GREE Electric Heat Kit Line Voltage Remove Instructions

June 3, 2024
Gree

**

GREE Electric Heat Kit Line Voltage Remove logo**

GREE Electric Heat Kit Line Voltage Remove

GREE Electric Heat Kit Line Voltage Remove product Document #: TB-FLX-11102022
Author: Justin Sylsberry
Reference: Installation of FLEXX Electric Heat Kit
Product Group: FLEXX
Models Affected: ALL
Serial Number Range: ALL

Summary

Instances of high voltage electrical shorts have been reported with FLEXX air handlers with electric heat kits installed. This can lead to damage to the unit or personal injury. Most commonly, damaged Molex connectors have been reported.GREE Electric Heat Kit Line Voltage Remove 01 Solution:
When installing an electric heat kit in a FLEXX air handler, line voltage must only be connected to the circuit breakers included with the heat kit. Line voltage must be disconnected permanently from L1 and L2 on the terminal block. If line voltage is connected to the electric heat kit circuit breakers and the terminal block at the same time, a high voltage short will occur.GREE
Electric Heat Kit Line Voltage Remove 02 Disconnect line voltage from L1 and L2 permanently before installing an electric heat kit to prevent a high voltage short.