EPH CONTROLS RFRPV2 Programmable RF Thermostat and Receiver Installation Guide
- July 31, 2024
- EPH CONTROLS
Table of Contents
RFRPV2 Programmable RF Thermostat and Receiver
Specifications
- Power Supply: 2 x AA Alkaline Batteries
- Power Consumption: 2 mW
- Battery Replacement: Once a year
- Dimensions: 130 x 95 x 23mm
- Frost Protection: Only operational in OFF and Holiday mode
- Pollution Degree: Pollution degree 2
Product Information
RFRPV2 Room Thermostat
How Your Programmable Thermostat Works
When the thermostat is in AUTO mode, it operates based on the
programmed times and temperatures. Users can choose from 6 programs
per day, each with a specific time and temperature setting. There
is no OFF time, only higher and lower temperature settings. To keep
the thermostat OFF at a certain time, set the temperature low for
that period.
Mounting & Installation
Follow the installation instructions provided in the manual.
Ensure proper mounting to allow for accurate temperature readings
and efficient operation.
Operating Instructions
Refer to the user manual for detailed instructions on using the
thermostat, including LCD symbol descriptions, button functions,
resetting, locking/unlocking, setting date/time, programming modes,
copy function, temporary override, auto mode, boost function,
battery warnings, and more.
Frost Protection
The thermostat is equipped with built-in frost protection. When
activated in OFF or Holiday mode, it triggers the boiler if the
temperature falls below the setpoint. A specific symbol indicates
when frost protection is active.
RF1B Wireless Receiver
Mounting & Installation
Install the RF1B receiver as instructed in the manual. Proper
wiring and placement are essential for seamless communication with
the thermostat.
Operating Instructions
Learn about the button and LED functions of the RF1B receiver to
ensure smooth operation. Understand how to pair receivers,
connect/disconnect from the thermostat, and pair with a GW04
Gateway.
System Architecture
Understand how to configure the RF1B receiver as a Hub or Branch
receiver. Learn to identify Hub receivers, pair receivers, and
disconnect them from other devices for effective system setup.
FAQ
What should I do if the battery low warning appears on the
thermostat?
If you see a battery low warning, replace the batteries with new
AA alkaline batteries as per the specified replacement interval
(once a year).
How can I activate frost protection on the thermostat?
Frost protection is automatically activated in OFF and Holiday
mode. Ensure the setpoint triggers the boiler when the temperature
drops below the desired level.
CP V
Programmable RF Thermostat & Receiver Installation and Operation Guide
Table of contents
RFRPV2 Room Thermostat
Installation Instructions
5
Factory Default Settings
6
Frost Protection
6
Specifications
7
How your programmable thermostat works
8
Mounting & Installation
9
Important notes
12
RF1B Wireless Receiver
Installation Instructions
13
Specifications & Wiring
14
Important notes
15
Mounting & Installation
16
RFRPV2 Room Thermostat
Operating Instructions
18
LCD Symbol Description
19
Button Description
20
Resetting the thermostat
21
Locking and unlocking the thermostat
21
Setting the date, time and programming mode
22
Factory Program Setting
23
Programming Modes
24
Adjust the program setting in 5/2 Day mode
25
Copy Function
26
Temporary Override
26
Auto Mode
27
Permanent Override
27
Boost Function
28
Battery low warning
29
Frost PRreoptleacctiinognthe batteries
29
Installer menu
30
P0 1 Operating Mode
32
Normal
32
Optimum Start
33
TPI
35
P0 2 Setting High & Low Limits
37
P0 3 Hysteresis
38
P0 4 Calibrate the thermostat
39
P0 5 Frost Protection
40
P0 6 Holiday Function
41
Frost PP0ro7teBcatcioknlight
42
P0 8 PIN Lock
43
Exit
46
RFRPV2 Room Thermostat (Continued) Table of contents
Installer menu – OpenTherm®
31
P0 9 Setting DHW temperature
47
P10 OpenTherm® Information
48
P11 DHOP
49
P12 Set OpenTherm® Parameters
49
Exit
51
System Architecture
52
Controlling an OpenTherm® Boiler with multiple CP4V2
54
Making your RF1B receiver either a Hub or Branch receiver
54
Identifying if a receiver is a Hub receiver
55
Pairing the RF1B receivers together
55
Disconnecting the RF1B receiver from other receivers
55
RF1B Wireless Receiver
Operating Instructions
56
Button / LED Description
57
LED Description
58
To connect the RFRPV2 Thermostat to an RF1B receiver
59
To disconnect the RFRPV2 Thermostat from an RF1B receiver
61
Pairing you RF1B receiver to your GW04 Gateway
60
Service Interval
62
RFRPV2 Room Thermostat Installation Instructions
5
RFaFcRtoPr-yODTeRfoauolmt STehtteinrmgsostat
Temperature indicator:
°C
Switching differential:
0.4°C
In built frost protection:
5°C
Clock:
24 hours
Keypad lock:
Off
Operating mode:
5/2 day
Backlight:
AUTO
High & Low Limits:
35°C & 5°C
Pin Lock:
OFF
Frost Protection
5°C
Frost protection is built into this thermostat.
It has a factory default of 5°C and is adjustable from 5…15°C.
When frost protection is activated the thermostat will switch on the
boiler when the temperature drops below the setpoint.
This symbol will show on the screen when frost protection is active.
Frost protection is only active in OFF and Holiday mode.
6
RFRPV2 Room Thermostat CP4V2
Specifications
Power supply:
2 x AA Alkaline Batteries
Power consumption: 2 mW
Battery replacement: Once a year
Temp. control range: 5…35°C
Ambient temperature: 0…45°C
Dimensions:
130 x 95 x 23mm
Temperature sensor: NTC 100K Ohm @ 25°C
Temperature indication: °C
Frost protection:
Only operational in OFF and Holiday mode
Pollution degree:
Pollution degree 2
RFRPV2 Room Thermostat CP4V2
7
How your programmable thermostat works
When the thermostat is in the AUTO mode, it will operate according to the
times and temperatures that have been programmed. The user can select from 6
different programs per day – each with a time and a temperature.
There is no OFF time, only a higher and a lower temperature.
If the user wants the thermostat to be OFF at a certain time, set the
temperature for this time to be low. The thermostat will turn ON if the room
temperature is lower than the setpoint for the current period.
Example: If P1 is set to be 21°C at 6am, and if P2 is set to be 10°C at 8am,
the thermostat will look for the temperature to be 21°C between 6am and 8am.
8
RFRPV2 Room Thermostat CP4V2
Mounting & Installation
Caution! Installation and connection should only be carried out by a qualified
person. Only qualified electricians or authorised service staff are permitted
to
open the thermostat. If the thermostat is used in a way not specified by the
manufacturer, its
safety may be impaired. Prior to setting the thermostat, it is necessary to
complete all required
settings described in this section. This thermostat can be mounted in the
following ways: 1) Directly mounted on wall. 2) Free standing – Stand
Included. Note: For accurate temperature control it is recommended to mount
the
thermostat as per the installation drawing on Page 11. *If installing multiple
CP4V2 / CP4V2 -HW please see page 15 & 50. Note: If installing multiple CP4V2
/ CP4V2 -HW please ensure to keep a minimum of 25cm distance between
receivers.
RFRPV2 Room Thermostat CP4V2
9
Mounting & Installation Continued
- The mounting height should be 1.5 metres above the floor level. 2) The
thermostat should be situated in the room where the
heating is to be controlled. The place of installation should be chosen so that the sensor can measure the room temperature as accurately as possible. Choose the mounting location to prevent direct exposure to sunlight or other heating / cooling sources when mounted. 3) Fix the mounting plate directly to the wall with the screws provided. 4) Attach the thermostat to the mounting plate. 5) Lower the flap at the front of the thermostat. There is a battery compartment located below the buttons. Apply downward pressure to remove the cover. 6) Insert the 2 x AA batteries and the thermostat will turn on. Close the battery compartment.
10
RFRPV2 Room Thermostat CP4V2
1
2
95 130
3
4
5
6
Important Notes
Good quality batteries are essential to ensure the correct operation of this
product. EPH recommend using Duracell or Energiser batteries.
Do not use low quality battery brands as they can cause the following
problems:
– Stop the wireless communication with the receiver. – Can cause the
thermostat to reset. – Can cause the thermostat to display the incorrect
information.
· When the battery low symbol appears on the CP4V2, CP4V2 -HW or EMBER App.
The batteries should be changed immediately.
· If a Symbol appears on your thermostat screen, please see page 21 for
unlocking instructions.
· If `OVERRIDE’ appears on your thermostat screen, please see page 27.
12
RFRPV2 Room Thermostat CP4V2
RF1B Wireless Receiver Installation Instructions
13
Specifications & Wiring
Power supply:
200 – 240Vac 50-60Hz
Contact rating:
250 Vac 10(3)A
Ambient temperature: 0 … 45°C
Automatic action:
Type 1.C.Q
Appliance classes:
Class II appliance
Pollution degree:
Pollution degree 2
IP Rating:
IP20
Rated Impulse Voltage: Resistance to voltage surge 2500V
as per EN 60730
Internal wiring diagram for RF1B
COM OFF
NL
200-240V~ 50/60Hz
ON
OT OT
Switching Options
Mains Switching – Link L to 1.
Low Voltage Switching – Remove the external controls link
from the boiler PCB. – Connect 1 and 4 to these terminals.
14
RF1B Wireless Receiver
CP4V2
Important Notes
Each receiver should have a minimum 25cm distance from any metal object such
as a pipe or a minimum 25cm from any electrical device such as a spur or
socket. It should not be fitted close to wireless devices such as a router or
Wi-fi booster. This is to ensure the best possible wireless connectiona and
operating range.
When installing multiple receivers, it is important to ensure that there is a
minimum 25cm between each receiver. If they are too close, they will not be
able to pair with each other.
Where possible, keep the receivers in the same area of the premises to allow
for stable communication.
25cm
RF1B Wireless Receiver
CP4V2
15
Mounting & Installation
- The RF1B receiver should be wall mounted in an area within 20 metres distance of the wireless thermostat. It is important that the receiver has over 25cm clearance from metal objects as this will affect communication with the thermostat.
The receiver should be installed at least 1 metre from any electronic devices such as radio, TV, microwave or wireless network adapter.
-
Use a Phillips screw driver to loosen the screws of the backplate on the bottom of the RF1B. The receiver is lifted upwards from the bottom and removed from the backplate. (see page 17)
-
Screw the backplate to the wall with the screws provided.
-
Wire the backplate as per the wiring diagram on page 14.
-
Mount the receiver on the backplate making sure the pins and the backplate contacts are making a sound connection. Push the receiver flush to the surface and tighten the screws of the backplate from the bottom. (See page 17)
-
If installing more than one RF1B receiver ensure they are 25cm apart.
16
RF1B Wireless Receiver
CP4V2
1
2
89
89
3
4
5
6
17
RFRPV2 Room Thermostat Operating Instructions
18
LCD Symbol Description
Current program
Day / Month Current Time (Boost to time)
Room Temperature Day of the week
Frost symbol
Battery low symbol
Wireless symbol
Heating on symbol
Keypad lock symbol
Operating mode
Target Temperature
RFRPV2 Room Thermostat CP4V2
19
Button Description
Automatic mode (Back)
Manual mode
Setpoint increase Wireless connect button Reset button Setpoint decrease
OK confirm button
Boost mode
Set Date / Time
OFF mode Program mode
Automatic mode Manual mode Off mode Program mode
Time Boost mode Confirm button Reset button
+ Setpoint increase
Setpoint decrease
Wireless connect button
20
RFRPV2 Room Thermostat CP4V2
ReFsRePtt-iOnTg RthoeotmheTrmheorsmtaotstat
Press the button on the side of the thermostat.
`rst nO’ will appear on the screen.
Press + .
`rst yes’ will appear on the screen.
Press
to reset the thermostat.
The thermostat will restart and revert to its factory settings.
Locking and unlocking the thermostat
OFF
To lock the thermostat
Press and hold + and
for 10 seconds.
will appear on the screen. The keypad is now locked.
To unlock the thermostat
Press and hold + and
for 10 seconds.
will disappear from the screen. The keypad is now unlocked.
RFRPV2 Room Thermostat CP4V2
21
Setting the date, time and programming mode
Press TIME once, the year will begin flashing.
Press + and
to adjust the year.
Press .
Press + and
to adjust the month.
Press .
Press + and
to adjust the day.
Press .
Press + and
to adjust the hour.
Press .
Press + and
to adjust the minute.
Press .
Press + and
to adjust from 5/2d to 7d or 24h mode. Press
.
Press + and
to turn DST (Day Light Saving time) On or Off.
Press AUTO or wait 5 seconds and the thermostat will return to normal operation.
22
RFRPV2 Room Thermostat CP4V2
Factory Program Setting
Mon-Fri Sat-Sun
Mon-Fri Sat-Sun
Everyday
P1 06:30 21°C 08:00 21°C
P1 06:30 21°C 08:00 21°C
P1 06:30 21°C
5/2 Day
P2
P3
08:00
12:00
10°C
10°C
10:00
12:00
10°C
10°C
P2 08:00 10°C 10:00 10°C
7 Day P3 12:00 10°C 12:00 10°C
24 Hour
P2
P3
08:00
12:00
10°C
10°C
5/2d
P4 14:00 10°C 14:00 10°C
P5 17:30 21°C 17:30 21°C
P4 14:00 10°C 14:00 10°C
P5 17:30 21°C 17:30 21°C
P4 14:00 10°C
P5 17:30 21°C
P6 22:00 10°C 23:00 10°C
P6 22:00 10°C 23:00 10°C
P6 22:00 10°C
RFRPV2 Room Thermostat CP4V2
23
Programming Modes
The RFRPV2 Room Thermostat has the following programming modes available:
5/2 Day mode
Programing Monday to Friday as one block and Saturday and Sunday as a 2nd block.
Each block can have 6 different times and temperatures.
7 Day mode
Programming all 7 days individually with different times and temperatures.
24 Hour mode
Programming all 7 days as one block with the same time and temperatures.
If 7 D mode is selected, you can program each day of the week with 6 individual times and temperatures. If 24H mode is selected, you can only program each day of the week with the same 6 times and temperatures. See page 22 to select 5/2D, 7d or 24hr mode.
24
RFRPV2 Room Thermostat CP4V2
Adjust the program setting in 5/2 Day mode
Press PROG .
Programming for Monday to Friday is now selected.
Press + and
to adjust the P1 time.
Press .
Press + and
to adjust the P1 temp.
Press .
Repeat this process to adjust P2 to P6 times & temperatures. Press .
Programming for Saturday to Sunday is now selected.
Press + and
to adjust the P1 time.
Press .
Press + and
to adjust the P1 temp.
Press .
Repeat this process to adjust P2 to P6 times & temperatures.
Press AUTO to return to automatic mode.
While in PROG Mode pressing PROG will jump from P1 – P2 etc without changing the temperature.
While in PROG Mode pressing TIME will jump to the next day (block of days).
RFRPV2 Room Thermostat CP4V2
25
Copy Function
Copy function may only be used if the thermostat is in the 7d mode.
Press PROG . Select the day of the week you want to copy from.
Press BOOST .
The day of the week that you have selected will be shown with `COPY’.
The next day will begin to flash on the top of the screen.
Press + to copy the times and temperatures to that day.
Press
to skip a day.
You can copy to multiple days by using + .
Press
when copying has been completed.
Temporary Override
When in AUTO mode, press + or
to adjust the temperature
setpoint. `OVERRIDE’ will appear on the screen.
Press
or after 5 seconds the thermostat will operate to this
temperature, until the next switching time.
To cancel temporary override, press AUTO to return to the automatic mode.
26
RFRPV2 Room Thermostat CP4V2
Auto Mode
When the thermostat is in the AUTO mode it will automatically change the
temperature throughout the day according to the schedule set by the user in
the PROG menu.
If the room temperature falls below the setpoint it will activate the heating.
See Page 8 for more information.
Note: If the heating is set to default Program 6 is 16°C. If during the night
the heating falls below 16°C it will turn on the heating. If you do not want
this to happen you should adjust P6 to a lower temperature.
Permanent Override
Press MAN to enter the manual mode (Permanent Override).
`MAN’ will appear on the screen.
Press + or
to adjust the temperature setpoint.
Press
or after 5 seconds the thermostat will operate in this
permanent override.
To cancel permanent override, press AUTO to return to the automatic
mode.
RFRPV2 Room Thermostat CP4V2
27
Boost Function
The thermostat can be boosted to a specific temperature for 30minutes, 1, 2 or 3 hours while the thermostat is operating in all modes except for holiday mode.
Press BOOST once for 30 minutes,
twice for 1 hour,
three times for 2 hours or
four times for 3 hours
Press
to confirm.
The boost temperature will flash.
Press + or
to select required temperature.
Press
to confirm.
`BOOST TO’ will now be displayed on the screen with the time that it is activated to displayed above this text.
Press BOOST to deactivate the boost.
28
RFRPV2 Room Thermostat CP4V2
Battery low warning
When the batteries are almost empty, the symbol will appear on the screen. The
batteries must now be replaced or the unit will shut down. A good quality
brand must be used – see important notes on Page 12.
Replacing the batteries
Lower the flap at the front of the thermostat. There is a battery compartment
located below the buttons. Apply downward pressure to remove the cover. Insert
the 2 x AA batteries and the thermostat will turn on. Close the battery
compartment.
RFRPV2 Room Thermostat CP4V2
29
Installer menu
To access the installer menu, press and hold PROG and
for 5 seconds.
When in the installer menu, press + or
to navigate and press
to select. Use AUTO , MAN or OFF to go back a step.
P0 1: Operating Mode (Normal / Optimum Start / TPI) P0 2: Hi Lo (limiting the thermostat) P0 3: Hysteresis (differential) P0 4: Calibration P0 5: Frost Protection P0 6: Holiday mode P0 7: Backlight P0 8: PIN Exit: Exit from menu
30
RFRPV2 Room Thermostat CP4V2
Installer menu OpenTherm® Instructions
P0 9: Setting DHW temperature P 10: OpenTherm® Information P 11: DHOP P 12:
Set OpenTherm® Parameters Exit
RFRPV2 Room Thermostat CP4V2
31
P0 1 Operating Mode Normal
There are three settings for selection, Normal, Optimum Start or TPI mode.
The default setting is Normal.
Press and hold PROG and
for 5 seconds.
`P01 & Nor’ will appear on the screen.
Press
to select.
Press + or
to select between:
Nor (Normal mode)
OS (Optimum start)
TPI (Time Proportion Integral mode)
Press
to confirm the mode.
Press AUTO to return to normal operation.
Nor (Normal Mode)
When the thermostat is in Normal mode, the thermostat will try to reach the
target temperature at the program time.
Example: Program 1 on the thermostat is 21°C for 06:30am and the room temperature is 18°C. The thermostat will start the heating at 06:30am and
the room temperature will start to increase.
32
RFRPV2 Room Thermostat CP4V2
OS (Optimum Start Mode) When the thermostat is in Optimum Start mode, the
thermostat will try to reach the target temperature by the start time of the
next program. This is done by setting the Ti (time interval) on the thermostat
in this menu to 10, 15, 20, 25 or 30. This will allow the thermostat 10, 15,
20, 25 or 30 minutes to increase the room temperature by 1°C. Ti can be set
when OS is selected in the installer menu. 20°C To achieve the target
temperature when the program starts, the thermostat will read:
1. The Room Temperature (RT) 2. The Setpoint Temperature (ST) 3. The Target
Temperature Difference (TTD) is the difference
between the setpoint temperature and the room temperature . The time (in
minutes) that it will take to overcome (TTD) is called Optimum Start Time
(OST) and its maximum value is 3 hours = 180 mins. This is subtracted from the
start time. As the temperature increases the thermostat will recalculate the
OST if the temperature is increasing too quickly.
RFRPV2 Room Thermostat CP4V2
33
OS (Optimum Start Mode) Continued
Optimum Start Time (Mins)
Optimum Start Control Graph with Ti = 20 0 20 40 60 80
100 120 140 160 180
9 87654321 Target Temperature Difference °C TTD
Example when Ti = 20 Program 1 on the thermostat is 21°C for 06:30am and the
room temperature is 18°C. The thermostat will start the heating at 05:30am to
reach 21°C for 06:30am @ Ti=20.
Example when Ti = 10 Program 1 on the thermostat is 21°C for 06:30am and the
room temperature is 18°C. The thermostat will start the heating at 06:00am to
reach 21°C for 06:30am @ Ti=10.
Optimum Start Time (Mins)
Optimum Start Time (Mins)
Optimum Start Control Graph with Ti = 15 0 15 30 45 60 75 90
105 120 135
987654321 Target Temperature Difference °C TTD
Optimum Start Control Graph with Ti = 10 0 10 20 30 40 50 60 70 80 90
987654321 Target Temperature Difference °C TTD
34
RFRPV2 Room Thermostat CP4V2
P0 1 Operating Mode Continued
TPI (Time Proportional & Integral Mode)
When the thermostat is in TPI mode and the temperature is rising in the zone
and falls into the Proportional Bandwidth section, TPI will start to affect
the thermostats operation. The thermostat will turn on and off as it gains
heat so that it doesn’t overshoot the setpoint by too much. It will also turn
on if the temperature is falling so it doesn’t undershoot the setpoint which
will leave the user with a more comfortable level of heat.
There are 2 settings that will affect the thermostats operation:
1. CYC – No. of Heating Cycles per Hour: 6 Cycles
This value will decide how often the thermostat will cycle the heating on and
off when trying to achieve the setpoint temperature. You can select 2/3/6 or
12.
2. Pb – Proportional Bandwidth: 2°C
This value refers to the temperature below the setpoint at which the
thermostat will start to operate in TPI Control. You can set this temperature
from 1.5°C to 3.0°C in 0.1°C increments.
RFRPV2 Room Thermostat CP4V2
35
TPI (Time Proportional & Integral Mode) Continued
Temp 22°C 21°C 20°C 19°C 18°C 17°C
TPI Control
Setpoint Temperature Proportional Bandwidth
0
20
40
60
80
100 Time Minutes
Heating On
Heating Off
Example: Program 1 on the thermostat is 21°C for 06:30am and the room temperature is 18°C. The thermostat will start the heating at 06:30am and the room temperature will start to increase then but will switch itself off before it reaches temperature and allow the room temperature to increase naturally this cycle may begin again if the thermostat isn’t reaching temperature.
36
RFRPV2 Room Thermostat CP4V2
P0 2 Setting High & Low Limits Hi 35°C and Lo 5°C
This menu allows the installer to change the minimum and maximum temperatures to between 5…35°C.
Press and hold PROG and
for 5 seconds.
`P01′ will appear on the screen.
Press + until `P02 & HI LO’ appears on the screen.
Press
to select.
`HI’ appears on the screen, the temperature will begin to flash.
Press + or
to select the high limit for the thermostat.
Press
to confirm.
`LO’ appears on the screen, the temperature will begin to flash.
Press + or
to select the low limit for the thermostat.
Press AUTO once to return to the menu or twice to return to normal operation.
RFRPV2 Room Thermostat CP4V2
37
P0 3 Hysteresis HOn and HOFF HOn 0.4°C and HOFF 0.0°C
This menu allows the installer to change the switching differential of the thermostat when the temperature is rising and falling.
If `H On’ is set at 0.4°C and the setpoint is 20°C, then the thermostat will
turn on when the temperature drops below 19.6°C.
If `H OFF’ is set at 0.0°C and the setpoint is 20°C, then the thermostat will turn off when the temperature reaches 20°C.
Press and hold PROG and
for 5 seconds.
`P01′ will appear on the screen.
Press + until `P03 & H On’ appears on the screen.
Press
to select.
`H On’ temperature will begin to flash.
Press + or
to adjust the `H On’ temperature between 0.2°…1°C.
Press
to confirm.
`H OFF’ temperature will begin to flash.
Press + or
to adjust the `H OFF’ temperature between 0.0°…1°C.
Press AUTO once to return to the menu or twice to return to normal operation.
38
RFRPV2 Room Thermostat CP4V2
P0 4 Calibrate the thermostat
This function allows the user to calibrate the temperature reading of
the thermostat.
Press and hold PROG and
for 5 seconds.
`P01′ will appear on the screen.
Press + until `P04 & CAL’ appears on the screen.
Press
to select.
The current actual temperature will appear on screen.
Press + or
to adjust the temperature reading.
Press
to confirm and you will return to the menu.
Press AUTO to return to the home screen.
RFRPV2 Room Thermostat CP4V2
39
P0 5 Frost Protection
5°C
This function allows the user to activate or deactivate frost protection.
Frost protection can be set from 5…15°C.
When frost protection is activated, the thermostat will switch on the boiler
when the temperature drops below the setpoint.
Frost protection is only active in OFF mode and Holiday mode.
Press and hold PROG and
for 5 seconds.
`P01′ will appear on the screen.
Press + until `P05 & Fr’ appears on the screen.
Press
to select. `ON’ will flash on the screen.
You now have two choices:
1. Press
to confirm frost protection,
Press + to select the frost protection temperature between 5…15°C.
Press
to confirm and you will return to the menu.
2. Press + to turn the frost protection OFF.
Press
to confirm and you will return to the menu.
Press AUTO to return to the home screen.
40
RFRPV2 Room Thermostat CP4V2
P0 6 Holiday Function
This function allows the user to switch the thermostat off for a certain
period of time.
Press and hold PROG and
for 5 seconds.
`P01′ will appear on the screen.
Press + until `P06 & HOL’ appears on the screen.
`HOLIDAY FROM’ will appear on screen.
Press + or
to select the year.
Press .
Press + or
to select the month.
Press .
Press + or
to select the day.
Press .
Press + or
to select the hour.
Press .
`HOLIDAY TO’ will appear on screen.
Press + or
to select the year.
Press .
Press + or
to select the month.
Press .
Press + or
to select the day.
Press .
Press + or
to select the hour.
Press .
Press AUTO to return to the home screen.
The thermostat will now return to the mode it was in before the Holiday
settings were entered. To cancel Holiday mode, press
once.
RFRPV2 Room Thermostat CP4V2
41
P 07 Backlight AUTO
There are two settings for selection.
AUTO The backlight is on for 10 seconds after any button press.
OFF
The backlight is permanently OFF.
Press and hold PROG and
for 5 seconds.
`P01′ will appear on the screen.
Press + until `P07 & bL’ appears on the screen.
`AUTO’ will appear on the screen.
Press
to select the AUTO setting or press + to select the OFF
setting.
Press AUTO to return to the home screen.
42
RFRPV2 Room Thermostat CP4V2
P0 8 PIN Lock OFF
This function allows the user to put a PIN lock on the thermostat.
There are two options available.
`OPt 01′. The thermostat is fully locked.
`OPt 02′. This will reduce the functionality of the thermostat.
The user will be able to change the mode between AUTO and OFF.
Set Up the PIN
Press and hold PROG and
for 5 seconds.
`P01′ will appear on the screen.
Press + until `P08 & PIn’ appears on the screen.
Press + . `OFF’ will appear on the screen.
Press + to select ON.
Press . Press + to select OPt 01′ or
OPt 02′.
Press + . `0000′ will flash on the screen.
Press + to set the value for the first digit.
Press
to confirm and move to the next PIN digit.
When the last digit of the PIN is set, press .
RFRPV2 Room Thermostat CP4V2
43
P0 8 PIN Lock Continued
It is necessary to verify the PIN. `vErI’ will appear on the screen. Re enter
the PIN code again. Press . The PIN is now verified and the PIN lock is
activated. If the verification PIN is entered incorrectly the user is brought
back to the menu. When the PIN lock is active, the lock symbol will appear on
the screen. When the thermostat is PIN locked, pressing any button will take
the user to the PIN unlock screen.
44
RFRPV2 Room Thermostat CP4V2
To Unlock the PIN Press any button, UnL’ appears on the screen.
0000′ will
flash on screen. Press + to set the value from 0 to 9 for the first digit.
Press + to move to the next PIN digit. When the last digit of the PIN is set.
Press . The PIN is now unlocked. If a PIN has been unlocked on the thermostat,
it will automatically reactivate if there is no button pressed for 2 minutes.
To Deactivate the PIN
When the PIN is unlocked (see above instructions)
Access PIN in the installer menu.
Press + , `ON’ will appear on the screen.
Press + to select `OFF’.
Press Press
. `0000′ will flash on the screen. Enter the PIN. .
The PIN is now disabled.
RFRPV2 Room Thermostat CP4V2
45
Exit: Exit from Menu
This menu allows the installer to return to the main interface. It is also
possible to exit the installer menu by pressing AUTO , MAN or OFF whilst in
the installer menu.
46
RFRPV2 Room Thermostat CP4V2
PO 9 Setting DHW temperature
This function allows the installer to change the DHW temperature of the boiler.
The temperature can be set in 0.5°C increments by pressing + or .
Press
to select the desired temperature.
This menu is only available when the thermostat is connected to OpenTherm® and DHOP is ON (P11 OT installer menu).
Note: P09 – P12 is only available when the receiver is connected to an OpenTherm® appliance.
RFRPV2 OpenTherm® Instructions
47
P10 OpenTherm® Information
This function allows the installer to view information received from the
OpenTherm® boiler. It may take a few seconds to load information relating to
each parameter. The information that can be shown from the boiler is outlined
in the table below.
Displayed on screen Description
Remark
tSEt tFLO trEt
tdH
tFLU tESt nOdU
Target water temp Outlet water temp Return water temp
DHW temperature
Flue gas temperature Outdoor temperature Modulation percentage
This is only visible if DHOP is On (P08 OT Installer menu)
Dependent on boiler
Dependent on boiler
FLOr
Water flow
This is only visible if DHOP is On (P08 OT Installer menu)
PrES
Water pressure
Dependent on boiler
48
RFRPV2 OpenTherm® Instructions
P11 DHOP
This function allows the installer to activate or deactivate DHW target
temperature control from the thermostat. This menu is only available when the
thermostat is connected to OpenTherm®
P12 Set OpenTherm® Parameters
This function allows the installer to configure the OpenTherm® parameters.
To access the menu please enter the password “08” by pressing + or .
Press
to confirm.
The parameters that can be set are outlined in the table on the next page 50.
RFRPV2 OpenTherm® Instructions
49
P12 Set OpenTherm® Parameters Continued
Param HHCH t-1 LLCH t-2 CLI t-3
InFL t-4
HHbO t-5
Exit
Description
Range
Maximum setpoint heating
45 – 85°C
Minimum setpoint heating
10 – HHCH°C
This allows user to select different climatic curves for weather compensation. This only applies to Boilers with an outside sensor connected.
0.2 – 3.0
Influence of room sensor on modulation of the boiler. Recommended value is 10.
0 – 20
This is the target setpoint for your CH flow temperature. Note: this value must be within the range of HHCH and LLCH.
HHCH Max >=ID57 >=LLCH Min
Press OK button to turn back to main interface.
Default 85°C 45°C 1.2
10
85°C
50
RFRPV2 OpenTherm® Instructions
Climatic Curve
3
2.5
100
2
80 1.5
1.2
60
1
0.8
40
0.6
0.4
0.2
20
20
16
12
8
4
0
-4
-8
-12 -16
Exit
This function allows the installer to return to the main interface. It is also
possible to exit the installer menu by pressing AUTO , MAN or OFF whilst in
the installer menu.
RFRPV2 OpenTherm® Instructions
51
System architecture
Example A CP4V2 controlling OT Boiler
RFRPV2 Thermostat
RF1B Receiver
OpenTherm® Boiler
This function allows the installer to confirm if the thermostat is receiving OpenTherm® information from the boiler.
Press and hold PROG and
for 5 seconds.
`P01′ will appear on the screen.
Press + until `P10 & InFO’ appears on the screen.
If P01 to P08′ is visible and
P10′ does not appear on the screen, the
thermostat is not communicating via OpenTherm®.
Note: To control an appliance with OpenTherm® run a dedicated two core cable from the OpenTherm® connection on the RF1B to the OpenTherm®connection on the appliance.
Note: When connected via OpenTherm® the OpenTherm® LED on the RF1B receiver will be illuminated.
52
RFRPV2 OpenTherm® Instructions
Example B Multiple CP4V2 controlling OT Boiler
RFRPV2 Thermostat
RFRPV2 Thermostat
RFRPV2 Thermostat
25cm
25cm
RF1B Branch Receiver
RF1B Hub Receiver
RF1B Branch Receiver
Motorised Valve
Motorised Valve
Motorised Valve
Note: A maximum of 6 CP4V2 can be used in the system.
OT
Auxiliary switch wire
from motorised valve
OpenTherm® Boiler
RFRPV2 OpenTherm® Instructions
53
Controlling an OpenTherm® Boiler with multiple CP4V2
It is possible to have up to six CP4V2 thermostats controlling one OpenTherm®
boiler. To do this it is necessary to make one of the RF1B receivers into a
Hub Receiver. This Hub Receiver will receive data from all of the RFRPV2
thermostats and relay this information to the boiler via OpenTherm®.
Note: The Hub Receiver should have a wired OpenTherm® connection to the
boiler. When installing multiple receivers – see important on page 15. Making
your RF1B receiver into a Hub Receiver:
1. The RF1B has an LED to indicate if it is a Hub.
2. Press and hold Manual & Connect for 5 seconds to make the receiver a Hub
or Branch.
Note: A Hub receiver is the master receiver in multiple zone installations. A
branch receiver is used for connecting additional zones. See Page 50 for
System Architecture.
Note: A Hub receiver can connect to a GW04 Wi-FI Gateway.
54
RFRPV2 OpenTherm® Instructions
Identifying if a receiver is a Hub Receiver: 1. If the Hub LED is illuminated
the RF1B is a Hub receiver. Pairing the RF1B receivers together: 1. Hold
Connect on the Hub receiver for 3 seconds.
The RF LED will begin to flash. 2. Hold Connect on the next receiver to be
paired. The RF LED
will flash 3 times and then stop. This receiver is now linked. 3. Repeat this
process to pair more, up to a maximum of 6 receivers. 4. Press Manual on the
hub to return to normal operation. Once all units have been paired, allow time
for the receivers to begin to communicate and receive OpenTherm® information
from the boiler. This may take approximately 2 5 minutes. Disconnecting the
RF1B receiver from other Receivers: 1. Hold Manual & Connect on the Hub
receiver until the Hub LED turns off. This will clear the connection to the
branch receivers.
RFRPV2 OpenTherm® Instructions
55
RF1B Wireless Receiver Operating Instructions
56
Button / LED Description
Hub LED
System LED
RF LED OpenTherm LED
Manual override button
Manual Manual override Reset button Press to reset the receiver
Connect button
Reset button
Connect Connect: Once voltage has been applied this button may be held to
initialise the pairing process with the wireless thermostat. Once pressed the
RF LED will begin to flash.
Note: Please refer to Page 14 for wiring information.
RF1B Wireless Receiver
CP4V2
57
LED Description
LED System
Function When the LED is RED the system is OFF. When the LED is GREEN the system is ON.
Hub
Solid White LED Indicating that the receiver is a HUB.
RF
Solid White LED indicating that the thermostat is connected.
The RF light will double flash when the thermostat is disconnected. Check thermostat pairing.
Note:
The RF light will blink intermittently when the system is sending and receiving a signal for communication.
Note:
The RF light will blink once every second when in RF pairing by holding Connect. Press Manual to exit from this state.
Opentherm® Solid White LED indicating that Opentherm® is connected.
The Opentherm® LED will blink when there is an Opentherm® communication error.
58
RF1B Wireless Receiver
CP4V2
To connect the RFRPV2 Thermostat to an RF1B receiver
When installing a CP4V2, the RFRPV2 thermostat and the RF1B receiver will have a pre-established RF connection so it is not necessary to carry out the RF connection process below.
On the RF1B receiver:
Hold Connect for 3 seconds.
The RF LED will begin to flash. On the RFRPV2 thermostat:
Press the connect button on the side of the thermostat.
The thermostat will show nOE’ followed by
—‘
Once an RF connection has been established the thermostat will show `r01’ on
the LCD screen.
Press
to finish the process.
The thermostat is now connected to the RF1B receiver.
CP4V2
59
Pairing your RF1B Receiver to your GW04 Gateway
Note: Your CP4V2 can be controlled remotely via the EMBER app with the
addition of a GW04 Gateway.
Ensure that your RFRPV2 thermostat(s) are paired to your RF1B receiver(s).
Ensure that the receiver you’re connecting to the boiler is set up as a Hub
receiver:
On the RF1B receiver:
Hold Manual & Connect for 5 seconds.
The Hub LED will illuminate. The receiver is now a HUB.
Hold Connect on the RF1B until RF LED flashes.
On the GW04 Gateway:
Hold the RF Connect button until RF LED flashes.
The gateway & receiver will stop flashing. Paring is now complete.
The white RF light on the GW04 will stay illuminated.
Note: If you are connecting multiple receivers to a GW04 Gateway, please
ensure that all branch receivers are connected to the hub receiver. There can
only be 1 hub receiver in a system. Allow 5 minutes for all receivers to
synchronise with the hub receiver before connecting the gateway to the EMBER
App. See page 52 & 53.
60
RF1B Wireless Receiver
CP4V2
To disconnect the RFRPD Thermostat from an RF1B receiver
This can be done from either the RFRPV2 thermostat or the RF1B receiver.
On the RFRPV2 thermostat:
Press connect button on the side of the thermostat,
`–‘ will appear on the screen.
Hold TIME for 10 seconds, `ADDR’ appears on screen,
Press
2 times to return to the normal screen the thermostat is
now disconnected.
On the RF1B receiver: Press Connect for 3 seconds to enter pairing mode, Press Connect for 10 seconds and System LED will turn on, Press Manual to exit, the thermostat is now disconnected.
CP4V2
61
Service Interval OFF
The service interval gives the installer the ability to put an annual
countdown timer on the timeswitch. When the Service Interval is activated
`SErv’ will appear on the screen which will alert the user that their annual
boiler service is due.
For details on how to enable or disable the Service Interval, please contact
customer service.
62
CP4V2
Notes
CP4V2
63
EPH Controls IE
technical@ephcontrols.com www.ephcontrols.com/contact-us +353 21 471 8440
Cork, T12 W665
EPH Controls UK
technical@ephcontrols.co.uk www.ephcontrols.co.uk/contact-us +44 1933 322 072
Harrow, HA1 1BD
©2024 EPH Controls Ltd. 2024-06-07_CP4-V2_Instructions_PK
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>