AirSense 9-30783 Modu Laser Owner’s Manual

August 30, 2024
AirSense

AirSense 9-30783 Modu Laser

Product Usage Instructions

Installation

  1. Ensure the operating voltage is within the specified range (18 to 30 VDC).
  2. Mount the detector module in a suitable location where it can effectively detect smoke particles.
  3. Connect the detector module to the sampling pipe according to the specified inlet and exhaust sizes and locations.

Maintenance

  1. Perform routine filter replacement on a module-by-module basis to reduce downtime and maintain protection.
  2. Check for any dust or dirt accumulation on the detector module and clean as necessary to ensure optimal performance.

Troubleshooting

  • If the detector module is not functioning properly, refer to the user manual for troubleshooting steps or contact customer support for assistance.

FAQ

  • Q: How many sampling holes can a detector module accommodate?
  • A: A detector module can accommodate up to 20 Class A, 40 Class B, or 50 Class C sampling holes.
  • Q: What is the sensitivity range of the ModuLaser detector module?
  • A : The sensitivity range is from 0.002 %obs/m to 25 %obs/m (0.0006 %obs/ft to 7.62 %obs/ft).

General

  • ModuLaser is a scalable aspirating smoke detection solution that makes installation easier, and maintenance quicker and takes applications further than traditional air sampling detectors. Two basic module types comprise
    the ModuLaser solution: a display module, and a detector module. Each detector module can accommodate up to 250 meters of combined sampling pipe.

  • Display modules and detector modules communicate by RS-485 interconnections.

  • Display modules are available in three configurations: Standard with TFT color display, status LEDs and navigation buttons, Minimum with only status LEDs, and Command which is similar to the Standard but with the added functionality to control various modules over SenseNET.

  • The Minimum and Standard Display Modules can each support up to 8 detector modules, while the Command Display Module can support up to 127 modules across the SenseNET network.

Detector module

  • The Detector Module is a fully self-contained unit, that aspirates the sampled air from the protected area, analyzes the air, and based on ClassiFire determines if a pre-alarm or alarm should be raise if smoke particles would be present in the sampled air. If an alarm condition or fault condition occurs, then the unit will activate the corresponding local relay output, subjected to the programming of the relays. Simultaneously the alarm or fault condition would also be reported to the Display Module to which the Detector Module is connected.
  • Due to the modular nature of the ModuLaser, maintenance (for example routine filter replacement) can be done on a module-per-module basis, rather than a complete system. This in turn reduces the risk of the area that is unprotected during the
  • maintenance period, as only one sampling pipe (protected zone) would be affected at a time.

Perfect solution

Thanks to advanced features that make it virtually impervious to dust and dirt, ModuLaser is ideal for use in hostile environments that would disable other kinds of smoke detectors. Forward scattering optical detection adds early warning capability without the risk of nuisance alarms normally associated with high-sensitivity smoke detection, while exclusive environmental compensation technology adds a high degree of reliability to an already solid detection solution.

Details

  • Modular Design: Separate centrally controllable detector modules allow efficient piping and discrete zones with no overlap.
  • Zoned aspirating smoke detection: Individual detector modules provide detection for individual areas or zones, specific zone alarm information can be transmitted to the main fire alarm panel via a common APIC address card in the display module or through
  • dedicated alarm relays within each detector module.
  • Simplified installation: Ingenious docking station design allows detectors to be easily connected together as a group. Sensitive electronics are easily removed to ensure they will not be damaged during first fix installation. Aspirating pipework and cable entries
  • can easily be made into either the top or the bottom of the unit.
  • Intuitive user interface : Bright easy-to-see color TFT display and universal navigation and control buttons take the guesswork out of programming and diagnostics.
  • Easy pipe connection: The quick-fit pipe adaptor system locks down securely, yet leaves plenty of room for easy pipe connection and removal.
  • Quick location of smoke: Each detector module is self-contained, which means no delays in determining in which zone (sampling pipe) smoke is present.

Technical specifications

General

  • Status indication LED’s
  • User interface TFT and navigation buttons on Normal and
  • Command Display Modules
  • Alarm levels 4 (Aux, Pre-alarm, Alarm and Alarm 2)
  • Event log 20,000 events per module
  • RS485 support Yes (SenseNET and SenseNET+)
  • Connectivity USB (x2), IP, and APIC on Display Module

Electrical

  • Operating voltage 18 to 30 VDC
  • Current consumption Display Module (at 24 VDC):
    • 204 mA – Minimum Display Module
    • 232 mA – Standard Display Module
    • 232 mA – Command Display Module
    • Detector Module (at 24 VDC):
    • 260 mA – fan speed 1
    • 380 mA – fan speed 6 (default speed)
    • 940 mA – fan speed 16

Detection

  • Detection principle Laser light scattering mass detection and particle evaluation
  • Sensitivity 0.002 %obs/m to 25 %obs/m (0.0006 %obs/ft to 7.62 %obs/ft)
  • Particle sensitivity range 0.003 to 10 microns

Sampling pipe

  • Length Up to 250 m (820 ft.) combined per detector module
  • Quantity sampling holes Up to 20 – Class A per detector module
  • Up to 40 – Class B per detector module
  • Up to 50 – Class C per detector module
  • Inlet size 27 or 25 mm (1.06 or 0.98 in) outer diameter
  • Inlet location Top or bottom
  • Exhaust size 27 or 25 mm (1.06 or 0.98 in) outer diameter
  • Exhaust location Top or bottom
  • Inlet quantity 1 per detector module

Input

  • Input quantity 2 per module
  • Input type and rating Supervised
  • Termination 15 KΩ 5% 1/4 W
  • Programmable Yes

Output

  • Output quantity 3 per module
  • Output type and rating Voltage free (contact rating 2 A at 30 VDC /
  • NO/NC/C)
  • Programmable Yes

Physical

  • Physical dimensions W x D x H 110.5 x 133.5 x 300 mm (4.35 x 5.25 x 11.8 in)
  • Net weight Display Module: 1.18 Kg (2.6 lb.)
  • Detector Module: 1.57 Kg (3.46 lb.)
  • Color Cream
  • Mounting type Surface mount
  • Cable entries 2 at the bottom, 2 at the rear, 2 at the top on
  • Detector Module, and 3 at the top on the Display Module
  • Cable entry size 20 mm (0.5 in) – top and bottom
  • Detector module Orientation Vertical (0 deg or 180 deg)

Environmental

  • Operating temperature Equipment:-20 to +60 °C (-4 to +140 °F) Sampled air: -20 to +60 °C (-4 to +140 °F)
  • Relative humidity 0 to 95% noncondensing
  • Environment Indoor
  • IP rating IP40

Regulatory

  • Compliance REACH, RoHS
  • Certification BOSEC, CPR, CSIRO, EN54-20, LPCB, VdS

Chart recorder

  • The sampling period Adjustable between 1s and 60s
  • Capacity 1 months @ 1s / Up to 5 years @ 60 s
  • Values recorded Detector value, 4 alarm level values, flow value and temperature (all simultaneously)

Compatible products

As a company of innovation, Carrier Fire & Security reserves the right to change product specifications without notice. For the latest product specifications, visit firesecurityproducts.com online or contact your sales representative. Last updated on 11 March 2024 – 16:14 Powered by