Danfoss AB024D Solenoid Coil Installation Guide

August 17, 2024
Danfoss

Danfoss AB024D Solenoid Coil

Specifications

  • Product Name: Solenoid Coil Type AB, AM, AC, AK, AL, AP, BB, BA, BC, and BD
  • Model Number: 042R9019
  • Manufacturer: Danfoss
  • Class of Protection: Class I
  • Control Type: Spade
  • Operating Temperature: Ambient temperature, refer to Tambient on the coil
  • Voltage Variation: Refer to print on coil

Product Usage Instructions

  • Installation Guide
    • Follow the steps below to install the solenoid coil:
    • Identify the type of coil required based on the model number.
    • Connect the appropriate spade connectors to A1 and A2 for the IP65/PD3 Cable plug for A – Coils.
    • For B – Coils, connect B1 and B2 with IP65/PD3 and B3 with IP67/PD4 Cable plug.
    • Ensure proper insulation and connection according to the provided specifications.
  • Maintenance
    • To maintain the solenoid coil, follow these guidelines:
    • Check for any signs of wear or damage regularly.
    • Clean the coil and surrounding area from any dust or debris that may affect performance.
    • Ensure all connections are secure and insulated properly.

FAQs

  • Q: What is the voltage tolerance for the solenoid coil?
    • A: For voltage tolerances, refer to the datasheet provided when ordering the coil.
  • Q: Where can I find information for UK customers?
    • A: For UK customers, contact Danfoss Ltd. at 22 Wycombe End, HP9 1NB, GB.

INSTALLATION INSTRUCTION

Solenoid coil

Type AB, AM, AC, AK, AL, AP, BB, BA, BC and BD

Type of control 1
Class of protection Class I
Ambient temperature See Tambient on coil

Voltage variation

Voltage tolerances

| For voltage variation, see the print on the coil For voltage tolerances see the datasheet when ordering the coil
Humidity| Only none-conductive pollution occurs except that occasionally a temporary conductivity caused by

condensation is to be expected.

Ball pressure test| 200 °C (392 °F) in accordance to IEC 60695-10-2

Impulse withstand voltage

| Spade

Plug Plug

| 4.0 kV at altitude <4000 m (13123 ft)

4.0 kV at altitude <2000 m (6561 ft)

3.1 kV 2000 m<altitude<4000 m (6561<altitude<13123 ft)

Overvoltage category| III
Degree of protection IPxx

Pollution degree PDX

| Enclosure rating according to IEC standard 60529 (See illustration for details A-B)

Pollution degree according to EN60664-1 (See illustration for details A-B)

Installation

| Integrated control Incorporated control

Independently mounted control (IP65/IP67)

Suitable cable,

Conductor size for plug

| ø6.6 – ø11 mm (ø0.26 – ø0.43 in)

0.75 – 1.5 mm² (21 – 15 AWG flexible cord)

Suitable cable for cable plug| See the datasheet when ordering the coil
Cable conductor size| 3 x 0.75 mm² (3 x 0.001 in2)
Plugs can be removed/Mounted| 10 times
Surface temperature| Independently mounted controls must be inaccessible in normal use if the surface temperature on the control is> 85°C

  • Only qualified personnel are allowed to install or maintain this product
  • Disconnect the power when dismounting the coil
  • Avoid direct exposure to alkaline conditions, use in neutral conditions is recommended
  • Ensure that the O-ring is in place on the valve
  • If the coil is used as an independently mounted control, the end-user shall use a plastic cable gland with strain relief