steinel DALI-2 IPD Multisensor True Presence Instruction Manual
- August 16, 2024
- STEINEL
Table of Contents
- About This Document
- General Safety Precautions
- System Description
- Electrical Connection
- Installation
- Function
- Maintenance And Care
- Disposal
- Declaration of Conformity
- Manufacturer‘s Warranty
- Technical Specifications
- Troubleshooting
- Customer Support
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
steinel DALI-2 IPD Multisensor True Presence
About This Document
- Under copyright. Reproduction either in whole or in part only with our consent.
- Subject to change in the interest of technical progress.
Hazard warning!
Warning of hazards from electricity!
Warning of hazards from water!
General Safety Precautions
Failure to observe these operating instructions presents hazards!
These instructions contain important information on the safe use of this product. Particular attention is drawn to potential hazards. Failure to observe this information may lead to death or serious injuries.
- Read instructions carefully.
- Follow safety advice.
- Keep instructions within easy reach.
- Working with electrical current may produce hazardous situations. Touching live parts can result in electrical shock, burns or death.
- Work on mains voltage must only be performed by qualified, skilled personnel.
- National wiring regulations and electrical operating conditions must be observed (e.g. D: VDE 0100, A: ÖVE-ÖNORM E8001-1, CH: SEV 1000).
- Only use genuine replacement parts.
- Repairs must only be carried out by companies qualified to do so.
System Description
Proper use
- Multisensor.
- Ceiling mounting indoors.
- Bluetooth networking.
- Connection to a DALI bus.
- AP version for surface mounting.
- UP version for concealed mounting.
Multisensor variants
- Multisensor True Presence® DALI-2 IPD as a surface-mounted version (AP) or concealed version (UP).
Multisensor
The multisensor can detect the following sensor variables:
- Presence.
- Brightness.
- Room temperature.
- Humidity.
- Air pressure.
- Noise level.
- CO₂.
- VOC (volatile organic compounds).
How presence detection works
- The presence and absence of people is detected by sensing micro-movements.
- The detection range can be precisely limited via an app.
This makes it ideal for use in offices and schools.
For special applications, for example on cruise ships or in hotels, please contact STEINEL GmbH directly so that we can jointly realise optimum integration of the sensors.
Connect Bluetooth Mesh
- The sensors can be networked via Bluetooth.
Note
The CO2 sensor used in the multisensor comes with an auto-calibration
function.
For this to work properly and ensure correct measurement by the CO2 sensor,
the multisensor must be permanently connected to the power supply.
Furthermore, the first seven days after switching on the power supply may show
major variations in the levels measured. The sensor must also be exposed to
fresh air for at least an hour a day.
Scope of delivery – concealed version
- 1 Multisensor
- 1 Safety data sheet (A)
- 1 Quick Start Guide (B)
Scope of delivery – surface-mounted version
- 1 Multisensor
- 1 Safety data sheet (A)
- 1 Quick Start Guide (B)
Product dimensions – concealed version
Product dimensions – surface-mounted version
Device overview – concealed version
- A Load module
- B Terminal
- C Sensor module
Device overview – surface-mounted version
- A Surface-mounting adapter
- B Load module
- C Terminal
- D Sensor module
Detection range
Electrical Connection
The power supply line consists of a 4- or 5-core cable:
L = Live (mostly black, brown or grey)
N = Neutral (mostly blue)
DA = Connection to the DALI bus (mostly blue)
PE = Protective earth (green/yellow)
The device can also be connected electrically after a mains switch, if it is ensured that the mains switch is permanently switched on.
Installation
Hazard from electrical power!
Touching live parts can result in electrical shock, burns or death.
- Switch OFF power and interrupt power supply.
- Using a voltage tester, check to make sure that the power supply is disconnected.
- Make sure power supply remains interrupted.
Risk of damage to property!
Mixing up connection leads may produce a short circuit.
- Identify connection leads.
- Connect the leads correctly.
Preparing for installation
- Check all components for damage. Do not use the product if it is damaged.
- Select an appropriate site to install the product.
- Take reach into consideration.
- Take reach and motion detection into consideration.
- Vibration-free.
- No obstacles in detection zone.
- Not in explosive atmospheres.
- Not on normally flammable surfaces.
Installation steps – concealed version
-
Check that power supply is switched off.
-
Connect load module to the mains power supply.
-
Screw load module into place on mounting box.
-
Fit magnetic sensor module on load module.
-
Switch on power supply.
Installation steps – surface-mounted version
-
Check that power supply is switched off.
-
Mark drill holes.
-
Drill holes (Ø 6 mm) and insert dowels.
-
Pull cable through.
-
Screw on load module.
-
Connect load module to the mains power supply.
-
Break out mounting tab.
-
Fit surface-mounting adapter.
-
Fit magnetic sensor module.
-
Switch on power supply.
-
Make settings.
Function
Initial operation is carried out in accordance with the valid DALI-2 standard. All functions and commands of the DALI standard IEC 62386 Part 101, Part 103, Part 303 and Part 304 are available.
- All sensor values (motion, brightness, temperature, CO2 , VOC, air pressure, noise level and humidity) can be queried by the DALI-2 Application Controller.
- For the motion and brightness values, there is also the option of automatic or time-based cyclical transmission.
Factory settings
The factory settings are activated when the multisensor is operated for the first time and when it is reset by the app.
The following factory settings are provided:
True Presence® detection setting:
True Presence® height 2.6 m
True Presence® radius 3.5 m
True Presence® scenario: Scenario 7
Note:
The parameter description can be found at: www.steinel.de
Steinel Connect app
To read out the sensor values with a smartphone or tablet, it is necessary to download the STEINEL Connect app from your AppStore. A Bluetooth-enabled smartphone or tablet is required.
Functions in connection with the Steinel Connect app:
- Setting the detection range.
- Displaying the current sensor values.
- Networking the sensor.
Start-up : LED flashes blue rapidly for 30 seconds.
Initialisation : LED lights up blue continuously.
Normal operation : LED off.
Identification : LED flashes blue slowly.
Firmware update : LED flashes cyan rapidly.
Error : LED flashes red rapidly.
Connect Bluetooth Mesh
The sensor is configured via the Steinel Connect app.
The corresponding network keys are stored on the smartphone or tablet when the
sensor and Steinel Connect app are connected for the first time. The keys
prevent unauthorised access to the sensor.
The network key must be shared for access via another smartphone or tablet.
True Presence ® DALI-2 IPD detection setting
- Set the range via the Steinel Connect app.
- DALI interface.
Initial operation of the True Presence® DALI-2 IPD
During initial operation, the multisensor creates an image of the room.
During this process, the room must be free of movement for 2 to 2.5 minutes.
The process is complete when the blue LED goes out.
True Presence® DALI-2 IPD detection setting
The range can be set via the parameters installation height, radius and scenario.
Scenario 9:
Small office, quiet workplace
This scenario offers maximum sensitivity. To avoid undesired switching, this scenario should preferably be used for small areas.
Scenario 8:
Large office, quiet workplace
Like scenario 9, but with slightly reduced sensitivity.
Also suitable for large areas.
Scenario 7:
Large office, large entrance area
Like scenario 8, but with further reduced sensitivity.
Scenario 6:
Hotel room, room with sleeping people
This scenario also offers maximum sensitivity. In addition, signal processing
is optimised to reliably detect the presence of persons sleeping.
Scenario 5:
Hotel room, room with sleeping people
Like scenario 6, but with further reduced sensitivity.
Scenario 4:
Noisy workplace, light industry, hall
Vibrations can retrigger the sensor. This can lead to longer stay-ON times in
scenario 7-9. Scenario 4 works more robustly.
Scenario 3:
Noisy workplace, light industry, hall
Like scenario 4, but with further reduced sensitivity.
Scenario 2:
Very noisy environment, heavy industry
This scenario should be used if there are major vibrations or if there are
sources of electrical interference. The True Presence® function is not
available, the sensor functions as a conventional presence detector.
Scenario 1:
Very noisy environment, heavy industry
Like scenario 2, but with further reduced sensitivity.
Maintenance And Care
The device requires no maintenance.
Hazard from electrical power!
Contact between water and live parts can result in electric shock, burns or death.
- Only clean device in a dry state.
Risk of damage to property!
Using the wrong cleaning product can damage the device.
- Clean device with a moist cloth without detergent.
Disposal
Electrical and electronic equipment, accessories and packaging must be recycled in an environmentally compatible manner.
Do not dispose of electrical and electronic equipment as domestic waste.
EU countries only:
Under the current European Directive on Waste Electrical and Electronic Equipment and its implementation in national law, electrical and electronic equipment no longer suitable for use must be collected separately and recycled in an environmentally compatible manner.
Declaration of Conformity
STEINEL GmbH hereby declares that the radio equipment Multisensor True
Presence® DALI-2 IPD complies with Directive 2014/53/EU.
The full wording of the EU Declaration of Conformity is available for
downloading from the following Internet address:
www.steinel.de
Manufacturer‘s Warranty
Manufacturer’s warranty of STEINEL GmbH, Dieselstrasse 80-84, DE-33442
Herzebrock-Clarholz, Germany
All STEINEL products meet the highest quality standards.
For this reason, we, the manufacturer, are pleased to provide you, the
customer, with a warranty under the following terms and conditions:
The warranty covers the absence of deficiencies which are proven to be the
result of a material defect or fault in manufacturing and which are reported
to us immediately after detection and within the warranty period. The warranty
shall cover all STEINEL Professional products sold and used in Germany.
Our warranty cover for consumers
The provisions below apply to consumers. A consumer is any natural person who,
on entering into the purchase transaction, neither acts in exercising their
commercial nor their self-employed activity.
You can opt for warranty cover in the form of repair or replacement which will
be provided free of charge (if applicable, in the form of a successor model of
the same or higher quality) or in the form of a credit note.
In the case of sensors, floodlights, outdoor and indoor lights, the warranty
period for the STEINEL Professional product you have purchased is 5 years in
each case from the date on which the product was purchased.
We shall bear the shipping costs but not the transport risks involved in
return shipment.
Our warranty cover for entrepreneurs
The provisions below apply to entrepreneurs. Entrepreneur is a natural or legal person or partnership with legal personality who or which, on entering into the purchase transaction, acts in exercising their or its commercial or self-employed activity.
We have the option of providing warranty cover by rectifying deficiencies free
of charge, replacing a product free of charge (if applicable, in the form of a
successor model of the same or higher quality) or by issuing a credit note.
In the case of sensors, floodlights, outdoor and indoor lights, the warranty
period for the STEINEL Professional product you have purchased is 5 years in
each case from the date on which the product was purchased.
Within the scope of warranty cover, we shall not bear your expenses accruing
from subsequent fulfillment nor shall we bear your expenses for removing the
defective product and installing a replacement product.
Statutory rights accruing from defects, gratuitousness
The warranty cover described here shall be applicable in addition to the statutory rights of warranty – including special consumer protection provisions – and shall not restrict or replace them. Exercising your statutory rights in the event of defects is gratuitous.
Exemptions from the warranty
All replaceable lamps are expressly excluded from this warranty.
- In addition to this, the warranty shall not cover:
- any wear resulting from use or any other natural wear of product parts or any deficiencies in the STEINEL Professional product that are attributable to wear caused by use or other natural wear,
- any improper or non-intended use of the product or any failure to observe the operating instructions,
- any unauthorised additions, alterations or other modifications to the product or any deficiencies attributable to the use of accessory,
- supplementary or replacement parts which are not genuine STEINEL parts,
- any maintenance or care of products that is not carried out in accordance with the operating instructions,
- any attachment or installation that is not in accordance with STEINEL’s installation instructions,
- any damage or loss occurring in transit.
Application of German law
The warranty shall be governed by German law excluding the United Nations Convention concerning the International Sale of Goods (CISG).
Making claims
If you wish to make a warranty claim, please send your product complete and carriage paid with the original receipt of purchase, which must show the date of purchase and product designation, either to your retailer or directly to us at STEINEL (UK) Ltd. – 25 Manasty Road, Axis Park, Orton Southgate, GB- Peterborough Cambs PE2 6UP United Kingdom. For this reason, we recommend that you keep your receipt of purchase in a safe place until the warranty period expires.
Technical Specifications
-
Dimensions (H × B × T):
Surface-mounted: 123 × 123 × 51 mm
Concealed: 142 × 142 × 45 mm -
Supply voltage: 220 − 240 V / 50/60 Hz
-
Power consumption: 1 W
-
Installation height: 2.8 − 12 m
-
Detection angle: 360°
-
Multisensor True Presence® DALI-2 IPD max.: Ø 9 m
(up to max. installation height 4 m)
Ø 15 m presence
Ø 15 m movement
(adjustable to within one centimetre) -
Temperature range: 0 °C to +50 °C
-
Protection class: IP 20
-
Bluetooth frequency: 2.4 − 2.48 GHz
-
Transmission power, Bluetooth: 4 dBm / 2.5 mW
-
Transmission power, UWB: ≤ -41 dBm / MHz
-
Frequency, True Presence®: 7.2 GHz
(responds to micro-movements of vital functions) -
Power consumption via DALI-2:
(12 − 22.5 V DC, no SELV):
max. 2 mA / 1 participant
Sensor values:
- Light measurement: 2 − 2,000 Lux
- Temperature: 0 − 40 °C
- Relative humidity: 0 − 100 %
- CO2: 400 − 10,000 ppm
- VOC: 0 − 1,000 ppm
- Air pressure: 300 − 1,200 mbar
- Noise level: 0 − 120 dB
Troubleshooting
Sensor transmits an unwanted motion signal.
- Interference factor, e.g. fan, air conditioner or other moving parts in the detection range.
- Reorganise or cover area, increase distance.
- Animals moving within the detection range.
- Reorganise or cover area.
- People are detected through thin walls in the neighbouring room.
- Reduce range of sensor.
- Wind moves paper or plants in the detection area.
- Reorganise area.
- Sensor near WiFi or other radio source.
- Install at least 2 m away from the radio source.
Sensor reacts late to motion.
- Excessive distance to the sensor.
- Install more sensors.
- Optimise sensor positioning.
- Range setting too low.
- Adjust range.
Temperature value inaccurate.
- Adjustment required.
- Enter correction value via sensor settings.
Sensor does not connect to the app.
- App or smartphone crashes.
- Restart mobile device.
Customer Support
STEINEL GmbH
Dieselstraße 80-84
33442 Herzebrock-Clarholz
Tel: +49/5245/448-188
www.steinel.de
Contact
www.steinel.de/contact
References