L0001724 Control Valves DucoBox Focus Instruction Manual

July 26, 2024
Duco

Quick Start
Control valve

L0001724-D 15.02.2024

Control valves, which may or may not feature an optional sensor for CO2 or humidity measurement, ensure that only stale and/or moist air is extracted, where and when necessary as well as at the right rate.

Wiring

Connect the ‘VALVE’ connector on the DucoBox to IN on the control valve. If applicable, connect OUT on the valve to IN on another control valve to be added. At least one valve must be connected to the DucoBox at any time (see illustration).

TIP: Use the letter labels on the DucoBox and the valves (A/B/C/D/E/F/G) to give these the same letter, so that the valves always remain in the same position.

Electronical installation

02.A Pairing

  1. Enter ‘installer mode’ by pressing the ‘INST’ button on the DucoBox. (see illustration below)

  2. The valves are paired automatically and the led on the relevant valve will flash green slowly.
    Proceed with steps 3-4 to add an underlying component to the valve optionally.

  3. Press the control valve button until the led flashes green rapidly.

  4. Add the underlying component by pressing the button on the relevant component.

  5. Once everything has been added to the network, exit ‘installer mode’ by pressing the ‘INST’ button on the DucoBox.

PHYSICAL REMOVAL

  1. The valve must be in the fully shut position to remove it from the DucoBox. Short-press the valve button in order to drive it shut for 15 minutes.
  2. Disconnect the wiring.
  3. Slide the valve out of the DucoBox.
    Take care to ensure that it is inserted back in the same location. Use the letter labels on the DucoBox and the relevant valve for this.

Removing paired components from the network or replacing is only possible within 30 minutes after the component is paired or is restarted. Restarting can be done by disconnecting the power for a moment. After a timespan of 30 minutes, remove and replace operations are ignored. This is valid for all components from date of manufacture 170323.

UNPAIRING

  1. Enter ‘installer mode’ either by pressing the ‘INST’ button on the DucoBox or by long-pressing the button on the valve until the green LED flashes slowly.
  2. Now press the control valve button again until the LED flashes red slowly.
    All underlying components will lose their connection with the network.

REPLACEMENT

  1. Enter ‘installer mode’ either by pressing the ‘INST’ button on the DucoBox or by long-pressing the button on the valve until the green LED flashes slowly.
  2. Now short-press the control valve button again twice until the LED flashes red slowly.
  3. Add the new valve (see “pairing”). The latter will take on all settings/ connections in the network.

LED INDICATIONS

| RED (blinking slowly)
Not in network
RED (blinking rapidly)
Logging in
---|---
| GREEN (blinking slowly)
In network
GREEN (blinking rapidly)
In network, waiting for associated components
| YELLOW (clignotement rapide)
Transitional phase (please wait
YELLOW (on)
Initialising (system configuration in progress)
| WHITE or OFF
Valve is operating normally (brightness indicates the flow rate through the valve: bright = max. flow rate, medium = half
flow rate, off = lowest flow rate)
| BLUE
Component is displayed if changes are being put through via the master.

Settings

The settings for the relevant component can be entered using the DucoBox (see DucoBox manual), Duco Network Tool or Duco Installation App.
Translation of the original instructions See www.duco.eu for information regarding warranty, maintenance, technical data, etc. Installation, connection, maintenance and repairs should be done by a recognised installer. The electronic components of this product may be live. Avoid contact with water.

Vero DUCO – Handelsstraat 19 – 8630 Veurne – Belgium
tel +32 58 33 00 33 – info@duco.euwww.duco.eu

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals