RECTORSEAL Aquaguard AG-1200 plus Switch Installation Guide
- July 31, 2024
- Rectorseal
Table of Contents
- Aquaguard AG-1200 plus Switch
- Specifications:
- Product Usage Instructions:
- Installation of Float Switch on Drain Pan:
- Wiring the AG-1200+ in a Conventional HVAC System:
- Wiring the AG-1200+ in a Communicating HVAC System:
- Q: Who should install the AquaGuard AG-1200+?
- Q: How often should the device be inspected?
Aquaguard AG-1200 plus Switch
“`html
Specifications:
-
Product: AquaGuard AG-1200+ Magnetic Float Switch
-
Installation: Must be done by or under the direct supervision
of a licensed contractor -
Maintenance: Condensation pan must be properly maintained and
kept free from obstructions -
Power: Ensure power is disconnected before installation
Product Usage Instructions:
Installation of Float Switch on Drain Pan:
-
Disconnect power to unit at main panel and low voltage
thermostat circuit. -
Loosen the three thumb screws and slide the float switch onto
the side of the pan at the lowest point. -
Tighten the thumb screws to secure the switch in place.
-
Secure switch wires to prevent interference with float
operation.
Wiring the AG-1200+ in a Conventional HVAC System:
-
Ensure power is disconnected at the main panel.
-
Test switch responsiveness by filling the pan with water to
verify the switch stops the unit before overflow. -
Place the ATTENTION sticker on the unit for visibility.
-
Inspect, clean, and test the device every 180 days and after
cleaning the drain line.
Wiring the AG-1200+ in a Communicating HVAC System:
Refer to the equipment manufacturer’s recommendations for
specific wiring instructions.
FAQ:
Q: Who should install the AquaGuard AG-1200+?
A: It must be installed by or under the direct supervision of a
licensed contractor.
Q: How often should the device be inspected?
A: The device should be inspected, cleaned, and tested every 180
days and after cleaning the drain line.
“`
INSTALLATION INSTRUCTIONS
AQUAGUARD® AG-1200+
Wiring the AG-1200+ Magnetic Float Switch
WORK SAFE, READ THIS
Failure to read and comply with all warnings, cautions and instructions prior
to starting installation may cause personal injury and/or property damage and
void warranty.
Remove electrical shock hazard DISCONNECT THE POWER BEFORE INSTALLATION to
avoid electrical shock and/or equipment damage. Do not use on circuits
exceeding 24 volts to avoid damage to switch, shock or fire hazard.
NNOOTTIICCEE In any installation where property damage and/or personal injury
might result from an inoperative switch due to power outages, a back-up
system(s) and/or alarm should be installed.
NNOOTTIICCEE The AquaGuard AG-1200+ must only be installed by or under the
direct supervision of a licensed contractor. Condensation pan must be properly
maintained after installation and be kept free from foreign objects, rust or
other obstructions that might interfere with the proper operation of the
AquaGuard float switch.
STOP/READ This device must be installed in accordance with manufacturer’s
instructions. This unit must be in accordance with all applicable local
plumbing, drainage and electrical codes.
STOP/READ Clean surface with alcohol pad before mounting with adhesive tape.
INSTALLATION OF FLOAT SWITCH ON DRAIN PAN:
(To ensure proper performance of product, instructions must be followed.)
1. Disconnect power to unit at main panel. Disconnect power to the low voltage
thermostat circuit.
2. Loosen the three thumb screws (fig.1). Unscrew the top thumb screw until the
clamp separates.
3. Slide the float switch onto the side of the pan at the lowest point on the pan.
4. Finger tighten the top thumb screw first, then the bottom two.
((fFiigg..11))
5. Secure switch wires so they will not affect the operation of the float.
Thumb screw
WIRING THE AG-1200+ in a Conventional HVAC System:
(To ensure proper performance of product, instructions must be followed.) 1.
Ensure the power is disconnected to the unit at the main panel prior to moving
to step 2. Refer to the
appliance manufacturer’s installation and operating instructions and also
review wire layout in their instructions. 2. Locate the red wire coming from
the 24 volt thermostat “R” terminal. 3. Disconnect or cut red wire. Connect
the Normally Closed non-ribbed wire of the switch, using a wire nut, to the
thermostat side of the circuit. Connect the Common ribbed wire of the switch,
using a wire nut, to the air handler side of the circuit or to terminal in
unit. Incorporating both switch wires in the red circuit will shut the unit
completely off. 4. Test the switch. (At start-up, check initial amperage
load.) A. With unit on, test switch by pulling the float pin up. (fig. 2)
Unit should stop running if switch is correctly wired. B. To test switch
responsiveness, fill pan with water to ensure that the switch stops the unit
before the pan
overflows. Remove water. 5. Place the ATTENTION sticker on unit in a clearly
visible location. (fig. 3)
PPulul lplinpiunputoptteosttest swswitcithch
Unit is equipped with an AquaGuard condensate shut-off switch. If A/C unit is
not operating, check for condensate in drain pan or tray.
Inspect, clean and test the device every 180 days and following each cleaning
of the drain line.
R50118-0624
(Fig. 3)
(Fig. 2)
6. For wiring the normally open third wire (short wire) refer to the following diagrams:
Standard HVAC installation w/optional external alarm or accessory
Optional HVAC installation for breaking Compressor Yellow wire w/optional external alarm or accessory
Thermostat C R
24Vac transformer 24Vac common
24Vac hot
Thermostat
C Y
24Vac transformer 24Vac common
White/Red stripe White/Red stripe
NC-Non-Ribbed Common-Ribbed
NO-Short wire (If not used, wire nut and tape)
White
AG 9100
Remote alarm
Common-Ribbed NC-Non-Ribbed NO-Short wire (If not used, wire nut and tape)
White
HVAC condenser unit
AG 9100
Remote alarm
WIRING the AG-1200+ in a Communicating HVAC System:
1. See equipment manufacturer’s recommendations for specific wiring
instructions.
24 Volt AC, 5 Amp, GP, Use in Class 2 (Thermostat) Circuit Only
Manufactured by RectorSeal, LLC 2601 Spenwick Drive Houston, TX 77055, USA
800-231-3345 rectorseal.com A CSW
Industrials Company. RectorSeal, the logos and other trademarks are property
of RectorSeal, LLC, its affiliates or its licensors and are protected by
copyright, trademark and other intellectual property laws, and may not be used
without permission. RectorSeal reserves the right to change specifications
without prior notice. ©2024 RectorSeal. All rights reserved. R50963-0624
INSTRUCCIONES DE INSTALACIÓN
AQUAGUARD® AG-1200+
Cableado del AG-1200+ Interruptor de flotador magnético
¡Trabaje seguro, LEA ESTO!
ADVERTENCIA El fracaso de no leer toda las precauciones, advertencias e instrucciones antes de comenzar la instalación puede causar riesgo de lesiones personales y/o daño a su propiedad y podrá perder su garantía.
ADVERTENCIA Desconecte la electricidad antes de instalar AquaGuard para evitar un posible corto circuito o daño al producto. No debe utilizarce en circuitos que excedan 24 voltios para evitar daño al interruptor, golpe eléctrico o riesgo de fuego.
NOTAR En cualquier instalación donde haya riesgo de lesiones personales o a su
propiedad debido a un interuptor inoperante, se debe correjir con un sistema
de alarma.
NOTAR El AquaGuard debe ser instalado por un contratista licenciado o bajo la
supervisión directa de un persona adecuada. La bandeja de condensacion debe
ser mantenerse en buenas condiciones despues de la instalacion y mantenerla
alejada de objetos extranos, oxido u otras circunstancias que puedan
interferer con el buen funcionamiento del dispositivo de AquaGuard.
DETENER/LEER Este dispositivo debe ser instalado en conformidad con las instrucciones del fabricante. Esta unidad debe estar conforme con todos los códigos de instalación de cañería, desague y códicos eléctricos.
DETENER/LEER Limpe la superfice con pano de alcohol antes de montar con cinta
pegante.
DETENER/LEER
INSTALACION DEL INTERRUPTOR DE FLOTA EN LA BANDEJA DE DESAGUE:
(para asegurar el buen funcionamiento del producto, se deben seguir correctamente las siguientes instrucciones):
1. Desconecte la electricidad del interruptor de la caja eléctrica principal. Desconecte el poder a bajo voltaje en el
circuito del termostato.
2. Afloje los tres tornillos de pulgar (fig.1). Desatornille el tornillo de pulgar superior hasta
que la abrazadera se separe. 3. Deslice el interruptor de flotador sobre el
lado de la cacerola en el punto más bajo en
la cacerola.
Tuerca de dedo
4. El dedo aprieta el tornillo de pulgar superior primero, entonces los dos inferiores. 5. Asegure los alambres del interruptor así que no afectarán a la operación del flotador. (fig.1)
(Fig. 1)
CABLEADO DEL AG-1200+:
(para asegurar el buen funcionamiento del producto, se deben seguir correctamente las siguientes instrucciones):
1. Asegure que la electricidad esta desconectada antes de seguir las próximas instrucciones. Refiérase a las instruc-
ciones de instalación de la unidad del aire acondicionado o la refrigeración y también revise la disposición de
alambre de revisión en su manual de instrucciones.
2. Localice el cable rojo que proviene de los terminales del termóstato (circuito de enfriamiento) “R” de 24 voltios.
3. Desconecte o corte el alambre rojo. Conecte el cable no crucería del aparato, usando una tuerca de alambre, al lado
del termostato del circuito. Conecte el cable del interruptor de crucería, con una tuerca para cable, a un lado el
ventilador de aire del circuito o terminal en la unidad. La incorporación de los cables del interruptor en el circuito
rojo se apagará completamente la unidad.
4. Pruebe el interruptor. (Al arrancar compruebe la carga del amperaje inicial)
A. Pruebe el interruptor levantando el flotador mientras la unidad este puesta y/o encendida. (fig.2) La unidad
debe parar de funcionar si las conecciones de alambres al interuptor estan correctamente instaladas.
B. A la cacerola del terraplén de la sensibilidad del interruptor de prueba con agua para asegurarse de que el inter-
ruptor pare la unidad antes de que desborde la cacerola. Quite el agua.
5. Ponga el stike de ATENCION en una locacion visible y clara. (fig. 3)
((fFiigg..22) )
Pruebe el interruptor jalando el aPlfriuleerbe el interruptor jalando el alfiler
Unit is equipped with an AquaGuard condensate shut-off switch. If A/C unit is
not operating, check for condensate in drain pan or tray.
Inspect, clean and test the device every 180 days and following each cleaning
of the drain line.
R50118-0624
(Fig. 3)
6. Para el tercer cable del cableado normalmente abierto (alambre corto) se refieren a los siguientes
diagramas:
Instalación HVAC estándar con alarma externa opcional o accesorio
Instalación HVAC opcional para romper el cable amarillo del compresor con alarma externa opcional o accesorio
Termostato C R
24Vac transformador 24Vac común
24Vac caliente
Termostato
C Y
24Vac transformador 24Vac común
Franja blanca/roja Franja blanca/roja
NC-No acanalado
Acanalado común
NO-Cable corto (Si no se utiliza, tuerca de
alambre y cinta)
Blanco
AG 9100
Alarma remota
Acanalado común
NC-No acanalado
NO-Cable corto (Si no se utiliza, tuerca
de alambre y cinta)
Blanco
HVAC Unidad condensadora
AG 9100
Alarma remota
EL CABLEADO de AG-1200+ en un sistema de comunicación HVAC:
1. Ver las recomendaciones del fabricante para obtener instrucciones
específicas del cableado.
24 voltios CA, 5 amperios, GP, uso en circuito de clase 2 (termostato)
únicamente
Manufactured by RectorSeal, LLC 2601 Spenwick Drive Houston, TX 77055, USA
800-231-3345 rectorseal.com A CSW
Industrials Company. RectorSeal, the logos and other trademarks are property
of RectorSeal, LLC, its affiliates or its licensors and are protected by
copyright, trademark and other intellectual property laws, and may not be used
without permission. RectorSeal reserves the right to change specifications
without prior notice. ©2024 RectorSeal. All rights reserved. R50963-0624
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>