Danfoss NRVT 10sH Refrigeration Circuit Check Valve Installation Guide
- August 16, 2024
- Danfoss
Table of Contents
Danfoss NRVT 10sH Refrigeration Circuit Check Valve
Specifications
- Model: Check valve Type NRVT
- Certification: UL certified for use in CO2(R744) systems
- Design Pressure : Must meet the value outlined in section 9.2 of ANSI/ASHRAE 15 for the refrigerant used
- Authorized Personnel: Only authorized persons should install the valve
Product Usage Instructions
Installation
This valve is specifically designed for use in CO2(R744) systems. Ensure
that the design pressure meets the requirements outlined in ANSI/ASHRAE 15 for
the refrigerant used. Only authorized personnel should handle the installation
to prevent the build-up of excessive pressure in the system.
Possible Orientations:
The valve can be mounted vertically, horizontally, or inclined.\ Ensure
proper orientation based on system requirements.
Risk Orientations
For risk orientations with a soft spring (Danfoss 20-8041), be cautious of
internal leak risks. Follow proper installation guidelines to mitigate these
risks.
Brazing
When brazing, ensure a minimum of 5% Ag brazing alloy is used to maintain
the integrity of the valve connection.
USING INSTRUCTION
- Refrigerants: R744 (CO˜)
- Temperature range (TS): -40 °C – 150 °C / -40 °F – 302 °F
- Max. working pressure (PS/MWP): 140 bar / 2031 psig
Warning:
This valve is UL certified for use in CO2(R744) systems only. The design
pressure shall not be less than the value outlined in section 9.2 of ANSI/
ASHRAE 15 for the refrigerant used in the system.
Only authorized persons are allowed to install this valve, as closing can
cause build-up of excessive pressure in the system.
Possible orientations(hard spring)
It is possible vertical, horizontal or inclined mounting
Risk orientations(soft spring)
Internal leak risk orientations for soft spring
Brazing
© Danfoss | Climate Solutions
AN400564784627en-000201
FAQ
- Q: Can this valve be used in systems other than CO2(R744)?
- A: No, this valve is UL certified for use in CO2(R744) systems only. Its design and specifications are tailored for this specific refrigerant.
- Q: What should I do if I encounter an internal leak risk orientation?
- A: If you encounter an internal leak risk orientation with a soft spring (Danfoss 20-8041), consult with a qualified technician to address the issue promptly and ensure system safety.