MClimate Fan Coil Thermostat LoRaWAN®
User manual
MC-LW-FCT-01 MClimate Fan Coil Thermostat
Scan the QR Code to access MClimate Fan Coil Thermostat LoRaWAN® extended documentation
Need some help?
For more product information and issues related to it, visit: mclimate.eu
/lorawan-resources
or write us to: lorawan-support@mclimate.eu
00359 800 3 1010
Monday-Friday 09:00 – 18:00
Sofia, Bulgaria
Sofia Tech Park, Labs Building, 111J Tsarigradsko Shose
What’s inside the box?
Introduction
Overview of the product
The Fan Coil Thermostat (FCT) is a LoRaWAN Thermostat for 2- and 4-pipe Fan
Coil Units, accommodating 1-3 speed or ECM fans. Ideal for building
retrofitting, it enables room-by-room monitoring and control, enhances energy
efficiency and has great potential to reduce heating/cooling expenses
significantly. With its 4.2” e-ink fast refresh display it allows the end-users
to change the target temperature and see current indoor conditions. Its fully
open and transparent communication protocol allows seamless integration into
different systems including MClimate Enterprise platform.
The MClimate FCT is a Class C LoRaWAN device, available for EU868, US915,
AS923 and AU915 regions. This means that there’s real-time communication
between the FCT and the LoRaWAN network – commands can be sent to the FCT and
it will respond as
soon as possible.
MClimate’s ultimate aim is to help decarbonize buildings. The Fan Coil
Thermostat unlocks great retrofitting opportunities – one can gain quick access
to control and monitoring on a room-by-room basis in the building.
MClimate FCT can be integrated into existing BMS and BAS systems. Please visit
MClimate’s website to learn more about this.
The MClimate Fan Coil Thermostat (FCT) can be used with the following FCU
configurations:
FCU | Valve(s) type | FAN type | Configuration |
---|---|---|---|
2-pipe | ON/OFF (220VAC) | 1-3 speeds | 0 |
2-pipe | 3-wire ON/OFF (220VAC) | 1-3 speeds | 1 |
4-pipe | ON/OFF (220VAC) | 1-3 speeds | 2 |
4-pipe | ON/OFF (220VAC) | ECM | 3 |
2-pipe | ON/OFF (220VAC) | ECM | 4 |
2-pipe | 3-wire ON/OFF (220VAC) | ECM | 5 |
Technical wiring diagrams for the different configurations are available further in the document.
The MClimate Fan Coil Thermostat (FCT) also supports the following additional
inputs/outputs:
– Room occupancy/Key card input (opened/closed circuit)
– Auto-changeover external temperature sensor (10k NTC, max 3m length)
– Dew point sensor (opened/closed circuit)
– Filter alarm (opened/closed circuit)
Functions
– Maintenance of room temperature via built-in temperature sensor or external
room temperature/return air temperature sensor
– Automatic or manual changeover between heating and cooling mode
– Selection of operating mode via the operating mode button on the thermostat
– 1-speed, 3-speed or DC 0…10 V fan control (automatic or manual)
– Display of current room temperature or setpoint in °C
– Minimum and maximum setpoint limitation
– Buttons lock
– 1 digital input, freely selectable for:
– Occupancy mode contact (keycard)
– Automatic heating/cooling changeover 10k NTC
– Dew-point sensor
– Fault input
– Advanced fan control function, e.g. fan kick, selectable fan operation
(enable, disable or depending on heating or cooling mode)
– Installer’s menu for setting the desired wiring configuration and further
settings.
Technical specifications
Designed and manufactured by MClimate™ in the EU.
SKU: MC-LW-FCT-01
Dimensions: 105 x 115 x 23mm
Weight: 220gr
Materials: ABS, PC, Stainless steel
Radio frequency range: 863÷870MHz / 902-928MHz
Radio technology: LoRaWAN Class C, EU868, US915,
AS923 and AU915
Power supply: 110-240VAC, 50/60Hz, 50mA
Outputs:
Output (1-4): 5(2)A
Output 5NA, 5NC: 5A
No internal fuse. External preliminary protection with max. current 10A
circuit breaker required in all cases.
Fan Control (1-3 speed fans): Q1, Q2, Q3 – 100-240VAC
Rating min, max, resistive (inductive): 5(2)A
Fan Control (ECM fans): IO1 and IO2, control signal between 0VDC and 10VDC
Fans must NOT be connected in parallel! Connect one fan directly, for
additional fans, one relay for each speed.
Control outputs V1, Q1-Q3: 100-240VAC; 5A resistive load, 2A reactive load
(cos > 0,4)
Control output V2: 100-240VAC, resistive load only, max 5A 3A fast microfuse,
cannot be exchanged
Multifunctional analogue/digital input/output IO1 and IO2:
Operation: Selectable through downlink. Available options are auto change-over
NTC, ECM FAN, filter alarm contact, dew point sensor contact, occupancy
(keycard) contact.
Change-Over temperature sensor:
Type: 10k NTC (10k at 25 degrees C)
Temperature range: 0 to 125 degrees C
Maximum cable length: 50m at 1.31mm2 (AWG 16).
Connection terminals: Solid wire or prepared stranded wire, 0.05mm2 – 1.31mm2
(AWG 24 to AWG 16)
Based on EU Regulation 813/2013(Eco design directive) and 811/2013 (Labeling
directive) concerning space heaters, combination heaters ,the following
classes apply:
Application with On / Off operation of a heater Class I value
1.0% PWM (TPI) room thermostat, for use with Class IV value
2.0% On/Off output heaters. Application with On / Off operation of a heater
Class I value 1.0%
Sensors: Temperature & Humidity
Operating conditions:
Operating temperature: 0°С to +50°С
Operating humidity: 0-80% RH (non-condensing)
Storage & Transport conditions: As per IEC 60721-3-1
Temperature: −25…65 °C
Humidity: <95% r.h.
IP rating: IP31 (EN60529)
Mounting options: Screws and dowels on a wall or screws only on an electrical
box; Anti-theft bracket with secure screw (T5 Torx).
Safety Instructions
Environmental conditions in which the device is intended to operate:
– Indoor use only;
– for altitude up to 2000m;
– for an ambient temperature: 0°С to +50°С;
– for maximum relative humidity of 80% for temperature up to 31°С, decreasing
linearly to 25% relative humidity at temperature 50°С;
– for an environment with a degree of contamination 2 (PD2).
The device is a thermostat – it’s used for controlling purposes only and it is
not meant to serve as protection.
Legal Notices
All information, including but not limited to, features, functionality, and /
or other product specifications are subject to change without notice. MClimate
retains all rights to review or update its products, software or documentation
without being required to notify any natural or legal person.
The MClimate and MClimate logo are trademarks of MClimate Jsc. All other brands and product names mentioned herein are trademarks of their respective owners.
EU Declaration of Conformity
This device complies with the essential requirements and other applicable
provisions of the following EU directives:
2014/53/EU
2014/30/EU
EN 55032
EN 55035
2014/35/EU
EN 60730-2-9
EN 62368-1
Installation Guide
Tools required (not exhaustive, depends on what thermostat you are replacing):
– T5 torx screwdriver (used on secure bolt on mounting plate).
– Small flat screwdriver (used for connecting wires to the terminal block).
Before you install the device, we highly recommend that you first commission it on your LNS. Once the device is powered, it’ll initiate a LoRaWAN join- procedure using SF12. Please, make sure you enable ADR in your LNS and/or mark the device as static. The lower the spreading factor, the better the communication interval from the FCT to the LoRaWAN gateway will be.
- Open your LoRaWAN® Network provider access panel and add the device using the supplied Serial Number, DevEUI, AppEUI (JoinEUI) and AppKey.
- Continue the Installation with the instructions of your LoRaWAN® Network provider.
The data is example. Do not use.
Installation Guide
High voltage, danger of electrocution!
The removal of the device from the metal mounting bracket exposes parts which
carry mains voltage.
The unit should be opened only by a qualified electrician or by the
manufacturer‘s service personnel. Before starting any work on the electrical
connections, separate the unit from the mains power supply. To prevent access
by unqualified persons and, in particular, children, do not leave the opened
unit unattended. Do not insert any objects, or allow any objects to fall, into
the housing‘s slits. Disconnect any damaged devices from the mains power
supply.
Danger – Electrical voltage!
Contact with components carrying dangerous voltages, an ungrounded thermostat
as well as uninsulated, unsecured cables can cause electric shock and result
in property damage, serious injury, or death.
– Disconnect the device from the power supply before making any electrical
connections.
– Insulate and secure all unused cables and wires before applying voltage to
the thermostat.
The following conditions must be met or observed during the installation:
- Connection may only be performed when the system is disconnected from the electrical supply.
- The unit must be protected against contact.
- There must be an external primary isolating facility.
- The device must not be installed in vibrating systems (e.g. means of transport such as ships) because the vibrations can cause micro-interruptions in the relays.
- The plant devices are connected via screw terminals with the appropriate 0.25N torques.
Mounting
The room thermostat must be mounted in a clean, dry indoor place and must not
be exposed to drip or splash water.
Comply with local regulations to wire and protect the thermostat.
Warning!
No internal line protection for supply lines to external consumers (Q1, Q2,
Q3, V1 and V2) It is recommended to use 6A circuit breaker for each one. Risk
of fire and injury due to short-circuits!
Warning!
Do not mount the device on a metallic surface.
Use only valve actuators rated for 100-240VAC
Disconnect power supply before removing the thermostat from the mounting
plate!
Adapt the line diameters as per local regulations to the rated value of the
installed overcurrent protection device.
Inputs IO1 and IO2 carry mains potential. If the sensor’s cables are extended,
they must be suited for mains voltage.
The 100-240VAC mains line must have a circuit breaker with a rated current of
no more than 10 A.
Properly size the cables to the thermostat, fan and valve actuators for
100-240VAC mains voltage.
Find out what is the correct wiring diagram.
Further in this document, you’ll find wiring diagrams for different types of
Fan Coil Units, compatible with the Fan Coil Thermostat. You have to determine
which wiring diagram is your FCU using and later wire the terminals
accordingly. Correctly identifying the wiring diagram of paramount importance
for the correct working of the Fan Coil Thermostat.
When connecting any wires to the FCT terminals, please do not leave any stranded wires or exposed wire metal not fully in the terminal.
Connect the wires according to the chosen Wiring Diagram in Step 2.
Then re-insert the power module into the FCT and restore the power using the
breaker.
Enter the Installer’s menu by turning the device off first (hold the M button
for 3 second), then hold the reset button (on the back) and the fan speed
button for 5s
Check the connections in every 6 month and tighten them again if needed!
Once you enter the Installer’s menu, select the correct wiring diagram for your application.
Validate that the Fan Coil Unit is reacting to adjusting the modes, fan speed and target temperature through the FCT.
User Interface Guide
Physical buttons
The device has 4 visible physical buttons.
Assembled MClimate Fan Coil Thermostat
LoRaWAN®, top view
# | Button | Function |
---|---|---|
1 | ON/OFF/MODE | When device is OFF: |
Short press turns the thermostat ON.
When device is ON:
Short press changes between different operational modes
(heating/cooling/ventilation) Long press 3 seconds turns the thermostat OFF.
2| Down arrow| Decreases target temperature Navigates items in Installer’s
menu
3| Up arrow| Increases target temperature Navigates items in Installer’s menu
4| Fan| Changes the fan speed according to the allowed fan speeds.
User interface
The device has a simple and intuitive user interface.
Assembled MClimate Fan Coil Thermostat
LoRaWAN®, top view
# | Section | Meaning |
---|---|---|
1 | Modes | |
selection | Shows the current selected operational mode – |
heating/cooling/ventilation
2| Current temperature| Indicates the current temperature measured in the
room.
3| Humidity| Indicates the current relative humidity measured in the room.
4| Target temperature| Shows the current target temperature of the thermostat
5| Fan speed| Shows the selected fan speed.
6| Occupancy| Occupied/not occupied. Determined by an additional sensor wired
to IO1 and IO2 or set through a downlink.
7| LoRaWAN signal| Indicates the current spreading factor
8| Valve status| Indicates if any of the valves are currently open or closed.
Only 1 valve can be opened at a time.
9| Messages| Various messages displayed – Join Request/Join Accept/Join
Failed/Sending, indicating the radio activity of the device.
10| Lock| Shows in case some of the buttons are locked
11| Filter alarm| Shows in case a filter alarm is connected to the IO1 and IO2
terminals.
Operating Instructions
Temperature adjustment
Use the up and down button to adjust the target temperature.
The target temperature cannot be adjusted while in Ventilation mode.
If you want to change the step of increase/decrease of the target temperature,
you can further configure it via a downlink.
Turning the thermostat ON/OFF
The button on the far left of the thermostat serves two functions – turn it on
and off and switch between modes.
If the thermostat is currently off (screen is blank), a short press of the
ON/OFF/MODE button will turn it on. The device should show more information,
incl. measured temperature & relative humidity, fan speed and target
temperature if the selected mode is heating or cooling.
If you want to turn the thermostat OFF, hold the ON/OFF/MODE button for 3s.
Fan Speed
If you want to change the fan speed, you can click the FAN button. You will be
able to change the fan speed based on the allowed fan speeds in your wiring
diagram (e.g. ECM fans have 6 speeds).
Further, using a downlink, you can limit the selection of the fan speed – e.g.
make it so that only the first and second speed can be used.
Mode selection
By default, the device supports 3 operating modes –
heating/cooling/ventilation. Depending on the wiring diagram of the Fan Coil
Unit, some modes might be disabled by default. E.g. if you are using a 2-pipe
fan coil unit, it can either heat or cool, it cannot do both throughout the
whole year. In this case, short-pressing the ON/OFF/MODE button will switch
between heating/ventilation or cooling/ventilation, depending on the current
allowed operational modes. If you are using a 10k NTC connected to IO1 and
IO2, the FCT will determine the allowed operational modes independently based
on whether the system is circulating hot or cold water.
Connectivity and Smart Building Features
Explanation of LoRaWAN Class C connectivity
LoRaWAN Class C enables devices to constantly listen for commands from the
gateways. It means that the device will send information only on the keepalive
interval, or any change in the target temp/mode/fan speed selection occurs,
but unlike Class A devices, the FCT is able to receive commands from the
Application/Network server in real-time.
Integration with MClimate Enterprise
The device is compatible with our Building Management Software MClimate
Enterprise, which unlocks monitoring and controlling capabilities using
MClimate devices. For further instructions on how to add your MClimate FCT to
the Enterprise, please refer to the available documentation on our website.
Integration with Building Management Systems
(BMS) and Building Automation Systems (BAS)
In case you want to integrate the MClimate FCT into an existing BMS/BAS
system, that’s possible when using a special gateway that translates the
signal from LoRaWAN and exposes the device’s points as e.g. Modbus or BACnet
objects for further processing. Refer to our website for up-to-date
information on available LoRaWAN <> BMS gateways.
Wiring diagrams
Heating and cooling with 3-speed fan
Heating and cooling with ECM Fan
www.mclimate.eu
Designed & Manufactured by MClimate in Europe.
last update: 28.05.2024