Specifications
- Product: Reinforcement Strip
- Reference(s): 350 461/466/464
Frequently Asked Questions
Q: What is the purpose of the reinforcement strip?
A: The reinforcement strip is designed to enhance the rigidity of installations like Cablobend when necessary.
Q: What are the different material characteristics of the PG, HR, and SS316L strips?
A: The PG strip has a resistance class of Class 3 against corrosion, the HR strip has a resistance class of Class 8, and the SS316L strip has a resistance class of Class 9D.
USE
A flexible band that reinforce the rigidity of Cablobend and other installations when needed
RANGE
Designation
| ****
Code
| ****
Thickness
| Weight
---|---|---|---
mm| Inch| Kg/m| Ib/m
REINFORCEMENT STRIP PG| 350 461| ****
1,5
| ****
0,06″
| 0,192| 0,423
REINFORCEMENT STRIP HR| 350 466
REINFORCEMENT STRIP 316L| 350 464| 0,195| 0,430
DIMENSIONS (mm/inch)
INSTALLATION
Reinforcement strip on external radius
Reinforcement strip on external radius of flat bend 90°
W
|
R Ext
| L Reinforcement Strip
---|---|---
(mm)| (inch)| (mm)| (inch)| (mm)| (inch)
100| 3,94| 325| 12,80| 1161| 45,69
150| 5,91| 445| 17,52| 1349| 53,11
200| 7,87| 495| 19,49| 1428| 56,20
300| 11,81| 670| 26,38| 1702| 67,02
400| 15,75| 840| 33,07| 1969| 77,54
450| 17,72| 960| 37,80| 2158| 84,96
500| 19,69| 1010| 39,76| 2237| 88,05
600| 23,62| 1200| 47,24| 2535| 99,80
TECHNICAL DATA
Material characteristics
Coating| Resistance class against corrosion| Raw material|
Standard
---|---|---|---
PG| Class 3 / IEC 61537| DX 51 D Z275 MAC| EN 10346
HR| Class 8 / IEC 61537| S 235 JR| EN 10025
SS316L| Class 9D / IEC 61537| X2 Cr Ni Mo 17-12-2| EN 10088-2
Climatic characteristics
Storage and operating temperature : – 20° C à + 120°