iO HVAC CONTROLS Z-2000 Modulating 20 Zone System Installation Guide
- August 16, 2024
- iO HVAC Controls
Table of Contents
Z-2000 Modulating 20 Zone System
“`html
Specifications
-
Product: Z-2000 Modulating 20 Zone System
-
Compatibility: 2 Heat / 2 Cool conventional or 3 Heat / 2 Cool
heat pump systems -
Wiring: All low voltage wiring is 18 gauge thermostat wire
-
Setup: No computer required for setup, configuration, or
diagnosis
Product Usage Instructions
Overview
The Z-2000 system controls the system fan and all stages of
heating and cooling. It is designed for compatibility with specific
heating and cooling systems.
Sequence of Operation
The Z-2000 panel is responsible for controlling the system fan
and managing the different stages of heating and cooling. It
operates based on a specific sequence of actions as outlined in the
user manual.
Design and Installation Guidelines
-
Zone dampers should not exceed 2 w.c. for applications.
-
VAV diffusers should not exceed 0.25 w.c.
-
Install zone dampers away from discharge air grills and
diffusers. -
Use flex duct for the last 5 feet of each branch run.
-
Size bypass dampers for 90% of the total system CFM.
-
Locate the Z-2000 panel in an accessible location within the
conditioned space.
Typical Wiring and Layout Guide
Refer to the provided wiring diagram for proper installation of
the Z-2000 system in conjunction with the HVAC unit, bypass damper
system, and other components.
Z-2000 Panel Layout
The Z-2000 panel features various terminals and indicators for
thermostat connections, system power, scheduling clock, discharge
air sensor, economizer, and HVAC system status LEDs. Follow the
user manual for proper setup and configuration of these
components.
Frequently Asked Questions (FAQ)
Q: What systems are compatible with the Z-2000?
A: The Z-2000 is compatible with 2 Heat / 2 Cool conventional or
3 Heat / 2 Cool heat pump systems.
Q: Is a computer required for setting up the Z-2000?
A: No, a computer is not required for setup, configuration, or
diagnosis of the Z-2000 system.
“`
Installation Guide Version 2001
Z-2000
MODULATING 20 ZONE SYSTEM
Indianapolis, IN 46237
TABLE OF CONTENTS
Overview ……………………………………………………………………………………………………… 3 Sequence of Operation
…………………………………………………………………………………… 3
Panel ………………………………………………………………………………………………….. 3 Zone Thermostat
………………………………………………………………………………….. 3 Design and Installation Guidelines
………………………………………………………………… 3,4 Typical Wiring and Layout Guide
………………………………………………………………………. 4 Z-2000 Panel Layout
……………………………………………………………………………………… 5 System Wiring
…………………………………………………………………………………………… 6-9 Warning!
…………………………………………………………………………………………….. 6 Caution!
……………………………………………………………………………………………… 6 Z-2000 Panel Wiring
…………………………………………………………………………… 6,7
System Power ……………………………………………………………………………… 6 HVAC System
……………………………………………………………………………… 6 Discharge Air Sensor
……………………………………………………………………. 6 Night Stat …………………………………………………………………………………… 7
Economizer …………………………………………………………………………………. 7 Heat/Auto/Cool Terminals
…………………………………………………………….. 7 Zone Damper Actuator Board
…………………………………………………………………… 8 Z-2000-T Zone Thermostat Wiring
…………………………………………………………… 8 Optional wiring for electric duct heater or
baseboard electric ………………. 9 Panel Setup ……………………………………………………………………………………………
10, 11 Switch Congurations ………………………………………………………………………….. 10 High and Low
Limit Settings ………………………………………………………………….. 11 Night Stat Setup and Scheduling
……………………………………………………………….. 11-13 Overview ……………………………………………………………………………………………
11 How It Works ……………………………………………………………………………………… 11 Recommended Setup
…………………………………………………………………………… 11 System Switch Settings
…………………………………………………………………………. 11 Installer Setup Menu
…………………………………………………………………………….. 12 Setting the Clock and Day of Week
………………………………………………………… 12 Daylight Saving Time …………………………………………………………………………..
12 Programming Events ………………………………………………………………………. 12, 13 Typical 7-Day
Schedule ………………………………………………………………………… 13 Zone Thermostat Setup
……………………………………………………………………………. 14-18 Switch Functions
………………………………………………………………………………… 14 Key Functions
……………………………………………………………………………………. 14 Entering Setup Menu
………………………………………………………………………….. 15 Setting the Minimum Damper Position
……………………………………………………. 15 Setting the Maximum Damper Position
……………………………………………………. 15 Setting the Unit Number ……………………………………………………………………….
15 Setting a Zone Number ……………………………………………………………………….. 16 Setting the Heating
Limit ……………………………………………………………………… 16 Setting the Cooling Limit
……………………………………………………………………… 16 Setting the Actuator Speed
……………………………………………………………………. 16 Setting the Modbus Address
………………………………………………………………….. 17 Temperature Calibration Offset
……………………………………………………………… 17 Saving Settings and Exiting the Setup Menu
…………………………………………….. 17
1
TABLE OF CONTENTS
Advanced Functions ………………………………………………………………………………………. 17, 18 Damper Position
Override ……………………………………………………………………….. 17 Override to Open
………………………………………………………………………………….. 18 Override to Close
………………………………………………………………………………….. 18 Cancelling the Damper Override
………………………………………………………………. 18
Checking Thermostat Status Points ……………………………………………………………………… 18 Unit Number
…………………………………………………………………………………………. 18 Zone Number
……………………………………………………………………………………….. 18 Duct Temperature
…………………………………………………………………………………… 18 Damper Position
…………………………………………………………………………………….. 18
System Status LED Denitions and Functions ………………………………………………………………….. 19
Z-2000 Panel …………………………………………………………………………………………………… 19 Actuator Board
…………………………………………………………………………………………………. 19
Z-2000 Panel Time Delays …………………………………………………………………………………………… 19 Staging and
Limit Control ……………………………………………………………………………………………. 20
2
OVERVIEW
The Z-2000 (Version 2001) is a commercial, modulating forced air zone control
system that allows a single HVAC unit to have up to 20 individual zones. Each
zone is controlled by a proprietary space thermostat that wires to a factory
mounted actuator board located on a master damper or diffuser serving the
zone. The actuator board also wires back to the Z-2000 logic panel which
receives calls from each zone thermostat for either heating or cooling and
controls the HVAC equipment based on a selected control sequence conguration.
The Z-2000 is compatible with 2 Heat / 2 Cool conventional or 3 Heat / 2 Cool
heat pump systems. All low voltage wiring is 18 gauge thermostat wire and no
computer is required to setup, congure or diagnose the system.
SEQUENCE OF OPERATION
Z-2000 Panel: The Z-2000 controls the system fan and all stages of heating and
cooling. During the
occupied mode, the fan runs continuously. As calls for heating or cooling are
received from the individual zone thermostats, the zone control panel
establishes the equipment mode of operation based on a selectable Majority
Wins or Cooling Priority control algorithm. In addition, the panel is equipped
with Minimum Call selector switches designed to prevent the equipment from
coming on until a minimum number of calling zones is reached. This feature
helps prevent short equipment run times and minimizes high or low limit trip-
out when only a few zones are calling. Refer to the Panel Setup and Scheduling
section for conguration guidelines. Z-2000-T Zone Thermostat:
The Z-2000-T zone thermostat is an integral part of the Z-2000 zoning system.
The thermostat not only signals the panel when the zone requires heating or
cooling, but also controls the damper or diffuser serving the zone. The
Z-2000-T is a single setpoint thermostat and sends a signal to the Z-2000
panel for heating or cooling when the temperature in the zone deviates 1.5° F
above or below the setpoint. The thermostat can be congured for modulating or
two-position damper control and interfaces with a duct sensor mounted in the
master damper or diffuser to determine if the discharge air is usable for the
call. If the discharge air temperature at the damper is warmer than 72° F, the
thermostat will open the damper on a call for heating. If the discharge air
temperature at the damper is below 72° F, the thermostat will open the damper
on call for cooling. Refer to the Zone Thermostat Setup section for
conguration guidelines.
DESIGN AND INSTALLATION GUIDELINES
[ ] Extra consideration should be given when applying any zone control system
to a building that requires large amounts of cooling in the core zones during
cold weather. Consider adding auxiliary heat to external zones or using one
system for the core zones and one system for the external zones. [ ] It is
recommended that the system installation be limited to 25 tons of cooling
capacity. Rooftop units with economizers and relief dampers are strongly
recommended for building with core cooling loads. [ ] Using zoning with
oversized HVAC equipment is not recommended. This can cause short equipment
run times and humidity problems. [ ] Multi-stage equipment is recommended with
zone control systems. [ ] The pressure drop through zone dampers is negligible
and not a factor when sizing branch runs.
3
DESIGN AND INSTALLATION GUIDELINES
[ ] Zone dampers are rated for applications not exceeding 2″ w.c. VAV
diffusers should not exceed 0.25″ w.c.
[ ] Zone dampers should be installed as far back from discharge air grills and
diffusers. Flex duct should be used for the last 5 feet of each branch run. [
] Bypass dampers should be sized for 90% of the total system CFM. [ ] The
Z-2000 panel should be located in an accessible location in the conditioned
space and never mounted inside the rooftop unit. [ ] The Z-2000 system
requires a separate 24VAC, 75VA transformer that provides power to the
TYPICAL WIRING AND LAYOUT GUIDE
HVAC UNIT
8
HEAT/COOL OR
HEAT PUMP
3
Z-2000-NS NIGHT STAT
120/208/240/480 VAC
BYPASS DAMPER SYSTEM DUCTED RETURN
RETURN
SUPPLY
24VAC
STATIC PRESSURE CONTROL
BYPASS ACTUATOR
STATIC PRESSURE
PROBE
PRESSURE TUBING
4
BYPASS DAMPER SYSTEM OPEN RETURN
RETURN
SUPPLY
STATIC PRESSURE
PROBE
CEILING
24VAC
PRESSURE TUBING
BYPASS ACTUATOR
STATIC PRESSURE CONTROL
Z-2000 PANEL LAYOUT
3
26
4 AMP
4 AMP
4
25
OFF ON
SETUP
1 2 3 4 5 6
MAJORITY COOLING PRIORITY
HC
HP
SYSTEM
O
B REV VALVE
OFF 3 ZONES MIN
OFF 2 ZONES CALLS
OFF
ON
E HEAT
5
44
160
42
46
23
40
48
LOW LIMIT
150
170
24
140
175
HIGH LIMIT
1
22
21 20 19 18 17 6
16 7
8
15
9
10
W3/AUX/EH
2
2 AMP
2 AMP
.. REMOVE JUMPER FOR RH – RC
2 AMP
14 1. Zone 1-12 Thermostat Terminals with Heat/Cool LED Indication 2. Cool/Auto/Heat Terminals 3. 4 AMP System Power Fuse 4. 24VAC System Power Terminals (Input) 5. Zone 13-20 Thermostat Terminals with Heat/Cool LED Indication 6. Scheduling Clock Terminals 7. 24VAC Clock Power Terminals (Output) 8. Discharge Air Sensor Terminals 9. Economizer Terminals
13
12
11
10. HVAC System Terminals 11. 2 AMP RC Fuse 12. RH/RC Jumper 13. 2 AMP RH Fuse 14. 2 AMP Spare Fuse 15. HVAC System Status LEDs 16. Occupied LED 17. System Status LED
5
18. Heat Status LED 19. Cool Status LED 20. Discharge Air Sensor LED 21. Speed UP Mode LED 22. Speed UP Mode Button 23. Low Limit Adjustment 24. High Limit Adjustment 25. System Conguration Switches 26. 4 AMP Spare Power Fuse
SYSTEM WIRING
WARNING! 1. Turn power off to HVAC equipment and control panel during
installation to prevent serious injury from electrical shock and/or damage to
the system. 2. Use extreme care when making duct openings and handling sheet
metal to avoid injury. 3. Install all components in a manner that provides
easy access for test, check and startup. CAUTION! 1. Installation of this
system must be in compliance with all applicable codes. 2. HVAC system must be
properly sized and balanced to assure optimum system performance. 3. An
electronic bypass damper or VFD (Variable Frequency Drive) must be installed
to maintain proper system static pressure. 4. All low voltage wire must be 18
gauge. 5. All wiring should be color coded and tagged for proper identication.
Z-2000 PANEL WIRING System Power 1. Wire a 24VAC, 75VA transformer to the
24VAC R’ and
C’ terminals on the Z-2000 panel.
24VAC
120/208/240/480 VAC
HVAC System
TR-75 TRANSFORMER
2. Wire the HVAC equipment to the HVAC SYSTEM terminals on the Z-2000 panel.
CONVENTIONAL HEAT/COOL SYSTEM
HEAT PUMP SYSTEM
C
C
DO NOT WIRE EQUIPMENT COMMON TO PANEL
Discharge Air Sensor 3. Mount the Z-2000-DAS Discharge Air Sensor in the main supply plenum as far down stream from the evaporator coil but prior to any duct transitions and dampers. Wire the discharge air sensor to the DAS terminals on the Z-2000 panel.
Z-2000-DAS
6
SYSTEM WIRING
Night Stat 4. Remove the factory jumper on the Z-2000 panel from the NS CLOCK
CONTACT terminals. Wire the Z-2000-NS Night Stat as shown in the wiring
diagram. The Z-2000-NS Night Stat should be located in an area that represents
the general load characteristics of the building. If the thermostat is located
in an equipment room, a remote sensor may be required. In applications where
24 hour occupancy exists, a night stat may not be necessary.
NOT USED
Optional Z-2000-S1
Remote Sensor Terminals
Z-2000-NS NIGHT STAT
BATTERY COMPARTMENT
MOUNTING HOLES
WIRE ACCESS
HOLE
W2 MOUNTING
S2 SC S1 AUX AUX O/B
HOLE
MOUNTING HOLES
Y1 Y2 W1 G R C
Economizer If the HVAC unit has an economizer, the auxiliary contacts on the
Z-2000-NS Night Stat can be used with the ECONO contacts on the Z-2000 panel
so that the economizer is only energized during the occupied period. Wire the
Night Stat as illustrated above and the ECONO terminals as illustrated below.
Refer to the Z-2000-NS Installation Manual on assigning the auxiliary
contacts.
Z-2000-NS NIGHT STAT
BATTERY COMPARTMENT
MOUNTING HOLES
WIRE ACCESS
HOLE
W2 MOUNTING
S2 SC S1 AUX AUX O/B
HOLE
MOUNTING HOLES
Y1 Y2 W1 G R C
TO ECONOMIZER
Heat/Auto/Cool Terminals The Z-2000 panel has a set of terminals that can be
used to place the panel in heating only, cooling only or auto changeover mode.
A simple jumper wire can be placed between the COM and H for heat only or, COM
and C for cool only mode. If a jumper is not used, the panel is in Auto
Changeover. The terminals can also be used with a 3-position selector switch
for remote applications.
AUTO CHANGEOVER
HEAT ONLY
COOL ONLY
JUMPER
JUMPER
7
SYSTEM WIRING
Zone Damper Actuator Board Each master zone damper has an actuator board mounted to the side of the damper motor or diffuser. Run 4-wire cable from the Z-2000 panel to each zone actuator board as illustrated.
ACTUATOR BOARD
DAMPER OR DIFFUSER MOTOR
2001AB Rev2 PO
PC
THERMOSTAT
W
HEAT
R
FACTORY WIRING
C
PO
0
DAMPER
DS
PC
FP45-MOTOR
DS
C
1
Y
DS
45in-lb/5Nm 24VAC/DC
1 Comm 2 Close
C
DS
90S 2.5 VA 1.5W
3 Open
R
R
COOL
Y
W 1 2 3
Z-2000 PANEL
Z-2000-T Zone Thermostat Wiring Each Z-2000-T zone thermostat wires to its master zone damper actuator board. Run 8-wire cable from the thermostat subbase terminals to the actuator board as illustrated.
Z-2000-T
AUTO CHANGEOVER SPACE THERMOSTAT
PO DAMPER OPEN (24VAC) PO
PC DAMPER CLOSED (24VAC) PC
W CALL FOR HEAT (24VAC) W
R 24VAC POWER (HOT) R
C 24VAC POWER (COMMON) C
DS DUCT SENSOR
DS
DS DUCT SENSOR
DS
Y CALL FOR COOL (24VAC) Y
TO Z-2000 PANEL
C
FACTORY R JUMPER R
Y
W
THERMOSTAT
ACTUATOR BOARD
2001AB Rev2
DAMPER OR DIFFUSER MOTOR
HEAT
DAMPER
FACTORY WIRING
PO PC C DS DS
0
FP45-MOTOR
1
45in-lb/5Nm 24VAC/DC
90S 2.5 VA 1.5W
1 Comm 2 Close 3 Open
COOL
1 2 3
WIRE TO
DUCT SENSOR (10K OHMS @77°)
OPTIONAL AUXILIARY DAMPERS
8
(UP TO 12 MAY BE WIRED IN PARALLEL)
SYSTEM WIRING
ZONE THERMOSTAT WIRING WITH ELECTRIC DUCT HEATER OR BASEBOARD ELECTRIC
Z-2000-T with Electric Duct Heater There are two wiring options when using an
electric duct heater in a zone. Option1. A DPDT relay can be used to bring on
the electric heat and drive the damper open without relocating the duct
sensor. A 15K Ohm resistor must be wired to one side of the relay contact so
that when the relay is energized, the resistor will be in parallel with the
duct sensor. This will change the ohms value, translating to a higher duct
temperature which will drive the damper open. Option 2. The duct sensor can be
relocated after the electric duct heater. A SPDT relay with a 24 volt coil can
be applied and the coil wired to terminals C and W on the actuator board. The
relay contacts are wired in series with the duct heater terminals.
Z-2000-T
AUTO CHANGEOVER SPACE THERMOSTAT
PO DAMPER OPEN (24VAC) PO
PC DAMPER CLOSED (24VAC) PC
W CALL FOR HEAT (24VAC) W
R 24VAC POWER (HOT) R
C 24VAC POWER (COMMON) C
DS
DUCT SENSOR
DS
DS
DUCT SENSOR
DS
Y CALL FOR COOL (24VAC) Y
C R FACTORY JUMPER R Y W
THERMOSTAT
ACTUATOR BOARD
2001AB Rev2
HEAT
PO PC C DS DS
COOL
DAMPER
DAMPER OR DIFFUSER MOTOR
0
FP45-MOTOR
1
45in-lb/5Nm 24VAC/DC
90S 2.5 VA 1.5W
1 Comm 2 Close 3 Open
1 2 3
C R
WIRE TO THERMOSTAT W TERMINAL WIRE TO THERMOSTAT C TERMINAL
OPTION 1
24 V COIL
RY2 RELAY
REMOVE FACTORY JUMPER WIRE TO W TERMINAL WIRE TO R TERMINAL
OPTION 2
24 V COIL
RY1 RELAY
NC C NO NC C NO
DUCT SENSOR (10K OHMS @77°)
WIRE TO DS TERMINAL WIRE TO DS TERMINAL 15K Ohm Resistor
WIRE TO DUCT HEATER COIL
WIRE TO DUCT HEATER COIL
NC C NO
Z-2000-T with Electric Baseboard Heat Option 2 above would apply for electric
baseboard heat with the exception that the duct sensor would not have to be
relocated. The contact rating of the relay must be determined for the specic
electric baseboard application.
9
PANEL SETUP
The Z-2000 panel has a row of slide switches that are used to congure the panel for the specic equipment application along with other options. Switch denitions are as follows:
OFF ON
SETUP
1 2 3 4 5 6
MAJORITY COOLING PRIORITY
HC
HP
SYSTEM
O
B REV VALVE
OFF 3 ZONES MIN
Switch 1 – Priority:
OFF 2 ZONES CALLS
OFF
ON
E HEAT
OFF = Majority
When the Priority switch is placed in the OFF position, the panel treat calls for heating and
cooling based on a Majority Wins control algorithm. This means that the panel will energize
the equipment in the mode that represents the greatest number of calls. In the event of a tie,
cooling will receive priority.
ON = Cooling
When the Priority switch is placed in the ON position, the panel gives priority to any cooling
call regardless how many heating calls are taking place.
Switch 2 – System:
OFF = HC
When the System switch is placed in the OFF position, the panel is congured for
conventional heating/cooling systems with up to 2 stages of heat and 2 stages of cooling.
ON = HP
When the Priority switch is placed in the ON position, the panel is congured for heat pump
systems with up to 3 stage heat / 2 stage cool.
Switch 3 – Rev Valve: (Applies to heat pump operation only)
OFF = O
In heat pump conguration, when the Rev Valve switch is OFF, the reversing valve will
energize on a call for cooling.
ON = B
In heat pump conguration, when the Rev Valve switch is ON, the reversing valve will
energize on a call for heating.
Switch 4 and 5 – Min Call:
4 OFF and 5 OFF = No Minimum Call Requirement
When both Min Call switches are OFF, any single zone can initiate an equipment call.
4 ON and 5 OFF = 2 Zones
When switch 4 is ON and switch 5 is OFF, at least two zones must be calling in the same
mode before the panel will energize the equipment.
4 OFF and 5 ON = 3 Zones
When switch 4 is OFF and switch 5 is ON, at least three zones must be calling in the same
mode before the panel will energize the equipment.
4 ON and 4 ON = 5 Zones
When both switch 4 and 5 are ON, at least ve zones must be calling in the same mode
before the panel will energize the equipment.
Switch 6 – E Heat (Applies to heat pump operation only)
OFF = No Emergency Heat
When switch 6 is OFF, the panel uses the compressor(s) and auxiliary heat for normal
heating
calls.
ON = Emergency Heat
10
PANEL SETUP
High and Low Limit Settings The panel has adjustable High and Low Limit potentiometers. When the low or high limit discharge air setpoint is reached, the panel will lock out the equipment while maintaining fan operation and initiate a time delay before the equipment is allowed to come back on. In conventional heating and cooling conguration, the time delay only applies to the cooling cycle. In heat pump conguration, the time delay applies to both heating and cooling.
44
160
42
46
150
170
40
48
LOW LIMIT
140
175
HIGH LIMIT
NIGHT STAT SETUP AND SCHEDULING
OVERVIEW: The Z-2000-NS programmable touchscreen thermostat can be used for
occupied and unoccupied scheduling of the Z-2000 panel. When wired and
configured properly, the thermostat takes the place of a separate 7-day clock,
night stat and override timer. The Z-2000-NS Programmable Fan option is used
to trigger the G’ fan relay to open or close the Clock Contact
NS’ terminals
on the Z-2000 panel that places the system in the occupied or unoccupied mode
of operation. The thermostat can also be used with a Z-2000-S1 Indoor Remote
Sensor. 24 volt power to the thermostat is supplied by the Z-2000 panel
through dedicated Clock Power terminals R’ and
C’. The thermostat also has
battery backup to maintain the real-time clock in the event of a power
failure. The thermostat can be configured to provide 7-day scheduling with 2
or 4 events per day. For commercial schedules, 2 events per day is typical.
HOW IT WORKS: The Z-2000-NS does not control the HVAC equipment and only uses
the `G’ fan relay to set the Z-2000 panel in either the occupied or unoccupied
mode. This is accomplished by using the Programmable Fan option so that the
fan relay is energized during occupied mode (Always On) and de-energized
during unoccupied mode (Automatic). When in Automatic mode, the fan relay will
only energize when the temperature falls below or rises above the programmed
unoccupied heating and cooling setpoints. RECOMMENDED SETUP: Refer to the
Installation Instructions to configure the thermostat. Leave all other setup
menu items not shown below in factory default. SYSTEM SWITCH SETTINGS: The
Z-2000-NS contains a set of four system switches located on the thermostat
printed circuit board. Make sure the system switches are set as follows:
Sw 1 = OFF Sw 2 = ON Sw 3 = OFF Sw 4 = OFF
11
NIGHT STAT SETUP AND SCHEDULING
INSTALLER SETUP MENU CHANGES: After the thermostat is powered up, touch and hold both the Clock and Mode section for 5 second to enter the Installer Menu. Touch Next to advance forward through the menu or touch Back to backup.
REQUIRED MENU CHANGES:
02= 2 04 = 1
(Program Schedules) (Programmable Fan)
DAYLIGHT SAVING TIME: The Z-2000-NS default setting compensates for Daylight Saving Time. In areas of the country where DST is not observed, the feature can be disabled by entering Installer Menu 30. Touch the UP or DOWN arrows to change the selection to 0.
After the changes have been made, touch and hold Next until the thermostat exits the Installer menu. All changes will be stored in non-volitile memory.
SETTING THE CLOCK AND DAY OF WEEK: It is important that the time of day and day of the week is set properly so that occupied and unoccupied programs start on time.
1. Touch the Clock until the hour flashes. Tap the UP or DOWN arrow to select the hour. Note: Make sure hour is correctly set for AM or PM.
2. Touch Clock again and the minutes will flash. Tap the UP or DOWN arrow to select the correct minutes.
3. Touch Clock again and month will flash. Tap the UP or Down arrow to select the correct month.
4. Touch Clock again and the day will flash. Tap the UP or Down arrow to select the day of the month.
5. Touch Clock again and the year will flash. Tap the UP or Down arrow to select the year.
6. To exit the menu, touch Clock again. The proper day of the week will automatically be displayed with the clock and calendar.
PROGRAMMING EVENTS: When the thermostat is configured to provide 2 schedules per day (Occupied/Unoccupied), 7 day per week, each event is displayed on the LCD as DAY (Occupied) and NIGHT (Unoccupied).
1. Touch Program until Mon (Monday) flashes.
2. Tap Program again until the hour flashes and Day is displayed on the LCD. Use the UP or DOWN arrow to set the hour start time. Note: Make sure hour is correctly set for AM or PM.
12
NIGHT STAT SETUP AND SCHEDULING
3. Tap Program again until the minutes flash. Use the UP or DOWN arrow to set
the minutes. 4. Tap Program again and the heating setpoint will flash. Leave
the setpoint at the factory default. 5. Tap Program again and the cooling
setpoint will flash. Leave the setpoint at the factory default. 6. Tap Program
again and the fan option Automatic will flash. Use the UP or DOWN arrow to set
the
fan option to Always On. 7. Tap Program again until the hour flashes and Night
is displayed on the LCD. Use the UP or
DOWN arrow to set the hour start time. Note: Make sure hour is correctly set
for AM or PM. 8. Tap Program again until the minutes flash. Use the UP or DOWN
arrow to set the minutes. 9. Tap Program again and the cooling setpoint will
flash. You can use the UP or DOWN arrow to
change the cooling setpoint or use the factory default of 82 degrees. 10. Tap
Program again and the heating setpoint will flash. You can use the UP or DOWN
arrow to
change the heating setpoint or use the factory default of 60 degrees. 11. Tap
Program again and the fan option Automatic will flash. Leave fan option set to
Automatic. 12. Tap Program again and CPY (Copy) will appear on the LCD. If you
wish to copy the Monday
program to additional days of the week, use the UP or DOWN arrow to add
additional days. Example: Mon Tue Wed Thu Fri 13. Once you have selected the
days to be copied, touch Program. CPY will begin to flash and then the next
programming day will flash. Example: If you copy the Monday schedule through
Friday, Sat (Saturday) will flash. Simply repeat the programming steps for any
day where the building will be unoccupied. The only required change is that
both the Day and Night fan option should be set to Automatic and the heating
and cooling setpoints for Day should reflect the unoccupied setpoints for
Night. 14. Once programming is completed, make sure the thermostat is set in
the Auto mode of operation. 15. Make sure the 2 AA batteries are installed in
the thermostat even though it will be powered by
24 VAC. In the event of a power failure, the batteries will maintain the real
time of day. Batteries should be replaced once a year or whenever the low
battery symbol appears on the LCD.
TYPICAL 7-DAY SCHEDULE HAVING 2 EVENTS PER DAY WITH SATURDAY/SUNDAY UNOCCUPIED
PROGRAM DAYS
SCHEDULE START TIME
HEAT
COOL
SETPOINT SETPOINT
FAN MODE
MON THRU
FRI
SAT AND SUNDAY
DAY NIGHT DAY NIGHT
7:00 AM 5:00 PM 7:00 PM
70
75
FACTORY DEFAULT FACTORY DEFAULT
ALWAYS ON
62
78
FACTORY DEFAULT FACTORY DEFAULT
AUTOMATIC
62
78
AUTOMATIC
5:00 PM
62
78
FACTORY DEFAULT FACTORY DEFAULT
AUTOMATIC
13
ZONE THERMOSTAT SETUP
SWITCH FUNCTIONS The Z-2000-T contains a set of dip switches numbered 1
through 8. Only dip switches 1, 2, 3, 6 and 7 are active.
FACTORY DEFAULT SETTING FOR ALL SWITCHES IF OFF
ON 1 2 3 4 5 6 7 8
…… ….
AB CD EF
Switch 1 – Switch 1 is used to lock the thermostat after setup is completed.
When the thermostat is locked (ON position) a padlock icon will show on the
LCD. When locked, only setpoint changes and status functions can be accessed
by the user. Do not set Switch 1 in the ON position until all setup functions
are completed. Switch 2 – Switch 2 is used to display the space temperature,
duct temperature and setpoint in Celsius (ON position) or Fahrenheit (OFF
position). Select Celsius or Fahrenheit before proceeding to the thermostat
setup menu. Switch 3 – Switch 3 is used to select two-position (ON position)
or fully modulating (OFF position) damper control to best suit the specific
application requirement. Switch 6 – When switch 6 is ON, Heat or Cool are not
displayed. Switch 7 – When switch 7 is ON, the space temperature is replaced
by the setpoint.
KEY FUNCTIONS A = ON/OFF KEY – When the Z-2000-T is not locked, this key
allows the thermostat to be turned ON or OFF. When in the OFF position, the
damper is also driven closed. B = STATUS KEY – Pressing the STATUS key
repeatedly scrolls through the UNIT number, ZONE number, DUCT temperature and
DAMPER position. C and D = UP and DOWN KEYS – Used to increase and decrease
the setpoint, as well as change thermostat setup values. E = SETUP KEY – Used
to toggle through the thermostat setup menu. F = ENTER KEY – Used to enter
changes as well as exit the setup menu.
14
ZONE THERMOSTAT SETUP
ENTERING THE SETUP MENU Press and hold the SETUP key until the word DAMPER
appears on the LCD. (Figure 1)
FIGURE 1
FIGURE 2
SETTING THE MINIMUM DAMPER POSITION Press the SETUP key again and the LCD will display the minimum damper position. The factory
default is 10% which means the damper is driven 90% closed after a heating or cooling call is
satisfied. Press the UP and DOWN keys to change the minimum damper position. Position may be
adjusted in 10% increments. (Figure 2)
FIGURE 3
FIGURE 4
SETTING THE MAXIMUM DAMPER POSITION Press the SETUP key again and the LCD will display the maximum damper position for heating and cooling. The factory default is 100% which means the damper can drive fully open with a call for heating or cooling. Position may be adjusted in 10% increments using the UP and DOWN keys. (Figure 3)
SETTING A UNIT NUMBER Press the SETUP key again and the LCD will display the
word UNIT. The factory default is 00. This number can be used to assign the
Z-2000-T to a particular HVAC unit. Use the UP and DOWN keys to assign a UNIT
number from 00 to 99. (Figure 4)
15
ZONE THERMOSTAT SETUP
SETTING A ZONE NUMBER Press the SETUP key again and the LCD will display the
word ZONE. The factory default is 00. This number can be used to identify each
Z-2000-T thermostat wired to a Z-2000TM zone control panel or when used in
multiple stand-alone applications. Use the UP and DOWN keys to assign a ZONE
number from 00 to 99. (Figure 5)
FIGURE 5
FIGURE 6
SETTING THE HEATING LIMIT Press the SETUP key again and the LCD will display the heating limit. The factory default is 76° F.
Press the UP and DOWN keys to change the heating limit setting. It is strongly recommended that
the limit not be set above the factory default setting. (Figure 6)
SETTING THE CFIOGUORLEIN7 G LIMIT
FIGURE 8
Press the SETUP key again and the LCD will display the cooling limit. The factory default is 68° F.
Press the UP and DOWN keys to change the cooling limit setting. It is strongly recommended that
the limit not be set below the factory default setting. (Figure 7)
SETTING THE ACTUATOR SPEED Press the SETUP key again and the LCD will display
the actuator speed. The factory default is 90 seconds which is the time it
takes the actuator to drive the damper blade fully open or fully closed. This
is a critical step in the Z-2000-T setup since the thermostat can be used with
a variety of 24 Volt actuators. If you are unsure of the actuator speed, place
the actuator in the fully closed position and then apply 24 Volts to common
and normally open. The time it takes to drive the damper blade fully open
equals the actuator speed setting. (Figure 8)
16
ZONE THERMOSTAT SETUP
SETTING THE MODBUS ADDRESS Press the SETUP key again and the LCD will display
the Modbus communications address. The factory default is 01. The Z-2000-T has
integrated Modbus communications capability for remote monitoring and control.
For more information on Modus Communications, contact iO HVAC controls.
FIGURE 9
TEMPERATURE CALIBRATION OFFSET
FIGURE 10
SENSOR LOCATION
Press the SETUP key again and the LCD will display the temperature calibration offset. The factory
default setting is 0. Typically, it is not necessary to adjust the temperature calibration offset, as the
Z-2000-T has been factory calibrated. If calibration is necessary, a high quality electronic digital
thermometer must be used. Place the thermometer sensor probe next to the thermostat sensor and
allow five minutes before comparing the temperature readings. Use the UP and DOWN keys to
adjust the temperature calibration. The range is +/- 9° F.
(Figure 10)
SAVING SETTINGS AND EXITING THE SETUP MENU Press the ENTER key and the Z-2000-T will save the setup menu settings and exit the program. The LCD will display the space temperature along with other normal operating functions. To review the thermostat settings, simply press and hold the SETUP key until the setup menu is displayed and then toggle through the settings. Press the ENTER key to exit the setup menu.
ADVANCED FUNCTIONS
DAMPER POSITION OVERRIDE The Z-2000-T has a damper position override feature
to assist in air balancing and bypass damper setup. With the thermostat
unlocked, press twice and hold the SETUP key until the word DAMPER appears on
the LCD.(Figure 11)
FIGURE 11
17
ZONE THERMOSTAT SETUP
OVERRIDE TO OPEN Press the UP or DOWN key until the word OPEN appears on the
LCD and then press the ENTER key. The damper will drive open and remain in the
open position until the override is cancelled. (Figure 12)
FIGURE 12
FIGURE 13
OVERRIDE TO CLOSE Press the UP or DOWN key until the word CLOSED appears on the LCD and press the ENTER key. The damper will drive closed and remain in the closed position until the override is cancelled. (Figure 13)
CANCELLING THE DAMPER OVERRIDE In order for the Z-2000-T to return to normal operation, the override must be cancelled. Press and hold the SETUP key until the word DAMPER OPEN or DAMPER CLOSE appears on the LCD. Use the UP or DOWN key until only the word DAMPER is displayed and then press the ENTER key. The thermostat will then resume normal operation. (Figure 14)
CHECKING THERMOSTAT STATUS POINTS
FIGURE 14
When the thermostat is first powered, it goes through a synchronization process to confirm the
damper position before becoming operational, after which status points can be checked by
repeatedly pressing the STATUS key and toggling through the following:
UNIT – Displays the HVAC unit number assigned to thermostat.
ZONE – Displays the thermostat zone number.
DUCT – Displays the duct temperature.
DAMPER – Displays the damper position in one degree increments.
(0% = fully closed and 100% = fully open)
18
SYSTEM LED STATUS DEFINITIONS
Z-2000 LED FUNCTION
COLOR
STATUS
Zones (1-20)
Time Delay Speed Up Mode DAS Active COOL
Red Green
Red Green Green
HEAT
Red
OCCUPIED O/B G Y1 Y2 W1 W2 W3/AUX/EH
Green Green Green Green Green Green Green Green
ACTUATOR BOARD LED FUNCTION
HEAT
Red
ON when there is a heating call. ON when there is a cooling call. OFF in normal mode. Blinks in speedup mode. Manual ON/OFF button with 10 minute auto- reset. On when DAS is connected. ON when system is in cooling mode. Blinks when system down-stages or goes out on cooling limit. ON when system is in heating mode. Blinks when system down-stages or goes out on heating limit. On when system is in occupied mode. OFF during unoccupied mode. ON when reversing valve is energized. ON constantly during occupied mode and for 5 minutes after panel goes unoccupied. ON with 1st stage cooling or compressor. ON with 2nd stage cooling or compressor. ON with 1st stage heating. ON with 2nd stage heating. ON with 3rd stage auxiliary heat or E. Heat. ON when space temperature drops 1.5° F below setpoint sending signal to Z-2000 panel.
COOL
Green
Z-2000 PANEL TIME DELAYS
ON when space temperature rises 1.5° F above setpoint sending signal to Z-2000 panel.
FUNCTION MINIMUM TIME IN HEAT OR COOL MODE Once system is in the heat or cool mode, it will remain there for a minimum of 15 minutes. The equipment may or may not be on during this period. MINIMUM CHANGEOVER TIME BETWEEN HEAT OR COOL CALL UPSTAGE TIMING MINIMUM ON/OFF TIME FAN RUN TIME AFTER CLOCK CONTACTS OPEN
NORMAL MODE 15 MIN
5 MIN 10 MIN
5 MIN 5 MIN
19
SPEEDUP MODE 60 SEC
20 SEC 40 SEC 20 SEC 20 SEC
STAGING AND LIMIT CONTROL SEQUENCE
Discharge Air Temperature Setpoints for Conventional Heating Any time the
discharge air temperature goes above the adjustable high limit setting of 145°
F to 175° F, stage 1 heat will drop out. Any time the discharge air
temperature drops below 135° F, stage 1 heat will come on. Any time the
discharge air temperature goes above 125° F, stage 2 heat will drop out. Any
time the discharge air temperature drops below 115° F, stage 2 heat will come
on. Discharge Air Temperature Heating Setpoints for Heat Pump Mode Only Any
time the discharge air temperature goes above 110° F, stage 1 will drop out.
Any time the discharge air temperature drops below 105° F, stage 1 will come
on. Any time the discharge air temperature goes above 100° F, stage 2 will
drop out. Any time the discharge air temperature drops below 95° F, stage 2
will come on. Any time the discharge air temperature goes above 120° F, stage
3 will drop out. Any time the discharge air temperature drops below 115° F,
stage 3 will come on. When stage 3 is energized, heat pump stage 1 and 2 are
locked on and their limits ignored. When the discharge air temperature goes
above 120° F, stage 3 is drops out and a 2 minute time delay is initiated
before stage 1 and 2 limits are activated. Discharge Air Temperature Setpoints
for Conventional Cooling and Heat Pump Any time the discharge air temperature
drops below the adjustable low limit of 40° F to 48° F, stage 1 cooling will
drop out. Any time the discharge air temperature goes above 53° F, stage 1
cooling will come on. Any time the discharge air temperature drops below 52°
F, stage 2 cooling will drop out. Any time the discharge air temperature goes
above 57° F, stage 2 cooling will come on.
www.iohvaccontrols.com For Technical Support Call Toll Free: 866-225-5032
20
iO-06-1402-062724
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>