OPEN SPACE
1500 SERIES™ OVERFLOOR RACEWAY
Wiremold® 1500 Series™ Steel Raceway provides permanent protection for overfloor cabling in high traffic areas.
CODE REFERENCE
cULus Listed Underfloor Raceways: File E4376 Guide RJBT.
Fittings : File E41751 Guide RJPR. Meets Article 386 of NEC.
Meets Section 12-1600 of CEC.
1500 Series Raceway System Layout
OVER FLOOR RACEWAY
NOTE : Illustration is for showing product applications only.
KEY
- A. V1517B Adapter Fitting
- B. 1528 Utility Box
- C. 1585 Combination Connector
- D. 1546A Single Receptacle Box
- E. 1546B Duplex Receptacle Box
- F. 1511 90° Flat Elbow
- G. 1517 Internal Elbow
- H. 1518 External Elbow
- I. 2642D Junction Box
- J. 2686FO Transition Feed Fitting
- K. 2600 Series Overfloor Steel Raceway
- L. 2400 Series Raceway
- M. V500 500/700 Series Raceway
- N. 1500 Raceway Base & Cover
- O. 1/2″ Conduit or Armored Cable
COLOR OPTIONS
1500 Series™ Raceway components are available in galvanized steel unless otherwise indicated in the part number description.
WIREMOLD / OPEN SPACE
1500 SERIES™ OVERFLOOR RACEWAY
Ordering Information
1500 Series Raceway Wire Fill Capacities for Communications
| CABLE/WIRE SIZE| O.D. (Approx. Inches| dia.) (mm)| 40% FILL
---|---|---|---|---
UNSHIELDED| 4-pair, 24 AWG, Cat 3| 0.190| (4.8)| 3
TWISTED PAIR| 4-pair, 24 AWG, Cat 5e| 0.210| (5.3)| 2
| 4-pair, 24 AWG, Cat 6| 0.250| (6.3)| 1
| 4-pair, 24 AWG, Cat 6a*| 0.354| (9.0)| 0
| 25-pair, 24 AWG| 0.410| (10.4)| 0
COAXIAL| RG6/U| 0.270| (6.9)| 1
FIBER| ZipCord| 0.118 x 0.236| (3 x 6)| 3
| Round 4 Strand Fiber| 0.187| (4.8)| 3
| Round 6 Strand Fiber| 0.256| (6.5)| 1
1500 Series Raceway Wire Fill Capacities for Power
WIRE SIZE THHN/THWN| O.D. (Approx. Inches| dia.)
(mm)
| NO. OF CONDUCTORS 40% FILL
---|---|---|---
14 AWG| 0.111| (2.8)| 9
12 AWG| 0.130| (3.3)| 6
10 AWG| 0.164| (4.2)| 4
NOTE: For additional information, refer to the Technical Section. * Category 6 augmented (6a) cable for 10 gigabit ethernet – max allowed cable diameter per addenda No. 11 ANSI TIA/EIA 568-B.2.
-
1500-10 Raceway Base & Cover
.040” (1.0mm) galvanized steel. Packed ten 10’ (3m) lengths per carton. Base has 9/32” (7.1mm) diameter mounting holes on centers of approximately 8”
(203mm). -
656 Cover Removal Tool
For removing cover of 1500 and 2600 Series Overfloor Raceways. -
1500WC Wire Clip
For holding conductors in place. Not UL Listed. -
1502 Fiber Bushing
Protects wires from abrasion. Slips into open end of 1500 Series Raceway where it enters a fitting. -
1504 Strap
Two-hole strap. Use to fasten 1500 Series Raceway to surfaces at any point desired. -
1511 90° Flat Elbow
For right angle turns on the same surface. -
1517 Internal Elbow
For internal 90° corners. -
V1517B Adapter Fitting
To feed to or from 500 or 700 Series Raceway on wall to 1500 Series Raceway on floor. Ivory finish. -
1518 External Elbow
For external 90° corners.
WIREMOLD / PERIMETER SYSTEMS 1500 SERIES™ OVERFLOOR RACEWAY
Wiremold® 1500 Series™ Steel Raceway provides permanent protection for overfloor cabling in high traffic areas.
CODE REFERENCE
cULus Listed Underfloor Raceways: File E4376 Guide RJBT.
Fittings: File E41751 Guide RJPR. Meets Article 386 of NEC.
Meets Section 12-1600 of CEC.
1500 Series Raceway System Layout
NOTE : Illustration is for showing product applications only.
KEY
- A. V1517B Adapter Fitting
- B. 1528 Utility Box
- C. 1585 Combination Connector
- D. 1546A Single Receptacle Box
- E. 1546B Duplex Receptacle Box
- F. 1511 90° Flat Elbow
- G. 1517 Internal Elbow
- H. 1518 External Elbow
- I. 2642D Junction Box
- J. 2686FO Transition Feed Fitting
- K. 2600 Series Overfloor Steel Raceway
- L. 2400 Series Raceway
- M. V500 500/700 Series Raceway
- N. 1500 Raceway Base & Cover
- O. 1/2″ Conduit or Armored Cable
COLOR OPTIONS
1500 Series™ Raceway components are available in galvanized steel unless otherwise indicated in the part number description.
WIREMOLD / PERIMETER SYSTEMS 1500 SERIES™ OVERFLOOR RACEWAY
Ordering Information
1500 Series Raceway Wire Fill Capacities for Communications
| CABLE/WIRE SIZE| O.D. (Approx Inches| dia.) (mm)| 40% FILL
---|---|---|---|---
UNSHIELDED| 4-pair, 24 AWG, Cat 3| 0.190| (4.8)| 3
TWISTED PAIR| 4-pair, 24 AWG, Cat 5e| 0.210| (5.3)| 2
| 4-pair, 24 AWG, Cat 6| 0.250| (6.3)| 1
| 4-pair, 24 AWG, Cat 6a*| 0.354| (9.0)| 0
| 25-pair, 24 AWG| 0.410| (10.4)| 0
COAXIAL| RG6/U| 0.270| (6.9)| 1
FIBER| ZipCord| 0.118 x 0.236| (3 x 6)| 3
| Round 4 Strand Fiber| 0.187| (4.8)| 3
| Round 6 Strand Fiber| 0.256| (6.5)| 1
1500 Series Raceway Wire Fill Capacities for Power
WIRE SIZE THHN/THWN| O.D. (Approx. Inches| dia.)
(mm)
| NO. OF CONDUCTORS 40% FILL
---|---|---|---
14 AWG| 0.111| (2.8)| 9
12 AWG| 0.130| (3.3)| 6
10 AWG| 0.164| (4.2)| 4
NOTE: For additional information, refer to the Technical Section.
- Category 6 augmented (6a) cable for 10 gigabit ethernet – max allowed cable diameter per addenda No. 11 ANSI TIA/EIA 568-B.2.
OVERFLOOR RACEWAY INDEX
-
1500-10 Raceway Base & Cover
.040” (1.0mm) galvanized steel. Packed ten 10’ (3m) lengths per carton. Base has 9/32” (7.1mm) diameter mounting holes on centers of approximately 8”
(203mm). -
656 Cover Removal Tool
For removing cover of 1500 and 2600 Series Overfloor Raceways. -
1500WC Wire Clip
For holding conductors in place. Not UL Listed. -
1502 Fiber Bushing
Protects wires from abrasion. Slips into open end of 1500 Series Raceway where it enters a fitting. -
1504 Strap
Two-hole strap. Use to fasten 1500 Series Raceway to surfaces at any point desired. -
1511 90° Flat Elbow
For right angle turns on the same surface. -
1517 Internal Elbow
For internal 90° corners. -
V1517B Adapter Fitting
To feed to or from 500 or 700 Series Raceway on wall to 1500 Series Raceway on floor. Ivory finish. -
1518 External Elbow
For external 90° corners.
Read User Manual Online (PDF format)